SECULOGIC T 320

10

Operation

5.4  Read out fault report (via TZ 320)

Faults in the system are indicated via flashing of LED 3.

X

X

Connect the service terminal with the door control unit.

 

à

The fault report is shown on the display of the service terminal.

X

X

Find out the cause of malfunction and correct the fault with the aid of the following table.

The table only contains faults that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further fault reports.

Fault report

Cause

Remedy

TT communication

Connection with door control unit is faulty

X

X

Switch off the terminal via the service menu

X

X

Establish connection to the terminal

X

X

Change the terminal

5.5  Read out alarm signal (via TZ 320)

Misuse of the system or emergency situations is indicated via alarm tones and lighting up of LED 3.

X

X

Connect the service terminal to the door control unit and press the ESC button.

 

à

The alarm signal is shown on the display of the service terminal.

X

X

Establish the cause of the alarm and cancel the alarm with the aid of the following table.

The table only contains alarm signals that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further alarm signals.

Alarm signal

Cause

Remedy

Sabotage alarm

sabotage contact TT Sabotage contact of the terminal is not  

closed

X

X

Close contact

X

X

Acknowledge alarm after expiry of the 

sabotage time

sabotage time runs Sabotage time unexpired

X

X

Acknowledge alarm after expiry of the 

sabotage time

Indirect release

EB TT pushed

Indirect release via terminal

X

X

Reset the emergency button on the 

terminal

fuse failure

Fuse F1 is defective

X

X

Change the fuse

J1, J2 jumper for indirect release to TZ 320 

falsely set

X

X

Confirm the emergency button of the 

T 320

X

X

Reset the emergency button of the T 320

Acknowledge alarm

Cause of the alarm eliminated

X

X

Acknowledge alarm via the key-operated 

push button

5.6  Correct fault

Fault

Cause

Remedy

Emergency button T 320 

without  

function, no  

alarm signal  

available

J1J2 jumper for indirect release to  

TZ 320 falsely set

X

X

Disconnect power supply to system

X

X

Set jumpers J1 and J2 to external  

power supply

X

X

Connect power supply

 

à

Alarm signal for indirect release is 

displayed

X

X

Confirm the emergency button of the  

T 320 and reset

X

X

Acknowledge alarm

By actuating the key- 

operated push button of 

the T 320 / TZ 320, all LEDs 

and the emergency button 

lighting go out

Ribbon cable incorrectly connected between 

SCT 320 and TZ 320 / T 320 

X

X

Connect ribbon cable correctly

All LEDs are off despite  

power supply

F1 locking device of the TZ 320 is defective

X

X

Change the F1 fuse 

(GEZE Id-No. 138362, VE 10)

Summary of Contents for SECULOGIC T 320 AP

Page 1: ...1 GEZE SECULOGIC T 320 Emergency Exit System Terminal EN Installation And Commissioning Instructions With Connection Diagram...

Page 2: ...gs 6 4 4 Terminal T 320 settings 6 4 5 Description of basic functions 7 5 Operation 8 5 1 Control the terminal T 320 via key operated push button 8 5 2 Open the doors and trigger the alarm in an emerg...

Page 3: ...these data sheets and other documents as well as the detailed installation and commissioning instructions with connection diagram for the door control unit TZ 320 No 131537 on the internet at www gez...

Page 4: ...tem monthly for externally identifiable damages and defects Such damages and defects if existing must be repaired immediately by a GEZE service technician or a professional organisation authorised by...

Page 5: ...es control of the system 4 Commissioning 4 1 Requirement Before the first commissioning of doors with electric locking mechanisms in the escape routes correlation with verification of suitability is t...

Page 6: ...automatically recognised and switched on The terminal can be switched off via the service menu 4 4 1 Switch on terminal X X In the service menu select system environment terminal terminal available T...

Page 7: ...short term release If the door is closed during a pending door alarm it is locked and can only be unlocked again when the alarm has been reset except with actuation of the emergency button or with eme...

Page 8: ...can be opened X X Turn the key left and hold for approximately one second LED 1 flashes green The door is unlocked Note The Unlock function can be disabled via the service menu system environment SCT...

Page 9: ...ge alarm 5 3 2 Acknowledge alarm Precondition The cause of the alarm is eliminated Reset alarm is displayed in the service terminal Acknowledge alarm and lock door X X Turn the key to the right Acknow...

Page 10: ...ause Remedy Sabotage alarm sabotage contact TT Sabotage contact of the terminal is not closed X X Close contact X X Acknowledge alarm after expiry of the sabotage time sabotage time runs Sabotage time...

Page 11: ...l connections Plug and screw terminals max cable cross section 1 mm Clamping field Terminal Function default setting X100 1 GND supply 3 24 V DC supply unit 7 Indirect release 24 V DC 8 Indirect relea...

Page 12: ...sh button key operated push button access control Caution Disconnect red bridge 1 7 in FT 331U or Door contact X106 orange terminal strip Locking mechanism Locking mechanism Door locked 24 V DC Door c...

Page 13: ...e Indirect release Indirect release Indirect release 24 V DC supply GND supply 24 V DC GND 6 3 Connection of external key operated push button to T 320 Connection of the key switch to the T 320 is onl...

Page 14: ...allation in flush mounted socket 60 mm depth 62 5 mm Operating voltage 24 V DC 10 Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 in installed state Application In inte...

Page 15: ...Operating voltage 24 V DC 10 Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 Application In interior spaces with up to 85 air humidity non condensing Operating temperat...

Page 16: ...0 71 E Mail france fr geze com Hungary GEZE Hungary Kft Bart k B la t 105 113 Budapest H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla...

Reviews: