SECULOGIC T 320
10
Operation
5.4 Read out fault report (via TZ 320)
Faults in the system are indicated via flashing of LED 3.
X
X
Connect the service terminal with the door control unit.
à
The fault report is shown on the display of the service terminal.
X
X
Find out the cause of malfunction and correct the fault with the aid of the following table.
The table only contains faults that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further fault reports.
Fault report
Cause
Remedy
TT communication
Connection with door control unit is faulty
X
X
Switch off the terminal via the service menu
X
X
Establish connection to the terminal
X
X
Change the terminal
5.5 Read out alarm signal (via TZ 320)
Misuse of the system or emergency situations is indicated via alarm tones and lighting up of LED 3.
X
X
Connect the service terminal to the door control unit and press the ESC button.
à
The alarm signal is shown on the display of the service terminal.
X
X
Establish the cause of the alarm and cancel the alarm with the aid of the following table.
The table only contains alarm signals that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further alarm signals.
Alarm signal
Cause
Remedy
Sabotage alarm
sabotage contact TT Sabotage contact of the terminal is not
closed
X
X
Close contact
X
X
Acknowledge alarm after expiry of the
sabotage time
sabotage time runs Sabotage time unexpired
X
X
Acknowledge alarm after expiry of the
sabotage time
Indirect release
EB TT pushed
Indirect release via terminal
X
X
Reset the emergency button on the
terminal
fuse failure
Fuse F1 is defective
X
X
Change the fuse
J1, J2 jumper for indirect release to TZ 320
falsely set
X
X
Confirm the emergency button of the
T 320
X
X
Reset the emergency button of the T 320
Acknowledge alarm
Cause of the alarm eliminated
X
X
Acknowledge alarm via the key-operated
push button
5.6 Correct fault
Fault
Cause
Remedy
Emergency button T 320
without
function, no
alarm signal
available
J1J2 jumper for indirect release to
TZ 320 falsely set
X
X
Disconnect power supply to system
X
X
Set jumpers J1 and J2 to external
power supply
X
X
Connect power supply
à
Alarm signal for indirect release is
displayed
X
X
Confirm the emergency button of the
T 320 and reset
X
X
Acknowledge alarm
By actuating the key-
operated push button of
the T 320 / TZ 320, all LEDs
and the emergency button
lighting go out
Ribbon cable incorrectly connected between
SCT 320 and TZ 320 / T 320
X
X
Connect ribbon cable correctly
All LEDs are off despite
power supply
F1 locking device of the TZ 320 is defective
X
X
Change the F1 fuse
(GEZE Id-No. 138362, VE 10)