24
Gossen Metrawatt GmbH
5.6
In-Service Function
An error bit is used in order to inform the analysis software that a channel is not reading
out valid data because, for example, it is currently being calibrated (ErrChan 24:
inservice). The in-service function is activated by configuring the in-service feature:
Example: INSERVICE FEATURE = 3
This function is only active per channel in mode 4=LON.
In-service can be configured with CHANNEL DATA under SETUP in menu 4:
InService OFF / InService ON / ALL OFF
The *ERIS enumeration is used specifically with the in-service function.
Example: All, Channel& *eris reads out all channels with the in-service status.
1)
is only shown when function InService is activated.
In-Service
Explanation
0
In-service not available (default setting)
1
In-service available
3
Same as 1, but direct jumping from the individual basic display to
SETUP CHANNEL menu 4 is also possible by pressing the F4 key
5
Same as 1, but in-service can only be activated for one channel
7
Same as 3, but in-service can only be activated for one channel
–SETUP
MODE:LON-ANA
INSERVICE
PULSE TIME
TRIGGER EDGE
ON
50 ms
1:__--
CHANNEL
Menu 4
In-service activation is indicated in
the individual basic display.
Z1: U1601Hebl
12:32:10
Channel 21
Select
0.014 kW
Z1: U1601Hebl
12:32:10
21¦U1661.1 ¦ ¦LonA
ETot
Pmom
15.615 kW
<<<<In-Service ON >>>>
Cold Water T4
Channel
1)
Summary of Contents for U1601
Page 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Page 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Page 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Page 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Page 79: ...Gossen Metrawatt GmbH 79 ...