22
Basic Settings
– continued –
The level controller features the following factory set default values:
n
Relay deenergizing delay, switchpoint 1:
1s
n
Relay deenergizing delay, switchpoint 4:
1s
n
Relay deenergizing delay, switchpoint 1:
3s
n
Relay deenergizing delay, switchpoint 4:
3s
n
Baud rate:
250 kb/s
n
Proportional range X
P
:
20 %
n
Node ID:
40
n
Switchpoint 1:
80 %
n
Switchpoint 4:
20 %
n
Dead band:
0 %
Fig. 12
Factory setting
The controller NRR 240 is specially designed for level control in steam boilers and feedwater
deaerators. The NRR 240 is a proportional controller with steadystate deviation.
The positive and negative deviation lies within the proportional band (X
P
) preselected by the user.
If is possible to control electric and pneumatic (optional) actuators.
The control of electric actuators is effected by an analogue signal which, in combination with an ac
tive position feedback coming from the valve, is converted in the controller into a threeposition step
ping signal. The control pulses for the electric actuator are transmitted by the relay integrated in the
controller.
The control of pneumatic valve actuators is effected by an analogue signal 4 – 20 mA. The analogue
signal is transmitted directly from the proportional controller to the positioner of the pneumatic control
valve, which means that an active position acknowledgement is not possible.
X
P
Werte:
X
P
> large permanent deviation, valve reacts sluggishly.
X
P
< no permanent deviation, valve may be hunting, recommended X
P
value 20 % to 60 %.
Function of the controller
1/80 %
2/60 %
3/40 %
4/20 %
20 %
100 %
0 %
Summary of Contents for NRR 2-40
Page 1: ...1 E N English Level Controller NRR 2 40 Original Installation Instructions 810369 06 ...
Page 9: ...9 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Page 10: ...10 Design 0 Fig 3 9 NRR 2 40 9 a ...
Page 11: ...11 Functional Elements NRR 2 40 Fig 5 Fig 4 1 7 6 5 4 3 2 8 ...
Page 13: ...13 Installation continued Fig 6 Example of Installation b 9 0 0 Fig 7 20 20 a ...