LMS MG PIR CLS SENSOR-R

B29004001

307127

Presence detectors

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Circular detection area 360° (up to 491 m

2

 

Restriction of detection area with cover clips

 

Automatic lighting control with constant lighting control 
or switching operation 

 

Lighting dimmable in switching operation with or wit-
hout effect of daylight

 

Orientation light (standby function)

 

DALI solution for up to 3 flexibly addressable lighting 

channels

 

Easy, intuitive configuration of DALI groups

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs

 

Adaptable 3-channel light measurement

 

Calibration of brightness measurement

 

Fully or semi-automatic operation, switchable

 

Brightness setpoint value adjustable in lux

 

Teach-in function via remote control or button

 

Self-learning time delay

 

Reduction of time delay when present briefly (short-term 

presence)

 

Detection sensitivity configurable

 

Connection option for up to 3 conventional buttons for 
manual dimming and switching

 

Flexible assignment of buttons to required lighting chan

-

nel by remote control

 

Behaviour upon button operation selectable

 

Scene functionality

 

Easy configuration of the energy-saving response with 

“eco plus” function

 

Test mode for checking function and detection area

 

Light test mode for checking the brightness threshold

 

Extension of detection area via Master/Master switching

 

Protection rating IP 54 (installed)

 

Ceiling installation in flush-mounted box

 

Accessories

: Surface mounting on ceilings possible with 

back box LMS MG SURFACE MNT FRAME (B29011002), 
optional; user remote control LMS MG USER REMOTE 
(B29012001), optional; app remote control LMS MG 
PROGRAM REMOTE BT (B29012003) optional, and the 
corresponding Glamox Sensor-app (iOS/Android); safety 
cover LMS SENSOR SAFETY COVER (B29011001), optional

2.  Safety

Danger of death through electric shock or fire!

 Installation should only be carried out  

by a qualified electrician!

WARNING

 

Work on electrical systems may only be carried out by 

qualified electricians or by instructed persons under the 
guidance and supervision of a qualified electrician in 

accordance with the technical regulations applying to 

electricity! 

 

Comply with the country-specific safety regulations for 
work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated with any object, the guarantee shall lapse.

3.  Proper use

The presence detector is intended for indoor installation.

4.  Function

The presence detector is primarily used in offices, schools, 

conference rooms and corridors, as well as in homes, for easy 

and energy-efficient control of lighting. The lighting is accor

-

dingly influenced by switching or constant lighting control.

Function description

 Mixed light measurement 

 Presence detection

 Artificial light

 Push button for manual lighting control

 Incident daylight

Lighting channel C1, C2, C3 

The lighting is controlled by presence and brightness. Artificial 

lighting is switched on and regulated at a constant brightness 

level via the DALI interface in the event of too little daylight 

and when the room is occupied.

The lighting is switched off via the DALI interface if there is 

sufficient daylight or if the room is unoccupied. 

Up to 3 lighting groups (lighting channels C1 - C3) can be 

configured on one single DALI line. DALI devices can be 

addressed and grouped very easily and intuitively. A detailed 

description can be found in chapter „9. Start-up“.

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...