29
Press button briefly.
Raise or lower the liquid level in the vessel
to the desired value.
Use button if you first want to establish
a different switchpoint or the proportional
band.
Press button briefly.
Lower or raise the liquid level until switch
point 4 within the control range is reached.
Attention:
In the event of a system malfunction, the
LED(s) “Bus status” and/or “Power” will be
flashing
rapidly
when in program mode.
Press button briefly.
Switchpoint 4 is now saved.
Press button briefly.
The lower limit of the proportional band X
P
(switchpoint 3) is now selected.
Press button briefly.
Lower or raise the liquid level until switchpoint
3 within the control range is reached.
Example:
Liquid level switchpoint 3 = 40 % and
liquid level switchpoint 2 = 60 % make an
X
P
value
(60 % – 40 %) = 20 %
.
The setpoint is
50 %
.
Establishing switchpoints and proportional range
Commissioning
– continued –