3A5856A
Advanjet HV-2000C Jet Controller Setup and Operation
Page 43 of 60
Appendix 2: Temperature Controller Factory Settings
The CN740 Temperature
Controller manual is included with your Advanjet controller shipment.
Please refer to it for specific instructions.
Listed below are factory set values programmed by Advanjet to work with the HV-2000C
controller and the HV-2000 Jet Nozzle plate for the majority of applications. It is strongly
recommended that users do not modify these values.
Use the
keys to adjust values. Press
once to save changes, and press
again to return to the previous menu.
OPERATION
Description
Setting
Value
Press
Control Run/Stop setting
r-S
Upper-limit alarm 1
AL1H
3
Lower-limit alarm 1
AL1L
3
Upper-limit alarm 2
AL2H
3
Lower-limit alarm 2
AL2L
3
LOC
oFF
REGULATION
Description
Setting
Value
Press
once, then press
PB (Proportional band)
P
4
Ti (Integral time)
i
20
Td (Derivative time)
d
5
Default value of Integral Volume
ioF
0
Heating Control Cycle Setting
HtPd
10
Process Temperature Offset
tPoF
0
INITIAL SETTINGS
Description
Setting
Value
Press and hold
Input temperature sensor type
inPt
Pt2
Temperature unit display selection
tPUn
C
Upper-limit of temperature range
tP-H
75
Lower-limit of temperature range
tP-L
-20
Control method
Ctrl
PiD
Heating/Cooling control Selection
S-HC
HEAt
Alarm 1 type
ALA1
1
Alarm 2 type
ALA2
1
Data Format
C-5L
ASCII