Pump screen 2 sets the pressure transducer settings
for the pump.
Figure 63 Pump Screen 2, Default Settings Enabled
Figure 64 Pump Screen 2, Default Settings Disabled
Default
Default
Default Settings
Settings
Settings Selected
Selected
Selected
When the “Use Default Settings” box is selected,
default settings are used for the calibration values,
and the fields are grayed out.
Default
Default
Default Settings
Settings
Settings Not
Not
Not Selected
Selected
Selected
When the “Use Default Settings” box is not selected,
the following calibration values must be entered.
Invalid values will be over-ridden and the system will
automatically select the default settings.
• Inlet Offset Factor: This field is only used if Inlet
Inlet
Inlet
Pressure
Pressure
Pressure in
is set to
Monitor; it is grayed out if set to Disabled. The
valid range is -01.20 to +01.20 mV/V.
• Inlet Sensitivity Factor: This field is only used if
Inlet
Inlet
Inlet Pressure
Pressure
Pressure in
is set
to Monitor; it is grayed out if set to Disabled. The
valid range is 18.80 to 21.20 mV/V.
• Outlet Offset Factor: The valid range is -01.20 to
+01.20 mV/V.
• Outlet Sensitivity Factor: The valid range is 18.80
to 21.20 mV/V.
86