Gillette SPH-120 Operation And Installation Manual Download Page 20

 

PAGE 20

 

BE EXTREMELY CAREFUL.  YOU ARE READY TO 
TEST RUN A GENERATOR THAT HAS BOTH ELEC-

TRIC SHOCK AND FLAMMABLE FUEL POTEN-
TIAL HAZARDS.  CHECK AND REVIEW ENTIRE 
INSTALLATION BEFORE START-UP.  MAKE SURE 

THAT RATING OF TRANSFER SWITCH, MATCHES 
OR IS MORE THAN THE RATING OF THE EMER-
GENCY GENERATOR, IN VOLTS, PHASE, AND 
FREQUENCY.  MISMATCHED SPECIFICATIONS 

WILL CAUSE EQUIPMENT DAMAGE. 

A) All models will allow either natural gas or LPG to 
be connected to fuel input line.  It may be necessary 

for a minor adjustment to be made at “engine load 
adjustment screw”, during initial start-up, or when 
changing from one fuel to another.  See page 19 for 

more details. 
 
B) C.A.R.B and EPA CARBURETION SYSTEMS: The 
secondary gas regulator has (2) separate fuel inputs.  

One is marked “LP” and the second is marked “NG”.  
When using LPG, the fuel hose from engine carbure-
tor must be connected to the regulator input “LP” with 

a dead plug attached to the “NG” input.  When Natu-
ral Gas is used, the fuel hose is connected to the “NG” 
input, with a dead plug attached to the “LP” input.  It’s 
just that simple to change fuel input, in the field.  See 

page 19 for further details. 
 
C) Model SPV-160: To change input fuels, remove 

flexible fuel line at bottom of engine carburetor, and 
either insert a threaded orifice into brass fuel line fit-
ting for LPG use, or remove same orifice, for Natural 
Gas uses.  No other adjustments are required. 

At this time, before the initial start-up is performed, 
the 10 amp fuse is still removed from controller and 
the “MODE SELECTOR” switch is at “OFF/RESET”.  
Also, fully charged battery is connected, oil level is 

correct, coolant in radiator (if liquid cooled set is be-
ing tested) is correct, and all listed requirements, 
leading up to the initial start has been completed. 

When the automatic start/stop system is activated, it 
may cause an unwanted start cycle.  Be very cautious 
of these possible, sudden engine starts. 
 

STEP 1: 

Replace 10 amp fuse in its proper position on 

control panel, and keep the “MODE SELECTOR” 
switch on “OFF/RESET” position.  Also, turn off the 

main 2-pole, automatic circuit breaker (item “D” on 

control panel, page 11).  Apply electric utility power 
to connected automatic transfer switch (ATS). 

STEP 2:

 Turn the “MODE SELECTOR” switch, located 

on the control panel, from “OFF/RESET” position to 

“TEST” position.  This will establish the first engine 
start cycle.  With the “ENGINE RUNNING” lamp 
(located on the annunciator panel) flashing, after a 10 

second time delay, the generator should crank over 
and start.  

NOTE:

 If a special controller is used that 

does not allow for a 10 second delay to start (for hos-
pitals or nursing homes), the engine will immediately 

start cranking, when switch is placed in “TEST” mode.  
Allow engine to run for approximately 2 minutes.  
Then return the engine test switch to the “OFF/

RESET” position.  The engine will then shut down. 
 
If the engine should fail to start, for some reason, the 
engine will crank for 10 seconds, rest for 10 seconds, 

and continue for a total (3) attempt cycle cranks be-
fore a complete shutdown occurs, and “Overcrank” 
LED energizes on 8 point annunciator.  Check all gas 
connections and shut off valves.  

REMEMBER: 

 This 

no start problem is a “Fault” and when fault is cor-
rected, the “MODE SELECTOR” switch must be 
turned to “OFF/RESET” to reset the controller.  After 

15 seconds, turn the “MODE SELECTOR” back to 
“TEST” for another start-run attempt. Anytime there 
after, the generator can be manually test run from this 

“MODE SELECTOR” switch by pushing it to the 
“TEST” position. 
 

STEP 3:

 During this initial testing time, it is advised to 

test the voltage at no load conditions, and at full load 
conditions.  

Repeat the manual start process.

  Turn 

the “MODE SELECTOR” switch, located on the gen-
set, from “OFF/RESET” position to “TEST” position.  

This will establish another engine start attempt.  The 
engine should crank steadily, and after a few seconds 
start running.  The generator set is now running and 

will remain running until “MODE SELECTOR” switch 
is returned to the “OFF/RESET” position.  

Do not 

move the switch from the “TEST MODE” position 

at this time.

  Allow engine to run un-loaded for 5-10 

minutes to warm up. This gives installer time to per-
form certain quality tests.  Use an AC Voltmeter and 
AC Frequency Meter to test the no load generator 

INITIAL START-UP 

CAUTION

 

START-UP USING MANUAL TEST MODE

 

WARNING

 

PROCEED WITH CAUTION.  THE CONTROL 

PANEL IS NOW “LIVE” WITH UTILITY POWER.  
CONTACT WITH THESE “LIVE” TERMINALS IN-
SIDE TRANSFER SWITCH AND GENERATOR 
CONTROL PANEL WILL RESULT IN SHOCK AND 

POSSIBLE DEATH WILL RESULT. 

CAUTION

 

SELECTING THE FUEL 

Summary of Contents for SPH-120

Page 1: ...OPERATION AND INSTALLATION GUIDE FOR MODELS SPS 100 SPH 120 SPS 120 SPV 160 GILLETTE GENERATORS AUTOMATIC POWER SYSTEMS...

Page 2: ...tural Gas NG 12 13 Gaseous Dry Fuel System Liquid Propane Gas LPG 14 15 Prepare for Generator Operation 15 18 Access to Interior Battery Selection Installation Electricians Wiring Installation Final P...

Page 3: ...procedure is used and is not recommended by GILLETTE the person or company responsible for the generator modification must assume all responsibility for safety and correct operation for the operator s...

Page 4: ...AU TIONS Starting batteries are not furnished with your generator set but they are available through your installing contractor The home standby generator requires a Group 36 12 VDC fully charged batt...

Page 5: ...running engine produces a poisonous gas from its muffler exhaust pipe This is an odorless in visible and colorless poison that cannot easily be detected Breathing carbon monoxide will cause fa tigue h...

Page 6: ...ical output shows sparks smokes emits flames vibrates or shows any other abnormal operation Do not modify generator design Do not modify carburetion system as it is factory set for C A R B EPA emissio...

Page 7: ...ibility of the sepa rate manufacturers of the ATS PRE INSTALLATION PLANNING The beginning installation requires some thought and planning The following illustrations are meant to fa miliarize reader w...

Page 8: ...ther air intakes should be minimum 10 feet from exhaust end 6 Windows and doors on adjacent walls to be closed at all times during generator operation 7 Nearest roof overhang vent should be 10 feet fr...

Page 9: ...best place for these two neutrals to meet generator and utility neutral is in the auto matic transfer switch However still connect gen set mechani cal ground to the stake All factory gen sets have a...

Page 10: ...with the entire generator set 11 12 VDC battery charger Installer must connect 120 volt 1 phase utility power to this charger 12 Oil drain with flexible drain hose NOTE Change oil after every 50 hour...

Page 11: ...to normal operation C Hour Meter Total hours of use and is used as service reminder D Main Line Circuit Breaker UL 146 circuit breaker will trip open upon short circuits or overloads KNOWYOUR SYSTEM C...

Page 12: ...sure must be 6 to 8 inches water column 4 to 4 ounces and minimum 1000 BTU rating per cubic foot hour Figure 1 BTU Values based on 1000 BTU s per cubic foot Gas supplier may need to know Nat Gas consu...

Page 13: ...l new installations plus any future repair or troubleshooting procedures must include a natural gas manometer test This test should be conducted after all other natural gas appliances have been turned...

Page 14: ...135 cu ft can be de livered over a 50 ft distance with a 1 diameter fuel pipe INSTALLER S RESPONSIBILITY Use Figure 4 chart to learn cubic feet hour value of generator to be installed Use Figure 5 cha...

Page 15: ...LPG tank are reasonably close 20 Ft to 50 Ft as it results in short runs for both electric wires and LPG fuel lines When these two identities are far apart always choose to locate generator as close t...

Page 16: ...jobsite A fully charged battery must test at 12 5 13 0 volts DC Also the correct battery for models SPH 85 SPH 100 SPH 120 and SPV 160 must have lug terminals to match lug battery cables for a bolt to...

Page 17: ...tery charger before working on battery terminals A battery can cause a chemical burn Before working on a battery follow safe procedures Wear full eye protection and protective clothing When battery el...

Page 18: ...unction The generator will not ex ercise in this position TEST position will start the engine but will not dis connect utility power from the transfer switch This position is used for testing the gene...

Page 19: ...re position this LPG venture For natural gas operation remove the carburetor flexible fuel line from LP stamped brass fitting and dead end brass cap from NG stamped brass fitting Attach fuel line to...

Page 20: ...r switch ATS STEP 2 Turn the MODE SELECTOR switch located on the control panel from OFF RESET position to TEST position This will establish the first engine start cycle With the ENGINE RUNNING lamp lo...

Page 21: ...rong enough to perform under this demanding scenario However if the load is 75 or more induc tive large motors UPS systems large air condition ers it may be necessary to install a time delay de vice a...

Page 22: ...or Inspect the debris guard on engine air intake to insure no obstructions have accumulated Inspect radiator liquid cooled sets to insure no debris accumulation has occurred Some generator models have...

Page 23: ...L CONNECTION THERE ARE TWO KNOCK OUT HOLES ON THE RIGHT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT GENERATOR END VIEW CONTROL DOOR PANEL THIS PANEL IS HERE TO HELP WITH INITIAL WIRING I...

Page 24: ...POLY BASE AS SHOWN USING 5 16 18 HEX NUT TO LOCK BOLT IN PLACE INSTALL GEN SET AND METAL BASE ONTO EXTENEDED 5 16 18 BOLT AND SECURE WITH LARGE FLAT WASHER AND HEX NUT CAUTION TIGHTEN NUT ONLY TO HOLD...

Page 25: ...IS A 3 4 THREADED PIPE FOR CONNECTION ELECTRICAL CONNECTION THERE ARE THREE PLUGGED HOLES ONE ON THE RIGHT HAND SIDE AND ONE ON THE LEFT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT FULL...

Page 26: ...NOT ENERGIZED GAS REGULATOR NOT OPENING SPARK PLUG IS DEFECTIVE OR SPARK PLUG WIRE IS DEFECTIVE OR DISCONNECTED VENTS IN GAS REGULATOR IS PLUGGED UP C ENGINE RUNS ERRATIC AIR CLEANER IS DIRTY AND NEED...

Page 27: ...START STOP HIGH TEMPERATURE DRY START STOP CONTACTS FROM OTHER EQUIPMENT NEUTRAL ENCLOSURE GROUND MECHANICAL GROUND LOAD SIDE 120 240 VAC AND NEUTRAL CONNECT TO TRANSFER SW GROUND STAKE FOR CONTROLLE...

Page 28: ...LINES X YEARLY FUEL LINES X YEARLY CONNECTOR JOINTS X YEARLY EXHAUST MUFFLER X EVERY 6 MONTHS SPARK ARRESTOR X EVERY 6 MONTHS FLEX LINE X EVERY 6 MONTHS LEAKAGE X EVERY 6 MONTHS JOINT CLAMPS X EVERY 6...

Page 29: ...g table to keep a record of all periodic and unscheduled maintenance and service See Ser vice Schedule Record the name address and phone number of your authorized GILLETTE service center DATE HOUR MET...

Page 30: ...5 OWN 794 20080828 Gillette Generators Inc 1340Wade Drive Elkhart IN 46514 Phone 574 264 9639 Fax 574 262 1840 E mail sales gillettegenerators com www gillettegenerators com Call for Tech Support 1 86...

Reviews: