16
Gossen Metrawatt GmbH
Memory Duration as a Function of Number of Channels I
4.2
Synchronizing-Interval Data Logger
The energy values which have been measured during a given interval can be stored to a
data logger. This interval (duration: 10 s .. 999 hr., default: 15 minutes) is either derived
from system time, or the interval limit is determined with a trigger pulse slope (default:
channel 11). Energy measured during this interval (EINT) is entered into a list along with
the time and the date. The mean power value occurring within the interval (PINT) is
calculated based upon EINT and the duration of the corresponding interval.
Formatting the Data Logger
Attention!
!
The contents of the data logger are deleted during formatting.
The number of records in the data logger depends upon the number of channels. Thus
the data logger can be formatted in accordance with the desired number of channels.
Formatting can only be performed with an interpreter. Data area resolution is also
defined simultaneously (ECL command: FORMAT).
Defining the Number of Records
The format command reserves adequate space for the selected number of channels in
system memory. The greatest possible number of records is thus determined, but not
memory duration which is solely dependent upon the duration of the interval.
Example: Only channels 1 ... 4, channel 17 and channels 21 .. 23 are to be recorded to
the data logger.
If the format command is called up without parameters, status information is read out to
the data logger. Most importantly, the number of records which can be entered to the
data logger is shown here.
<A> FORMAT = 1...4 + 17 + 21 ... 23
<A> format
Format(0): 8 channels, 26214 records (= 273 days, with a 15 min. interval)
Channels: 1;2;3;4;17;21;22;23
Number of Channels
Number of Records
Memory Duration in Days
with a 15 minute interval
2
65535
682
8
26214
273
16
14563
151
24
10082
105
32
7710
80
40
6241
65
48
5242
54
56
4519
47
64
3971
41
<A> FORMAT=1..4+17+21..23
Summary of Contents for U1601
Page 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Page 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Page 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Page 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Page 79: ...Gossen Metrawatt GmbH 79 ...