37
LRR 1-52, LRR 1-53, URB 55 - USA - Installation & Operating Manual -
850703-00
Changing the equipment settings
Code switch
D
- sliding switch, white
Conductivity controller LRR 1-52, LRR 1-53
Code switch
D
S1
S2 *
S3 *
S4
Configuration
OFF
MIN relay output as MIN alarm
(factory setting)
ON
MIN relay output for actuating an intermittent blowdown valve
OFF
Node ID = 72 *
ON
Node ID = 69 - compatibility with older equipment
(factory setting)
OFF
Terminal 3/4 (Out 2) as actual value output (X)
(factory setting) *
ON
Terminal 3/4 (Out 2) as manipulated variable output (Yw)
OFF
Electrical conductivity measured in µS/cm
(factory setting)
ON
Electrical conductivity measured in ppm
* Controller software version 311178.13 or later
Fig. 19