background image

SECULOGIC T 320

5

Installation and assembly

Installation and assembly

WARNING!

Danger of electric shock.

X

X

Installation may only be carried out by an expert authorised by GEZE.

X

X

Check that the cables are disconnected before installation.

3.1  Requirements

 

à

Cable routing is in accordance with GEZE cable diagram

 

à

Automatic circuit breakers as primary disconnection on the mains-side

 

à

Compliance with the VDE 0100 and VDE 0815 standards for the cable routing

 

à

Sabotage secured cable routing according to VDE 0833 (on-wall cables in the steel tube)

 

à

For in-wall plug socket variant installed near the door (depth 62.5 mm) with an installation height top of floor 
of 850 mm to a maximum of 1200 mm for the emergency button 

3.2  Install the terminal

Installation of the T 320 terminal is identical to installation for the door control unit TZ 320. Consult the  
installation instructions from the Installation and Commissioning Instructions No. 131537 or the Brief Instructions  
No. 139926. When using a T 320 terminal a TZ 320 is always required. The TZ 320 assumes control of the system. 

Commissioning

4.1  Requirement 

Before the first commissioning of doors with electric locking mechanisms in the escape routes, correlation with 
verification of suitability is to be confirmed by means of a certificate issued by the manufacturer. An expert must 
also ensure that the electric locking mechanism is installed properly and operational (see checklist for  
commissioning in the TZ 320 instructions or in the inspection book).
The door control unit TZ 320 must be in operation, and the connection between the door control unit and  
terminal must be set up according to the connection diagram (page 12). All settings for the terminal are  
implemented via the door control unit TZ 320.

4.2  Service mode

The service mode must be activated at the door control unit TZ 320 in order to set parameters on the terminal. 

4.2.1  Switch on the service mode

Requirement:

 

à

There is no alarm.

 

à

The burglar alarm system is disabled.

X

X

Turn the key left and hold for approximately ten seconds.

 

à

The right LED lights up green, the left and lower LEDs are off.

4.2.2  Switch off the service mode

X

X

Do not make adjustments or select 'end of service mode' in the service menu for three minutes.

 

à

The door control unit and terminal are in normal state again.

Summary of Contents for SECULOGIC T 320 AP

Page 1: ...1 GEZE SECULOGIC T 320 Emergency Exit System Terminal EN Installation And Commissioning Instructions With Connection Diagram...

Page 2: ...gs 6 4 4 Terminal T 320 settings 6 4 5 Description of basic functions 7 5 Operation 8 5 1 Control the terminal T 320 via key operated push button 8 5 2 Open the doors and trigger the alarm in an emerg...

Page 3: ...these data sheets and other documents as well as the detailed installation and commissioning instructions with connection diagram for the door control unit TZ 320 No 131537 on the internet at www gez...

Page 4: ...tem monthly for externally identifiable damages and defects Such damages and defects if existing must be repaired immediately by a GEZE service technician or a professional organisation authorised by...

Page 5: ...es control of the system 4 Commissioning 4 1 Requirement Before the first commissioning of doors with electric locking mechanisms in the escape routes correlation with verification of suitability is t...

Page 6: ...automatically recognised and switched on The terminal can be switched off via the service menu 4 4 1 Switch on terminal X X In the service menu select system environment terminal terminal available T...

Page 7: ...short term release If the door is closed during a pending door alarm it is locked and can only be unlocked again when the alarm has been reset except with actuation of the emergency button or with eme...

Page 8: ...can be opened X X Turn the key left and hold for approximately one second LED 1 flashes green The door is unlocked Note The Unlock function can be disabled via the service menu system environment SCT...

Page 9: ...ge alarm 5 3 2 Acknowledge alarm Precondition The cause of the alarm is eliminated Reset alarm is displayed in the service terminal Acknowledge alarm and lock door X X Turn the key to the right Acknow...

Page 10: ...ause Remedy Sabotage alarm sabotage contact TT Sabotage contact of the terminal is not closed X X Close contact X X Acknowledge alarm after expiry of the sabotage time sabotage time runs Sabotage time...

Page 11: ...l connections Plug and screw terminals max cable cross section 1 mm Clamping field Terminal Function default setting X100 1 GND supply 3 24 V DC supply unit 7 Indirect release 24 V DC 8 Indirect relea...

Page 12: ...sh button key operated push button access control Caution Disconnect red bridge 1 7 in FT 331U or Door contact X106 orange terminal strip Locking mechanism Locking mechanism Door locked 24 V DC Door c...

Page 13: ...e Indirect release Indirect release Indirect release 24 V DC supply GND supply 24 V DC GND 6 3 Connection of external key operated push button to T 320 Connection of the key switch to the T 320 is onl...

Page 14: ...allation in flush mounted socket 60 mm depth 62 5 mm Operating voltage 24 V DC 10 Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 in installed state Application In inte...

Page 15: ...Operating voltage 24 V DC 10 Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 Application In interior spaces with up to 85 air humidity non condensing Operating temperat...

Page 16: ...0 71 E Mail france fr geze com Hungary GEZE Hungary Kft Bart k B la t 105 113 Budapest H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla...

Reviews: