SECULOGIC T 320
6
Commissioning
4.2.3 Connect the service terminal ST 220 with the door control unit
The service terminal is connected with the door control unit via an infrared interface.
3
1
Service terminal ST 220
2
Infrared interface to TZ 320
3
ESC button
X
X
Before covering the control unit, hold the service terminal and press the ON button for approximately one
second.
à
The service terminal is switched on.
X
X
Press the ESC button.
à
The first level of the service menu is displayed.
4.3 Settings
All settings can only be implemented with the service terminal ST 220 via the TZ 320.
4.4 Terminal T 320 settings
A terminal connected to TZ 320 is automatically recognised and switched on. The terminal can be switched off
via the service menu.
4.4.1 Switch on terminal
X
X
In the service menu, select
system environment
>
terminal
>
terminal
available
.
à
The upper display line of the service terminal shows the selected value.
4.4.2 Switch off terminal
X
X
In the service menu, select
system environment
>
terminal
>
terminal
unavailable
.
à
The upper display line of the service terminal shows the selected value.
4.4.3 Set sabotage contact
X
X
In the service menu, select
system environment
>
sabotage contacts
.
X
X
To evaluate sabotage contacts, select
TT
>
sabotage contact TT active : yes
.
X
X
To not evaluate sabotage contacts, select
TT
>
sabotage contact TT active : no
.
4.4.4 Short-term unlock and alarm setup
The settings for short-term unlock and alarm setup for the terminal are implemented by the door control unit.