Goodman CONDENSING UNIT HEAT PUMP Installation & Service Reference Download Page 9

9

3. Check subcooling and superheat. Systems with TXV

application should have a subcooling of 5 to 7°F and
superheat of 7 to 9 °F.

a.

If subcooling and superheat are low, 

adjust

 TXV to 7

to 9 ºF superheat, then check subcooling.

NOTE:

 To adjust superheat, turn the valve stem clock-

wise to increase and counter clockwise to decrease.

b.

If subcooling is low and superheat is high, 

add 

charge

to raise subcooling to 5 to 7 °F then check super-
heat.

c.

If subcooling and superheat are high, 

adjust

 TXV

valve to 7 to 9 ºF superheat, then check subcooling.

d.

If subcooling is high and superheat is low, 

adjust

TXV valve to 7 to 9 ºF superheat and 

remove 

charge

to lower the subcooling to 5 to 7 ºF

NOTE:

 Do 

NOT 

adjust the charge based on suction

pressure unless there is a gross undercharge.

4. Disconnect manifold set, installation is complete.

SUBCOOLING FORMULA = SAT. LIQUID TEMP. - LIQUID

LINE TEMP.

NOTE:

Check the Schrader ports for leaks and tighten valve

cores if necessary. Install caps finger-tight.

H

EAT

 P

UMP

 - H

EATING

 C

YCLE

The proper method of charging a heat pump in the heat mode
is by weight with the additional charge adjustments for line
size, line length, and other system components.  For best
results on outdoor units with TXVs, superheat should be 2-5°
at 4-6" from the compressor.  Make final charge adjustments
in the cooling cycle.

A

DDITIONAL

 N

OTES

1. There are (4) LEDs on the PCB. Refer to the

Troubleshooting chart at the end of this manual for
definitions of the LED status.

2. “TERM” dip switch is used for communications bus

configuration. Leave the settings to the factory default
position.

3. “LEARN” push button is used in communication mode

to support device recognition on start-up. As the
communication system supports automatic identification
of both indoor unit and outdoor unit, this button is not
used for a normal start-up.

4. Press “TEST” push button, during system “Standby”

mode to turn on both the compressor and outdoor fan
for five seconds.

5. Press “RECALL” push button to retrieve the six most

recent faults. The control must be in Standby Mode (no
thermostat inputs) to use the feature. Depress the push
button for approximately two seconds and less than five
seconds. The LEDs will then display the six most recent
faults beginning with the most recent faults beginning
with the most recent fault and decrementing to the least
recent fault. The faults may be cleared by depressing
the button for greater than five seconds. Consecutively
repeated faults are displayed a maximum of three times.

Refer to the fault code definitions at the end of this manual
for more details.

6. A forced defrost can be initiated by pressing “TEST” and

“RECALL” push buttons simultaneously for more than 1
second with a valid call for heat. The forced defrost can
be terminated by

A 10 minute lapse in time,

A coil temperature rise above 75°F or

By pressing the two buttons again for more than 1
second.

C

OMFORT

N

ET

™ S

YSTEM

O

VERVIEW

The ComfortNet system (or CT system) is a system that in-
cludes a ComfortNet compatible air handler/furnace/modu-
lar blower and air conditioner or heat pump with a CTK0*AA
thermostat.  Any other system configurations are considered
invalid ComfortNet systems and must be connected as a tra-
ditional (or legacy) system.  The following table compares
the valid CT systems.

CT compatible

Air Handler/Furnace/Modular 

Blower

CT compatible

Air Conditioner

Full CT system

benefits & features

CT compatible

Air Handler/Furnace/Modular 

Blower

CT compatible

Heat Pump

Full CT system

benefits & features

A ComfortNet heating/air conditioning system differs from a
legacy/traditional system in the manner in which the indoor
unit, outdoor unit and thermostat interact with one another.
In a traditional system, the thermostat sends commands to
the indoor and outdoor units via analog 24 VAC signals.  It is
a one-way communication path in that the indoor and out-
door units typically do not return information to the thermo-
stat.
On the other hand, the indoor unit, outdoor unit, and thermo-
stat comprising a ComfortNet system “communicate” digitally
with one another.  It is now a two-way communications path.
The thermostat still sends commands to the indoor and out-
door units.  However, the thermostat may also request and
receive information from both the indoor and outdoor units.
This information may be displayed on the CT thermostat.  The
indoor and outdoor units also interact with one another.  The
outdoor unit may send commands to or request information
from the indoor unit.  This two-way digital communications
between the thermostat and subsystems (indoor/outdoor unit)
and between subsystems is the key to unlocking the benefits
and features of the ComfortNet system.
Two-way digital communications is accomplished using only
two wires.  The thermostat and subsystem controls are pow-
ered with 24 VAC.  Thus, a maximum of 4 wires between the
equipment and thermostat is all that is required to operate the
system.

Summary of Contents for CONDENSING UNIT HEAT PUMP

Page 1: ...the 10 Year Unit Replacement Limited Warranty and the 10 Year Parts Limited Warranty for Goodman branded products online registration must be com pleted within 60 days of installation Online registrat...

Page 2: ...for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clear ance Corner in...

Page 3: ...ant tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lin...

Page 4: ...ean any copper oxide present from the inside of the refrigerant lines and spread it throughout the system This may cause a blockage or failure of the metering device 3 After brazing quench the joints...

Page 5: ...CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK WIRING MUST CONFORM WITH NEC OR CEC AND ALL LOCAL CODES UNDERSIZED WIRES COULD CAUSE POOR EQUIPMENT PERFORMANCE EQUIPMENT DAMAGE O...

Page 6: ...ING THERMOSTAT 1 2 R C B L U E R E D W H T B L K INDOOR UNIT Communicating Thermostat with Low Voltage Wires to Heat Pump NOTE If the heat pump unit is wired in the communicating mode together with th...

Page 7: ...L R G W BL BR G W2 C R G W BL INDOOR UNIT 18 GA 7 WIRE NEEDED WHEN TWO OT ARE USED SEE NOTE 4 RED GREEN WHITE BLUE C W2 O Y1 Y2 G R E O Y1 Y2 HEAT PUMP W2 C R TYP H P ROOM THERMOSTAT 18 GA 7 WIRE SYST...

Page 8: ...or 10 minutes for fixed orifices and 20 minutes for expansion valves CHARGE VERIFICATION REFRIGERANT UNDER PRESSURE DO NOT OVERCHARGE SYSTEM WITH REFRIGERANT DO NOT OPERATE UNIT IN A VACUUM OR AT NEGA...

Page 9: ...e cleared by depressing the button for greater than five seconds Consecutively repeated faults are displayed a maximum of three times Refer to the fault code definitions at the end of this manual for...

Page 10: ...ooling Heating M odels CTK0 AAWIRING NOTE Refer to section Electrical Connections High Voltage Connections for 208 230 volt line connections to the air conditioner or heat pump NOTE A removable plug c...

Page 11: ...first sub menu is then displayed See tables below for listing of furnace sub menus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will a...

Page 12: ...itioner or heat pump model number Serial Number SER NUM Displays the air conditioner or heat pump serial number Optional Software SOFTWARE Displays the application software revision IDENTIFICATION Sub...

Page 13: ...econds Selects the indoor blower heat OFF delay applies to heat pump only Defrost Interval DEFROST 30 60 90 or 120 minutes default is 30 minutes Selects the time interval between defrosts applies to h...

Page 14: ...t the network may arise The integrated control module has some on board tools that may be used to trouble shoot the network These tools are red communications LED green receive Rx LED and learn button...

Page 15: ...blocks are securely twisted together prior to inserting into terminal block Verify heat pump installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal ne...

Page 16: ...ED SUCTION PRESSURE TEMPERATURE CHART SATURATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 9...

Page 17: ...Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrig...

Page 18: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Page 19: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Page 20: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Page 21: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Page 22: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Page 23: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Page 24: ...prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrated control module diagnostic status LED s display the...

Reviews: