Gillette SPH-120 Operation And Installation Manual Download Page 13

PAGE 13 

EXAMPLE 2:

 A model SPV-160, 16 KW generator is 

to be installed 50 feet from gas meter.  In reading the 

charts, Fig. 1 shows this model to require 280 cubic 
feet/hour (or 280,000 BTU/hr) gas volume to be deliv-
ered to generator.  Figure 2 chart show this required 
280 cu.ft. can not be delivered with a ¾” or 1” pipe.  

Only a 1¼” diameter pipe can safely deliver the 280 
cu.ft. gas requirement, over a 50 foot distance. 
 

INSTALLER’S RESPONSIBILITY: Use Figure 1 
chart to learn cubic feet/hour value of generator to 
be installed.  Use Figure 2 chart to learn minimum 

pipe size diameter and maximum distance from 
gas meter, to insure sufficient fuel volume from 
natural gas meter to generator set. 

 

CRITICAL POINTS FOR A PROPER 

NATURAL GAS INSTALLATION

 

 

Before natural gas fuel line plans are made, call 

your natural gas supplier, give information on the 

amount of cubic feet/hour and the BTU’s/hour that 
generator will use, and ask if natural gas meter and 
primary regulator, is adequate for your natural gas 
generator.  Natural gas companies have different me-

ters for increasing BTU gas demands. 
 

Check the natural gas primary regulator, con-

nected at natural gas meter output.  The correct pri-
mary regulator is set at 6 to 8 inches water column (4 

to 4½ ounces pressure or 0.19 to 0.26 PSI).  The exist-
ing primary regulator (for other gas appliances) may 
be too small to run your gas driven generator. 

 

A dedicated natural gas fuel line and primary 

gas regulator (if required) is mandatory for proper 
operation. 

 

A flexible natural gas fuel line is furnished for 

installation between utility gas line and generator for 
input. 
 

CAUTION:

 

Make sure this flexible fuel line is in-

stalled in horizontal position without bends.  A 
bend of any kind in this flexible line could lead to 

an eventual crack in the bend, causing a possible 
leak.

  See Figure 3 for a recommended installation. 

 

Make sure fuel pipe installation and connection at 

generator includes an on/off manual gas valve. 
 

All new installations, plus any future repair or 

troubleshooting procedures must include a natural 
gas manometer test.  This test should be conducted 
after all other natural gas appliances have been 
turned on.  After all appliances are running, start the 

generator.  If manometer stays within 6 to 7 inches 
water column with full load applied to a proper run-
ning generator, it’s a good installation. (See Figure 3) 

If manometer reading falls below 5 inches water col-
umn while generator engine is cranking, or running, 

it may indicate the gas meter or primary regulator is 
too small, or the fuel pressure from gas supplier is 
inadequate.  Any of these three problems will cause a 
fault in proper generator operation. 

 
If manometer reading stays within the 6 to 7 inches 
water column, but generator engine still will not start, 

or it runs erratic, it may indicate insufficient fuel vol-
ume due to long fuel line runs or fuel pipe diameter is 
too small.  Check calculations of chart in Figure 1 & 2. 
 

Figure 3 

NOTE: 

After completion of all gas tests, remove ma-

nometer and replace blank plug, using fresh pipe 
sealant. 
 

For additional precautions, a manual fuel shut-off 

valve should also be installed inside the building, for 

those locations with inside gas meters. 
 

Climates that have snow and ice build-up, along 

with sub-zero temperatures, should have gas fuel pip-

ing protection against freezing.  The generator end of 
the hard piping installation should include a sediment 
trap to drain any condensation, and a line filter. (See 
Figure 3) 

 

Best installations happen when electric utility me-

ter and gas meter are close together, as it results in 
short runs for both electric wires and fuel lines.  When 
these two utilities are far apart, always choose to lo-

cate gen-set close to the gas meter, as installation 
costs are lower when increased wire size must be 
used for the long runs rather than increased fuel pipe 

diameters. 

Sediment Trap

Dedicated
Natural Gas

Fuel Line

Manometer
Reading

Must Be 6”
to 7” Water

Column

Gas Fuel To
Generator

On/Off Valve

Furnished

Flexible

Gas Pipe

(without

bends or

angles)

Manometer Port: Remove
Blank Plug And Insert

Manometer Plug

Line Filter

Summary of Contents for SPH-120

Page 1: ...OPERATION AND INSTALLATION GUIDE FOR MODELS SPS 100 SPH 120 SPS 120 SPV 160 GILLETTE GENERATORS AUTOMATIC POWER SYSTEMS...

Page 2: ...tural Gas NG 12 13 Gaseous Dry Fuel System Liquid Propane Gas LPG 14 15 Prepare for Generator Operation 15 18 Access to Interior Battery Selection Installation Electricians Wiring Installation Final P...

Page 3: ...procedure is used and is not recommended by GILLETTE the person or company responsible for the generator modification must assume all responsibility for safety and correct operation for the operator s...

Page 4: ...AU TIONS Starting batteries are not furnished with your generator set but they are available through your installing contractor The home standby generator requires a Group 36 12 VDC fully charged batt...

Page 5: ...running engine produces a poisonous gas from its muffler exhaust pipe This is an odorless in visible and colorless poison that cannot easily be detected Breathing carbon monoxide will cause fa tigue h...

Page 6: ...ical output shows sparks smokes emits flames vibrates or shows any other abnormal operation Do not modify generator design Do not modify carburetion system as it is factory set for C A R B EPA emissio...

Page 7: ...ibility of the sepa rate manufacturers of the ATS PRE INSTALLATION PLANNING The beginning installation requires some thought and planning The following illustrations are meant to fa miliarize reader w...

Page 8: ...ther air intakes should be minimum 10 feet from exhaust end 6 Windows and doors on adjacent walls to be closed at all times during generator operation 7 Nearest roof overhang vent should be 10 feet fr...

Page 9: ...best place for these two neutrals to meet generator and utility neutral is in the auto matic transfer switch However still connect gen set mechani cal ground to the stake All factory gen sets have a...

Page 10: ...with the entire generator set 11 12 VDC battery charger Installer must connect 120 volt 1 phase utility power to this charger 12 Oil drain with flexible drain hose NOTE Change oil after every 50 hour...

Page 11: ...to normal operation C Hour Meter Total hours of use and is used as service reminder D Main Line Circuit Breaker UL 146 circuit breaker will trip open upon short circuits or overloads KNOWYOUR SYSTEM C...

Page 12: ...sure must be 6 to 8 inches water column 4 to 4 ounces and minimum 1000 BTU rating per cubic foot hour Figure 1 BTU Values based on 1000 BTU s per cubic foot Gas supplier may need to know Nat Gas consu...

Page 13: ...l new installations plus any future repair or troubleshooting procedures must include a natural gas manometer test This test should be conducted after all other natural gas appliances have been turned...

Page 14: ...135 cu ft can be de livered over a 50 ft distance with a 1 diameter fuel pipe INSTALLER S RESPONSIBILITY Use Figure 4 chart to learn cubic feet hour value of generator to be installed Use Figure 5 cha...

Page 15: ...LPG tank are reasonably close 20 Ft to 50 Ft as it results in short runs for both electric wires and LPG fuel lines When these two identities are far apart always choose to locate generator as close t...

Page 16: ...jobsite A fully charged battery must test at 12 5 13 0 volts DC Also the correct battery for models SPH 85 SPH 100 SPH 120 and SPV 160 must have lug terminals to match lug battery cables for a bolt to...

Page 17: ...tery charger before working on battery terminals A battery can cause a chemical burn Before working on a battery follow safe procedures Wear full eye protection and protective clothing When battery el...

Page 18: ...unction The generator will not ex ercise in this position TEST position will start the engine but will not dis connect utility power from the transfer switch This position is used for testing the gene...

Page 19: ...re position this LPG venture For natural gas operation remove the carburetor flexible fuel line from LP stamped brass fitting and dead end brass cap from NG stamped brass fitting Attach fuel line to...

Page 20: ...r switch ATS STEP 2 Turn the MODE SELECTOR switch located on the control panel from OFF RESET position to TEST position This will establish the first engine start cycle With the ENGINE RUNNING lamp lo...

Page 21: ...rong enough to perform under this demanding scenario However if the load is 75 or more induc tive large motors UPS systems large air condition ers it may be necessary to install a time delay de vice a...

Page 22: ...or Inspect the debris guard on engine air intake to insure no obstructions have accumulated Inspect radiator liquid cooled sets to insure no debris accumulation has occurred Some generator models have...

Page 23: ...L CONNECTION THERE ARE TWO KNOCK OUT HOLES ON THE RIGHT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT GENERATOR END VIEW CONTROL DOOR PANEL THIS PANEL IS HERE TO HELP WITH INITIAL WIRING I...

Page 24: ...POLY BASE AS SHOWN USING 5 16 18 HEX NUT TO LOCK BOLT IN PLACE INSTALL GEN SET AND METAL BASE ONTO EXTENEDED 5 16 18 BOLT AND SECURE WITH LARGE FLAT WASHER AND HEX NUT CAUTION TIGHTEN NUT ONLY TO HOLD...

Page 25: ...IS A 3 4 THREADED PIPE FOR CONNECTION ELECTRICAL CONNECTION THERE ARE THREE PLUGGED HOLES ONE ON THE RIGHT HAND SIDE AND ONE ON THE LEFT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT FULL...

Page 26: ...NOT ENERGIZED GAS REGULATOR NOT OPENING SPARK PLUG IS DEFECTIVE OR SPARK PLUG WIRE IS DEFECTIVE OR DISCONNECTED VENTS IN GAS REGULATOR IS PLUGGED UP C ENGINE RUNS ERRATIC AIR CLEANER IS DIRTY AND NEED...

Page 27: ...START STOP HIGH TEMPERATURE DRY START STOP CONTACTS FROM OTHER EQUIPMENT NEUTRAL ENCLOSURE GROUND MECHANICAL GROUND LOAD SIDE 120 240 VAC AND NEUTRAL CONNECT TO TRANSFER SW GROUND STAKE FOR CONTROLLE...

Page 28: ...LINES X YEARLY FUEL LINES X YEARLY CONNECTOR JOINTS X YEARLY EXHAUST MUFFLER X EVERY 6 MONTHS SPARK ARRESTOR X EVERY 6 MONTHS FLEX LINE X EVERY 6 MONTHS LEAKAGE X EVERY 6 MONTHS JOINT CLAMPS X EVERY 6...

Page 29: ...g table to keep a record of all periodic and unscheduled maintenance and service See Ser vice Schedule Record the name address and phone number of your authorized GILLETTE service center DATE HOUR MET...

Page 30: ...5 OWN 794 20080828 Gillette Generators Inc 1340Wade Drive Elkhart IN 46514 Phone 574 264 9639 Fax 574 262 1840 E mail sales gillettegenerators com www gillettegenerators com Call for Tech Support 1 86...

Reviews: