Installer manual NETZERO
GEOSMART ENERGY
59
EN
Specification NETZERO 12 kW
Units
Heating only
Passive
cooling
and
heating
Reversible
Reversible
and
passive
cooling
Application
Place of installation
-
Indoors
Type of brine system
-
Geothermal
Heating
-
HTR - High temperature recovery system
-
Integrated active cooling
-
--
--
Integrated Free cooling
-
--
--
Performance
Compressor modulation
%
12.5 - 100
Heating power
2
, B0W35
10
kW
2.1 - 16
COP
max2
/ Heating power
2
B0W35
10
- / kW
4.6 / 7.3
Active cooling power
2
, B35W7
10
kW
--
2.1 -15
EER
2
/ Active cooling power
2
B35W7
10
- / kW
--
5.2 / 6.3
Maximum DHW temperature without backup
11
°C
63
Maximum DHW temperature with backup
5,11
°C
70
Sound power level
6
dBA
34 - 45
Energy label /
η
s
average climate
--
A+++ / 194%
Operation
limits
Heating temperatures / Maximum setpoint
°C
10 - 60 / 60
Cooling temperatures / Min. setpoint
°C
-20 – 35 / -15
0 – 35 / 2
Brine heating temperatures
°C
-25 - +35
Dissipation cooling temperatures
°C
10 - 60
Min./max. refrigerant circuit pressure
bar
2 / 45
Production circuit pressure / pre-charge
bar
0.5 - 3 / 1.5
Brine circuit pressure / pre-charge
bar
0.5 - 3 / 0.7
Maximum ACS storage tank pressure
11
bar
8
Working
fluids
Refrigerant type / GWP
--
R410A / 2088
Charge / T CO
2
eq
Kg/ton
0,9 / 1,88 (without HTR)
1 / 2,09 (with HTR)
1 / 2,09
Compressor oil type / charge
kg
POE / 0,74
Electrical
control data
1/N/PE 230 V / 50-60 Hz
8
-
Maximum recommended external protection
9
A
C16A
Primary transformer circuit fuse
A
0.5
Secondary transformer circuit fuse
A
2.5
Heat pump
electrical
data:
Single phase
1/N/PE 230 V / 50-60 Hz
8
-
Maximum recommended external protection
9
A
C32A
Maximum consumption
2
, B0W35
kW/A
4.2/18.6
Maximum consumption
2
, B0W55
kW/A
5/21.7
Start-up intensity minimum/maximum
7
A
2/8
Correction of cosine φ
-
0.96-1
Electrical
integrated
resistance
backup data
Connection option 1/N/PE 230Vac / 50-60 Hz
8
-
Number of elements
-
1 / 2 / 3
External protection recommended 1 / 2 / 3
A
C16A / C20A / C32A
Max. consumption 1 / 2 / 3
kW
2 / 4 / 6
Max. consumption 1 / 2 / 3
A
8.8 / 17.6 / 26.4
Dimensions
and weight
Height x width x depth
mm
NETZERO BW: 1060x600x710
NETZERO CW: 1845x600x720
Empty weight (without assembly)
kg
B: 185
C: 246
B: 193
C: 254
B: 185
C: 246
B: 193
C: 254