GiBiDi DPT260 Fitting, Operation And Maintenance Instructions Download Page 37

37

DPT260

During the rising 
phase, the bollard 
does not perform 
the reversal 
managed by the 
pressure switch.

ATTENTION: when 
bollards are 
equipped with 
E.F.O the reversal 
function is not 
operative. (C004)

The bollard rises 
completely but the 
hydraulic unit 
continues working 
for about 10”. 
(C005)

The bollard 
completes the 
rising phase, but it 
performs the 
reversal and turns 
back in lower 
position. (C006)

• The  dip  switch  5  of  the  master 

unit  is  in  ON  position  (stop 
function  by  pressure  switch  is 
excluded).

• The  pressure  switch  does  not 

detect any pressure increase in 
the hydraulic circuit.

• The  hydraulic  unit  does  not 

generate  the  correct  operating 
pressure.

• The  dip  switch  4  of  the  master 

unit  is  in  ON  position  (the  stop 
function  by  pressure  switch  is 
excluded).

• The  pressure  switch  does  not 

detect any pressure increase in 
the hydraulic circuit.

• The  hydraulic  unit  does  not 

generate  the  correct  operating 
pressure.

The  adjustable  parameter  in  the 
master  board  which  corresponds 
to  the  reversal  time  in  case  of 
alarm  of  to  pressure  switch  pre-
adjusted, must be lowered of 1”.

• Only for cold territories: there is 

no heating device or it does not 
work.

• The piston rod is “dry” and must 

be lubricated.

• The  bollard  was  bumped 

violently when in high position so 
the piston rod is crooked.

• Set the dip switch 5 of the master board in OFF position 

(reversal function by pressure switch enabled).

• If  it  is  possible  adjust  the  pressure  switch  sensibility 

(adjustable old version) or replace the pressure switch 
(pre-adjusted and hermetic new version to increase the 
IP grade of protection and the system reliabilty). For the 
pressure switch adjustment please consult the chapter 
10: SPECIFIC OPERATIONS.

• Adjust  the  maximum  rising  pressure  in  the  hydraulic 

unit. For the adjustment, please consult the chapter10 : 
SPECIFIC OPERATIONS.

• Set the dip switch 4 of the master board in OFF position 

(the stop function by pressure switch is enabled).

• If  it  is  possible  adjust  the  pressure  switch  sensibility 

(adjustable old version) or replace the pressure switch 
(pre-adjusted and hermetic new version to increase the 
IP grade of protection and the system reliabilty). For the 
pressure switch adjustment please consult the chapter 
10: SPECIFIC OPERATIONS.

• Adjust  the  maximum  rising  pressure  in  the  hydraulic 

unit. For the adjustment, please consult the chapter10 : 
SPECIFIC OPERATIONS.

Request to Gi.Bi.Di. S.r.l. the specific document for the 
programming software, communicating the code on the 
master  board;  perform  the  parameter  1  adjustment 
lowering the time of about 1”.

• If there is no heating device, install one in each bollard; 

in  presence  of  heating  device,  check  the  proper 
operation of the resistance and the thermostat.

• Lubricate the piston rod.

• Replace the piston.

UK

The bollard is in 
high position and 
a lowering com-
mand is given, but 
the bollard 
remains up and 
lowers only after 
an initial pressure 
downward. (C007)

Summary of Contents for DPT260

Page 1: ...DPT260 DPT260 UK Automatic bollards FITTING OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...ed anti flame cable The dimension of the main power supply line must be evaluated by the installeraccordingtothequantityofbollards 500Weachbollard andthedistancefromtheoutputplace inorderto grantaprop...

Page 3: ...g effects in a range between 25 C and 55 C and foradeterminedtime lessthan24hours at 70 C The bollards do not require any availability of spare parts Gi Bi Di S r l warehouse can send any spare parts...

Page 4: ...s Lowering speed 25 cm s Manual emergency lowering Standard optional automatic lowering if power failed Safety reversal pressure switch Standard Connection line to control unit Standard 10 m max lengh...

Page 5: ...4 BOLLARD COMPONENTS 40 600 275 940 560 560 SOLENOID VALVE RISING SIDEBLOCK LOWER LIMIT SWITCH LOWER SUPPORT BASE REFLECTING STRIP FLASHING LIGHT HEAD MOVING CYLINDER FRAME PASSIVE BOX PISTON HYDRAULI...

Page 6: ...6 DPT260 5 INSTALLATION PROCEDURE 190 mm 200 mm 300 mm 1200 mm 1000 mm 1000 mm Quota di calpestio 10 mm SENSO DI TRAFFICO TRAFFIC WAY 50 mm PIC 1 PIC 2 PIC 3 PIC 5 PIC 4 UK...

Page 7: ...7 DPT260 5 INSTALLATION PROCEDURE UK PIC 6 FOUNDATION BRACKET CONTROL UNIT JUNCTION BOX 400 x 400 mm FLEXIBLE SHEATH diameter 50 mm max 1600 mm max 1600 mm...

Page 8: ...S WALKING LEVEL ROAD SURFACE ADDITIONAL CONCRETE CASTING SUPPORTING SLAB M8 CHEMICAL ANCHORS M16 CHEMICAL ANCHORS WATERPROOF PIT IN STAINLESS STEEL WATERPROOFING SHEATH 10 mm 50 mm 600 mm 275 mm 450 m...

Page 9: ...9 DPT260 PIC 8 PIC 10 PIC 11 PIC 9 M16 M16 5 INSTALLATION PROCEDURE UK...

Page 10: ...10 DPT260 5 INSTALLATION PROCEDURE min 25 cm 95 cm 95 cm 95 cm 95 cm 3 00 m 1 80 m 280 cm 200 cm 80 cm 80 cm 5 5 cm 9 cm 15 cm 15 cm 15 cm PIC 12 PIC 14 PIC 16 PIC 13 PIC 15 PIC 17 Control Unit UK...

Page 11: ...annel complete with covering grid to avoid rainwater infilitrations in the pits due to incline An important factor in the installation of bollards prior to the assessment of the permeability of soil i...

Page 12: ...it to the control unit for the electrical connection of the bollards PIC 2and4 WARNING If the distance between pits and control unit is more than 10m purchase the bollards equipped withelectricalconne...

Page 13: ...e the stainless steel waterproof pits to the ceilingofthebasement 7 Laythepipesfortheelectricalcablesfromthebollardstothecontrolunit 8 Laythepipesforrainwaterdrainagefromthewaterproofpitstothedrainage...

Page 14: ...ke into account other dimensions 2 The inductive loop is made of a special cable of 9mm diameter and it is suitable for the direct laying into the ground withoutanysheathnorprotection 3 Itisessentialt...

Page 15: ...G No 1 2 3 4 5 6 Colour BLUE GREY YELLOW BLACK WHITE RED Device FLASHING LIGHT BUZZER optional SOLENOID VALVE FOR LOWERING SAFETY PRESSURE SWITCH LIMIT SWITCH BOLLARD DOWN LIMIT SWITCH BOLLARD UP opti...

Page 16: ...ting bollard downposition Grey Sensor for detecting bollard up position nc Red Solenoid valve 24Vdc 1 3 2 4 2 4 2 4 4 2 1 1 2 4 2 6 BROWN 5 WHITE 3 YELLOW 1 BLUE 2 GREY Hydraulicl unit 4 BLACK M12 1 3...

Page 17: ...5bollards i e controlunitfor8bollards Electronic circuit Standard housing for control unit Protection class Power supply Control unit protection Service transformer Permitted ambient temperature Relat...

Page 18: ...everysinglebollard 5 Layandconnectanyadditionallines e g push buttonpanel inductiveloops trafficlights etc 6 Before running a functional test consult the instructions related to the electric connectio...

Page 19: ...parameters of the system 230V 10 per each moving bollard Master Slave F1 F2 F3 F5 F1 F6 F7 F2 Typology Protection 2A delayed Protection transformer 230V 24 VAC supply 1A delayed Protection timer progr...

Page 20: ...t outlet for yearly weekly progremmer connection Outlet 230V power supply for hydraulic pump common terminal 8 L7 L3 L4 L1 L2 L13 L13 LIN L5 L12 L11 L14 Outlet 24V power supply for solenoid valve Outl...

Page 21: ...Step Step Outlet for hydraulic pump power supply rising Outlet for hydraulic pump power supply lowering Outlet for hydraulic pump power supply in motion Inlet for safety devices Rising phase disabled...

Page 22: ...ne None Outlet 230V power supply for hydraulic pump common terminal 8 L7 L3 L4 L1 L2 Outlet 24V power supply for solenoid valve Outlet 24V power supply for acoustic buzzer Outlet 24V power supply for...

Page 23: ...ts rising lowering Power supply enabled Power supply enabled Limit switch enabled device in low position gate open Outlet enabled fixed or flashing depending on setting Outlet enabled fixed or flashin...

Page 24: ...STEPFUNCTION The bollard after the first control from up position moves to down position after another control the bollardreturnstoupposition step stepfunction CONTROLSENABLED Controlsfortheoperationo...

Page 25: ...pressed until the completeloweringofthebollard 4 Fastenthedowel PIC 23andPIC 24 PIC 25 PIC 26 PRESSURE SWITCHAS RISING LIMIT SWITCH ENABLED At the final stage of the rising the pressure switch worksas...

Page 26: ...a bollard during the rising phase the safety pressure switch detects the presence of a weight and immediately interrupts the rising phase and makes the bollards lower to down position inversion contr...

Page 27: ...upt the rising phase and make bollardsgobacktodownposition inversioncontrolbyinductiveloop Wetherthissituationoccurs beforecrossingit isnecessarytowaitforthegreensectortoturn If a pedestrian steps on...

Page 28: ...levant during winter they can be equipped with an heating resistance which prevents ice formation between the cylinder and the fixed side crown allowingfortheproperoperationofthesystem If automatic bo...

Page 29: ...icted or blocked In order to keep an adeguate drainage use a drill machine of suitable length approx 15mm anddrillinthe4holes drivingthetipintothegravelbelowforabout10cm Inthiswayanydepositthatobstruc...

Page 30: ...is rising and the pressure switch detects a pressure increase usually caused by the detection of a weight corresponding to 40 kg or more on the bollard e g a person the bollard stops and goes back to...

Page 31: ...and transmitters check the correct operation from a distance of about 30m and as far as possible verify the wear of thetransmittersandthebuilt inbatteries Check visually the overall status of the cont...

Page 32: ...ghthesuitablespyhole Unfasten and remove the black cap of the hydraulic pump generally placed abovethetransparentspyhole andfillitwiththesameoiluptoabouthalfofthe spyhole ATTENTION USEORIGINALOILONLY...

Page 33: ...ed thisblackwirepowersthefirstpointat 24VDC Move the black wire from the first terminal to the second or the third one to poweranotherlightpoint Test the proper operation of the multiled flashing ligh...

Page 34: ...ocedurebelow Bollardoutofthepit Bollardindownposition turn230Vpowersupplyoff Extract the waterproof protection made of black soft rubber for about 5cm toreachtheadjustingscrew Unscrew and remove the n...

Page 35: ...of 45 and after each step command a rising movement Once the bollard is completely up check the pressure on the pressure gauge and most important hear that the hydarulic unit continues running for abo...

Page 36: ...orreplaced For the pressure switch adjustment please consult the chapter10 SPECIFICOPERATIONS Note generally only the pressure switches of old supply are adjustable and recognizable from a waterproof...

Page 37: ...n reversalfunctionbypressureswitchenabled If it is possible adjust the pressure switch sensibility adjustable old version or replace the pressure switch pre adjusted and hermetic new version to increa...

Page 38: ...n it is lower than a certain value it performs an automatic adjustment When it occurs this problemmaybecausedby The automatic pressure adjust ment has been accidentally excluded The safety inductive d...

Page 39: ...board Consult the chapter 10 SPECIFICOPERATIONS UK EC Declaration of conformity The manufacturer GI BI DI Via Abetone Brennero 177 B 46025 Poggio Rusco MN ITALY declares that the products AUTOMATIC B...

Page 40: ...DI S r l Via Abetone Brennero 177 B 46025 Poggio Rusco MN ITALY Tel 39 0386 52 20 11 Fax 39 0386 52 20 31 E mail info gibidi com Numero Verde 800 290156 w w w g i b i d i c o m Cod AIC0061 01 2020 Re...

Reviews: