Advanced Programming
34
332298J
Models with Firmware 6.03 and
later. DMS Models with
Firmware 7.07 and later.
A10 - Low Level Reset Upon Power On.
This function changes the behavior of the low level upon
pump power on. When A10 is on, a low level fault clears when
the pump power is cycled. The pump will revolve 5 revolu
-
tions, checking to see if the low level condition is still present.
If not, it will self clear and continue. If a low level condition
exists during the 5 revolutions, it will go into a low level fault.
Low Level ON LED illuminates (F
. 29).
1. The default OFF is displayed.
The alarm output will toggle
once a second.
2. Press the UP or DOWN
ARROW button to change OFF
to ON on the display to change
the low level reset upon power
on.
3.
Press the ENTER button.
A11- Warning Off Through Alarm Relay
This function changes the behavior of the alarm output in a
warning condition to always off.
Fault and Warning LEDs Illuminate
1.
The default OFF is dis
-
played. The alarm out
-
put will turn on during a
warning condition.
2.
Press the UP or DOWN ARROW
to change OFF to ON on the dis
-
play to change the alarm output
to be off during a warning condi
-
tion.
3. Press the ENTER button to exit Advanced
Programming.