LRR 1-52, LRR 1-53, URB 55 - USA - Installation & Operating Manual -
850703-00
Configuring the conductivity controller
Setting automatic intermittent blowdown
If the function “MIN relay for intermittent
blowdown” is set on the code switch of the
conductivity controller (see page 63,
Fig. 19
),
you can assign parameters using the Automatic
Intermittent Blowdown button.
Open the menu.
Auto / Manual
Switch between automatic
intermittent blowdown and manual
mode.
Description of parameters:
Initiate intermittent blowdown
manually
The display lights up amber when
intermittent blowdown is active or
has been initiated manually.
Intermittent blowdown interval
(in hours)
Intermittent blowdown time (in
seconds)
The intermittent blowdown valve
is switched on regularly at set
intervals and opens for the set
intermittent blowdown time.
Intermittent blowdown pulses
Number of pulses
Pulse interval (in seconds)
Set the time between the individual
intermittent blowdown pulses.