background image

50

Model: FSH-4 Hood

Parts List

* Not shown

6

7*

2

9

1

8*

4

5

6

8*

7*

2

1

3

5

7.03

Hood Front - Opened

Summary of Contents for FSH-4 Hood

Page 1: ...d Committed to Quality 2750 Gunter Park Drive West Montgomery AL 36109 USA Toll Free 800 554 4537 USA Canada Only Other 334 272 1457 Fax 334 239 4117 Website www gfse com Email services gfse com Printed in USA Form 65497 Rel Date Apr 2009 Rev Date Feb 2020 Rev G ...

Page 2: ......

Page 3: ...is requested Giles will dispatch factory authorized service representatives to inspect repair recondition or replace units of its manufacture with such labor being rendered without cost to owner for twenty four 24 months from the date of installation Otherwise service including labor and transportation charges or other expenses in connection with the removal or installation of any part or parts su...

Page 4: ......

Page 5: ...ces 8 2 04 3 Oven Limitations 9 2 04 4 Oven Clearances 9 2 04 5 Griddle Limitations 10 2 04 6 Griddle Clearances 10 2 04 7 Range Limitations 11 2 04 8 Range Clearances 11 2 05 Electrical Specifications Hood Only 12 2 05 1 Electrical Connections 12 2 05 2 Routing Power Conduit Wiring 13 2 05 3 Hood and Appliance Interlock Diagram 13 2 06 Fire Suppression System Installation 14 2 06 1 Fire Suppressi...

Page 6: ...ters Light 52 7 05 Doors Front Panel 54 4 Operation Filter Maintenance 25 4 01 Starting the Hood 25 4 02 Filter System Filter Maintenance Filter Alarms 25 4 02 1 Ventless Hood Filter Table 25 4 02 2 Baffle Filter Removal 26 4 02 3 Baffle Filter Installation 27 4 02 4 Pre Filter Removal 28 4 02 5 Pre Filter Installation 29 4 02 6 E A C Filter Cell Removal 30 4 02 7 E A C Filter Cell Installation 31...

Page 7: ...sult in serious injury even death Indicates a potentially hazardous situation which if not avoided may result in minor to moderate injury This notification is also used as an alert to unsafe practices If used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in equipment and or property damage and may void the factory warranty NOTE or IMPOR...

Page 8: ...on hazard due to carbon monoxide build up in the kitchen area Hood is approved ONLY for use with electrically heated appliances Prior to installation consult a qualified electrician to ensure that installation will comply with all electrical requirements and codes The unit must be adequately and properly grounded Improper grounding may result in electrical shock to the user Always refer to local e...

Page 9: ...al protection such as oven mitts or gloves when handling hot pans utensils or foods Failure to comply with CAUTION notices may result in minor to moderate personal injury damage to equipment or property and potentially void the warranty Some components and controls are impact sensitive To avoid damage and maintain proper operation exercise care when moving items and working near the hood Handle th...

Page 10: ...ce equipment To clean difficult surface areas having excessive build up of grease residue GILES recommends using a mild biodegradable non toxic degreasing cleaner such as Simple Green Crystal Foaming Spray Cleaner Degreaser GILES assumes no responsibility in regard to code compliance for installation and use of Ventless Recirculating Ventilation equipment The customer is responsible for obtaining ...

Page 11: ...g plenum nozzles not appliance drop downs detector link brackets and conduit The fire extinguishing system field installation set up testing and final charging shall be provided by the purchaser and must be supplied by an authorized Ansul Distributor Dealer not included with hood purchase Hood is constructed primarily of Series 430 stainless steel 16 18 20 Ga 1 Introduction THANK YOU for purchasin...

Page 12: ...INSIDE 53 1 4 1352 5 14 355 6 MIN MIN FROM FLOOR TO CEILING 49 11 16 1262 54 A 39 3 8 999 61 D 42 3 16 1070 83 CEILING 54 1371 58 43 5 8 1108 02 E INCHES mm A B INSIDE C D E Dim FSH 4 A 48 11 16 1236 7 B 45 1 16 1144 6 C 50 3 8 1279 5 With 72 Floor Stand D 72 1828 8 E 115 5 8 2936 9 ...

Page 13: ...3 Introduction Hood Crated Weight Uncrated Weight approx FSH 4 w Stand 835 lbs 379 kg 710 lbs 322 kg 1 04 2 Agency Certifications 1 04 3 Weights Model FSH 4 Hood ...

Page 14: ...4 Model FSH 4 Hood Introduction ...

Page 15: ...on set up testing and final commissioning shall be provided by the purchaser and must be supplied an authorized Ansul Distributor Dealer IMPORTANT Before installing the GILES Recirculating Ventless Hood system ensure that A all necessary approvals from local code authorities have been obtained B the appliances to be used with the hood are all within the hood s listing limitations as outlined in Se...

Page 16: ...rts and or framework that might be attached 6 Locate and secure the envelope containing Warranty Card and any other documentation or hardware provided for installation 7 It is preferable to leave the hood unit on the pallet so that handling equipment can be used to move it to the desired permanent location after the stand is assembled and in place Unit is very heavy and bulky Use suitable equipmen...

Page 17: ...and or when moving the assembled hood stand into a final location The assembly is very heavy and will be extremely top heavy Install upper back panel TRIM CAP ADJUST LEGS TO LEVEL HOOD ANCHOR LEGS TO FLOOR AS REQUIRED BY LOCAL CODE TRIM CAP TABS ON CHANNELS SHOULD FIT INTO SLOTS ALONG BOTTOM EDGE OF STAND SIDES ...

Page 18: ...Clearances 2 04 1 Fryer Limitations Electrically Heated Appliances ONLY 2 04 2 Fryer Clearances Side to Side Overhang Not Applicable w Floor Stand Dim FSH 4 A 48 11 16 1236 7 A The diagrams in this section depict ceiling suspended hoods over various appliances The side clearance minimum dimensions shown in these illustrations will not apply to current free standing hood versions The entire width o...

Page 19: ... Model FSH 4 Hood Installation Hood Max Temp Max kW Input Total FSH 4 500 55 kW Inches mm 2 04 3 Oven Limitations Electrically Heated Appliances ONLY A Dim FSH 4 A 48 11 16 1236 7 2 04 4 Oven Clearances ...

Page 20: ...ax Temp Max kW Input Max Cooking Surface FSH 4 400 25 42 X 42 Inches mm 2 04 5 Griddle Limitations Electrically Heated Appliances ONLY 2 04 6 Griddle Clearances Side to Side Overhang Not Applicable w Floor Stand Dim FSH 4 A 48 11 16 1236 7 A ...

Page 21: ... Hood Max Temp Max kW Input Max Burners FSH 4 400 25 kW 8 2 04 7 Range Limitations Electrically Heated Appliances ONLY 2 04 8 Range Clearances Side to Side Overhang Not Applicable w Floor Stand Dim FSH 4 A 48 11 16 1236 7 A Inches mm ...

Page 22: ...n 2 05 Electrical Specifications Hood ONLY Food service equipment must be properly grounded in accordance with local code or in the absence of local code with the National Electrical Code ANSI NFPA 70 Improper grounding may result in electrical shock to Users Check local electrical code to ensure that proper grounding techniques are used Always consult a certified electrician or other qualified se...

Page 23: ...e under Hood appliance Once properly connected the appliance s should not receive service power unless the hood is running properly 2 05 3 Hood and Appliance Interlock Diagram IMPORTANT Failure to interlock served appliances with the hood such that appliances are not powered unless the hood is operating is not compliant with the Hood s UL listing and may be in violation of local building fire and ...

Page 24: ...zzles Ansul No 56927 Plenum Nozzles Detector Links Ansul No 56811 165ºF 74ºC 2 Appliance nozzles shall be positioned 11 279 4mm below the lowermost front edge of the hood 3 Both appliance nozzles must be installed 4 A manual activation station for the fire system NOT included is to be installed and located in a path of egress exit The pull station must be clearly marked and easily accessible 5 The...

Page 25: ...F Ansul P N 56811 Appliance Nozzle 2 minimum Sized and positioned by Local Authorized Fire Suppression Installation Company Not supplied with Hood Nozzles centered over cooking surface s 285 F Factory installed 2 06 2 Fire Suppression Detector Links Location 2 06 3 Appliance Nozzles ...

Page 26: ...ppliance Nozzle 2 minimum Sized and positioned by authorized Ansul Service Agent Customer supplied Plenum Nozzle Factory installed Plenum Nozzle Factory installed Plenum Nozzle Factory installed 2 06 4 Fire Extinguisher Nozzle Locations ...

Page 27: ...brief overview of hood components functions and accessories Please review carefully before proceeding farther Left Filter Chamber Section 3 02 3 Overview Control Panel Section 3 01 Right Filter Chamber Section 3 02 Hood Exhaust Duct 4 Adjustable Legs ...

Page 28: ...Model FSH 4 Overview 18 1 2 3 4 6 7 3 01 Control Panel 5 ...

Page 29: ...ng and power to appliances is shutdown IMPORTANT Do not rely on this indicator as a signal for routine cleaning cell must be cleaned daily to maintain peak performance and extend the useful life of charcoal filters CHECK Indicates that collector cell has stopped operating properly either damaged shorted to ground fins are shorted due to excessive moisture etc No alarm sounds the appliances remain ...

Page 30: ...20 Model FSH 4 Overview 5 2 1 3 4 6 7 8 1 5 3 4 3 02 Filter Chamber Exhaust 9 9 Not shown ...

Page 31: ...DAILy as described later in this manual 5 Charcoal Filter 2 Single use disposable filters that help to control cooking aromas in exhausted air Filters must be replaced periodically NEVER attempt to clean and re use charcoal filters Typically replace with NEW filters every 30 to 45 days Replacement cycle is dependent on appliances in use and type of foods cooking activities 6 Self Supporting Hood S...

Page 32: ...grease particulate contaminant Pre Filter 2 required P N 91707 Removes additional grease laden vapor and moisture from the air Single use only disposable must be replaced weekly approx E A C Filter Cell P N 20521 Left Side P N 20520 Right Side Captures fine grease particulates and some smoke contaminant from the air Sustainable must be cleaned DAILy ...

Page 33: ...40 days approx NOTE Will not completely remove odors 1 Sample Can Foaming Crystal Cleaner Degreaser P N 41510 12 count Case NSF approved Spray foam degreaser for cleaning EAC collector cell Sample can of the GILES recommended collector cell cleaner It is readily available from Giles and on line distributors as well as many nationwide retail outlets 3 03 Accessory Items Included w Hood continued ...

Page 34: ...24 Model FSH 4 Overview ...

Page 35: ...place every 30 to 40 days Section 4 02 8 DO NOT attempt to clean ONLY replace Section 4 03 5 Section 4 02 9 1 Press and momentarily hold the top START portion of the Power Switch until the hood blowers start running Release and switch will spring back to remain ON 2 The green HOOD POWER light and both small EAC ON lights should turn ON A constant tone alarm may sound briefly and stop as the fan re...

Page 36: ...26 Model FSH 4 Hood Operation Filter Maintenance 4 02 2 Baffle Filter Removal Place in OFF position The 2 baffle filters are accessed from underneath the hood ...

Page 37: ...27 Model FSH 4 Hood Operation Filter Maintenance Switch Arm must be actuated by the baffle filter as shown Front View 4 02 3 Baffle Filter Installation Position filter w baffles in a vertical position ...

Page 38: ...28 Model FSH 4 Hood Operation Filter Maintenance Door open Front View 4 02 4 Pre Filter Removal Place in OFF position Pre Filters ...

Page 39: ...ilters are changed always record the installation date in the space provided on the filter label 4 02 5 Pre Filter Installation Metal mesh side facing toward middle Pre Filter Paper side to outside Paper side to outside Switch roller must be actuated by the pre filter when installed Close Door ...

Page 40: ...30 Model FSH 4 Hood Operation Filter Maintenance Folding handle use to avoid damaging the cell Left E A C Cell Right E A C Cell Door open 4 02 6 E A C Filter Cell Removal Place in OFF position ...

Page 41: ... the cell IMPORTANT E A C filter cells are side specific Give attention when placing into hood to avoid improper positioning Contact pads of both cells must be position toward top of hood and airflow direction arrow of each must point toward the center If cell does not engage the alignment pin and slide fully into the hood it is NOT positioned properly Brass contacts on cells must make good contac...

Page 42: ...32 Model FSH 4 Hood Operation Filter Maintenance Charcoal Filter Door open Front View 4 02 8 Charcoal Filter Removal Place in OFF position ...

Page 43: ...od Operation Filter Maintenance 4 02 9 Charcoal Filter Installation Door open Close Door Front View Charcoal Filter Blue fiber fill side faces middle Switch roller must be actuated by the charcoal filters when installed ...

Page 44: ...ter rack underneath hood 4 03 Hood Filter Alarms 4 03 1 Baffle Pre Filter or Charcoal Filter Missing If baffle filters pre filters or charcoal filters become clogged or other conditions occur that obstruct airflow through the Hood such that it falls below the minimum required to provide effective capture of cooking vapors the CHARCOAL OR BAFFLE FILTER CLOGGED light will turn ON Power to all applia...

Page 45: ... Cell is damaged and has shorted out to ground Collection fins are shorted out because of excessive moisture When CHECK light is ON system is no longer operating to clean the air even though the hood continues to run and the appliances are powered DO NOT CONTINUE TO USE APPLIANCES WHEN THIS CONDITION EXIST DETERMINE THE CAUSE AND CORRECT The following actions may clear the alarm condition 1 Turn O...

Page 46: ... system malfunction and result in interruption of power to appliances being served by a ventless hood unit Two 2 different cleaning methods are endorsed by GILES Food Service as follows Preferred spray foam method uses Simple Green Crystal Foaming Spray Cleaner Degreaser A readily available foaming aerosol that is an exceptionally effective cleaner as well as being safe for use on aluminum NSF app...

Page 47: ...s of all collector fins are completely covered with the foam 3 Allow foam to soak for 5 to 10 minutes In cases of extreme build up a second application may be required after rinsing 4 Carefully move cell to sink and rinse thoroughly using hot water spray Rinse ONLY DO NOT scrub with brushes 5 Stand cell upright on end on a drain board w contact plate up allow it to drain and air dry overnight The ...

Page 48: ...ic tote etc that is large enough to hold the cell along with enough degreasing solution to completely cover and soak it either standing on end on edge or lying flat 2 Fill the container with fresh water to a level that will cover the cell Measure water as filling and note the quantity Add Simple Green Pro HD in the ratio of 1 12 to the water e g 8 gals of water would require 67 gals 2 qts 21 ozs d...

Page 49: ...onsumable items which must be replaced periodically see Sections 4 02 8 4 02 9 They CANNOT be cleaned and reused Typical replacement cycle is every 30 to 40 days depending on usage Use GILES replacement Item No 30248 Write the replacement date on the new filter IMPORTANT Failure to use Giles OEM parts and OEM replacement filters may void the factory warranty 4 03 5 Charcoal Filter Maintenance ...

Page 50: ... 2 except perform for each pre filter and charcoal filter one at a time in succession Reinstall the filters See Sections 4 02 4 4 02 5 4 02 8 4 02 9 Removal Installation 3 E A C Filter Test Remove one of the E A C collector cells close and latch door then start hood Verify that WASH light on E A C Status comes ON for the side without cell and that the amber APPLIANCE POWERED light is also ON Wait ...

Page 51: ...ctions 4 04 1 4 04 2 If necessary obtain and install a new fresh pre filters and charcoal filters Ensure all filters are reinstalled in the hood 8 As necessary reposition appliance under hood and restore power supply to the hood 5 02 Quarterly Hood Cleaning The factory recommended product to use for general cleaning degreasing of this equipment is Simple Green Crystal Foaming Spray Degreaser Clean...

Page 52: ...ks Location Inspect conduit and wire cable for wear at pulleys and detectors replace if necessary Record maintenance date and service performed in a permanent file and sign off on tag attached to system in a conspicuous location Service and inspection of the fire suppression system must be performed by a qualified Ansul Distributor Dealer As a minimum field inspection of the fire suppression syste...

Page 53: ...1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 Check Initial Date 1 Door Check Section 5 01 2 Baffle Filter Check Section 5 01 3 EAC Filter Check Section 5 01 ...

Page 54: ...upply voltage Connect to proper electrical supply e Not properly connected to power source Confirm connections correct f Blown fuse or tripped circuit breaker Check main electrical panel CHARCOAL OR BAFFLE FILTER MISSING light ON at start up a Baffle or charcoal filters not installed or not properly seated Install filter and or check filter positioning inside hood EAC WASH light ON intermittent be...

Page 55: ...ckage e Fans running slow or blades are loaded with grease build up Check voltage and inspect blowers clean if needed Under hood appliances will not power up HOOD POWERED light ON WASH light ON APPLIANCE POWERED light OFF Intermittent beeping tone alarm sounding a Excessive grease film built up on collector fins too dirty Clean the EAC cell Section 4 04 2 b EAC cell is not installed Install clean ...

Page 56: ...46 Model FSH 4 Hood Troubleshooting ...

Page 57: ...THERS call 334 272 1457 Normal business hours are 8 00 AM to 5 00 PM Central Time calls are handled by an auto attendant answering system Please follow the recorded prompts to route your call appropriately If necessary after hours leave a voicemail message and a representative should respond within 30 minutes Website www gfse com Email services gfse com Giles is an equipment manufacturer and we do...

Page 58: ...48 Model FSH 4 Hood Parts List 10 7 2 1 9 7 02 Component Drawer Control Panel 1 3 4 5 6 11 13 14 17 16 15 2 12 8 ...

Page 59: ...7 20390 1 VACUUM SWITCH ADJUSTABLE 8 21441 2 SWITCH ROCKER ON 0N OFF 250V 20A 9 23782 1 SONALERT 250V CONTINUOUS TONE TOP 10 22950 1 SONALERT 250V INTERMITTENT TONE BOTTOM 11 20318 2 RELAY 240 VAC 10A 12 20312 2 RELAY BASE 13 23751 2 TERMINAL BLOCK 6 PL 250V 15A 14 21337 1 TRANSFORMER 230VAC 115VAC 15 40880 1 FITTING 1 4 BARBED 90 EL NYL 1 4 NPT 16 40877 1 FITTING 1 4 BARBED 90 EL NYL 1 8 NPT 17 3...

Page 60: ...50 Model FSH 4 Hood Parts List Not shown 6 7 2 9 1 8 4 5 6 8 7 2 1 3 5 7 03 Hood Front Opened ...

Page 61: ...91545 2 DRIP CUP EAC FILTER 3 20521 1 FILTER EAC 12 X 20 LEFT SIDE ONLY 4 20520 1 FILTER EAC 12 X 20 RIGHT SIDE ONLY 5 31964 2 CHARCOAL FILTER ASSY 6 21157 2 DOOR SWITCH FILTER ACCESS 7 23200 4 SWITCH SNAP ACTION ROLLER 8 21125 2 CONTACT BOARD EAC FILTER 9 33589 2 BLOWER ASSEMBLY 7 03 Parts List for Hood Front ...

Page 62: ...52 Model FSH 4 Hood Parts List Not shown 4 5 2 1 3 1 7 04 Under Hood Filters Light ...

Page 63: ... Parts List ITEM PART NO QTY DESCRIPTION 1 40943 2 BAFFLE FILTER S S 16 X 20 2 32776 1 DRIP CUP 3 32102 2 BAFFLE FILTER SWITCH ASSY 4 40625 1 LIGHT FIXTURE 5 20395 1 FLUORESCENT BULB COATED 7 04 Parts List for Under Hood ...

Page 64: ...54 Model FSH 4 Hood Parts List Not shown 7 05 Doors Front Panel 11 8 7 9 10 1 4 2 6 3 5 12 ...

Page 65: ...1553 1 FAN COVER 5 91699 1 GUARD FIRE DAMPER 6 91475 1 ACCESS DOOR ASSY RIGHT 7 91583 1 72 HOOD STAND SIDE LEFT 8 91586 1 72 HOOD STAND SIDE RIGHT 9 92100 1 72 HOOD STAND TOP BACK PANEL 10 92127 1 72 HOOD STAND BOTTOM BACK PANEL 11 92128 2 CHANNEL APPLIANCE POSITIONING 12 91708 2 CHANNEL FRONT TRIM HOOD STAND 72 Not shown NOTE Legs are welded to Stand Sides cannot be replaced ...

Page 66: ...56 Model FSH 4 Hood Parts List ...

Page 67: ......

Page 68: ...2750 Gunter Park Drive West Montgomery Al 36109 USA Phone 334 272 1457 Toll Free 800 554 4537 USA Canada Only FAX 334 239 4117 www gfse com Form No 65497 Rel Date Apr 2009 Rev Date Feb 2020 Rev G ...

Reviews: