Installer manual NETZERO
GEOSMART ENERGY
31
EN
Services control
1.
Used to enable remote control of the SUMMER / WINTER program. Also allows select
DI1 / DI2 / DI3 as digital input for winter / summer remote control. With SG mode and
winter / summer remote control activated, it is not allowed select DHW remote
control. Also used to select the program control operation logic.
A.
NO: Closed contact to select WINTER, open contact to select SUMMER.
B.
NC: Closed contact to select SUMMER, open contact to select WINTER.
2.
Used to enable remote control of DHW production. Also allows select DI1 / DI2 / DI3
as digital input for DHW remote control. With SG mode and DHW remote control
activated, it is not allowed select winter / summer remote control. Used to select the
DHW remote control operation logic.
A.
NO: Closed contact to enable DHW production.
B.
NC: Open contact to enable DHW production.
Note:
When DHW production is enabled, it will only start if there is a request according to
the parameters established as USER and if there is no higher priority service with a request.
3.
Used to enable remote control of pool production. Used to select the pool remote
control operation logic.
A.
NO: Closed contact to enable pool production.
B.
NC: Open contact to enable pool production.
Note:
When pool production is enabled, it will only start if there is a request according to
the parameters established as USER and if there is no higher priority service with a request
BMS remote control
1.
Used to enable remote control via BMS or BMS / FBus2 communication ports through
ModBus protocol.
Note:
To access the controller via the BMS or BMS2 ports, they must be configured as
MODBUS SLAVE EXTENDED.
BMS configuration
1.
Used to assign the address of the BMS port.
2.
Used to configure the communication parameters via the BMS port.
Note:
This port can be used to connect several expansion cards for communication that
allow remote access to the controller through various protocols.
BMS2 configuration
1.
Used to assign the controller BMS2 port address.
2.
Used to configure the communication parameters via the BMS2 port.
Note:
This port can be used to connect indoor bus terminals with MODBUS MASTER
configuration.
Note:
This port can be used to access the controller remotely with MODBUS SLAVE
EXTENDED configuration.
Installer menu
2/7
a.Change language
b.Configuration
c.Information
Configuration
5/7
d.Auxiliary system
e.Remote control
f.Protections
Remote Control
2/3
a.EVU/SG Control
b.Services Control
c.BUS Control
Services Control
Wint./Summ.:
DI1
NA
DHW:
- -
NA
Pool:
DI4
NA
Installer menu
2/7
a.Change language
b.Configuration
c.Information
Configuration
5/7
d.Auxiliary system
e.Remote control
f.Protections
Remote Control
3/3
a.EVU/SG Control
b.Services Control
c.BUS Control
BMS remote control
Enable:
BMS CONFIG.
ADDRESS:
17
PROTOCOL:
MB SLV EXT .2
BAUDRATE:
19200
STOP BIT:
2
PARITY:
None
BMS2 CONFIG.
ADDRESS:
5
PROTOCOL:
MODBUS MASTER
BAUDRATE:
4
STOP BIT:
2
PARITY:
None