Modifying the operating parameters of the recharging station
Gewiss
13. Modifying the operating parameters of the recharging station
Even after installing the product, you can still modify certain station operating parameters by means of a text file to be saved in the
micro SD card inserted in the recharging station itself.
Create a text file on your computer and rename it “config.ini”. Insert the parameters you want to alter in this file. The addition of
parameters must follow the indications given below.
The parameters that can be modified are:
Function
description
Name of the
parameter to be
used
Options available and examples
Language
LANGUAGE
By default, the station is set with the Italian language. The language can be changed using the
LANGUAGE parameter. The languages that can be set, and the parameters to be used, are:
EN= English
FR= French
DE= German
ES= Spanish
IT= Italian
RO= Romanian
HU= Hungarian
Example
LANGUAGE=IT
or
LANGUAGE=EN
Maximum input
current
MAXAMPERAVAILABLE
You can set an input current other than the one set in the factory, to suit the real availability and
avoid problems during recharging. To do this, use the MAXAMPERAVAILABLE parameter
Example
MAXAMPERAVAILABLE=64
Maximum current
per socket-outlet
AMPERSOCKET
You can set a recharging current for each socket-outlet other than the one set in the factory, to suit
the real availability (e.g. if the maximum input current value is changed) and avoid problems during
recharging. To do this, use the AMPERSOCKET1 and/or AMPERSOCKET2 parameter
Example
AMPERSOCKET1=32
AMPERSOCKET2=16
Date
DATETIME
If the date on the recharging station is not correct, you can change it using the DATETIME parameter.
The format is YYYY/MM/DD-hh:mm
Example
DATETIME=2019/08/15-14:30
Log level
LOGLEVEL
The LOG level saved by the recharging station on the micro SD card can be altered via the LOGLEVEL
parameter. You can choose one of 5 levels, from 0 (limited verbosity) to 4 (high verbosity)
Example
LOGLEVEL=1