30
Establishing switchpoints and proportional range
– continued –
Commissioning
– continued –
Press button briefly.
Switchpoint 3 is now saved.
Press button briefly.
The upper limit of the proportional band X
P
(switchpoint 2) is now selected.
Press button briefly.
Lower or raise the liquid level until switchpoint 2
within the control range is reached.
Example:
Liquid level switchpoint 3 = 40 % and
liquid level switchpoint 2 = 60 %
make an
X
P
value
of
20 %
Press button briefly.
Switchpoint 2 is now saved.
Press button briefly.
Switchpoint 1 is now selected.