Installer manual NETZERO
GEOSMART ENERGY
32
EN
Configuración cascada
1.
Used to enable / disable communication between controllers through the pLan port.
2.
Used to select the number of slaves. Maximum 2.
3.
Used to assign the network address of the controller
Note:
This port can be used to connect blocks of NETZERO heat pumps with parallel
operation.
2.13.
Protection configuration
Limit compressor
1.
Used to limit the modulation range of the compressor for each production service. This
option is used to adjust the range of thermal power supplied to the production circuit,
absorbed in the source circuit or the electrical consumption of the heat pump.
Limit compressor 2
1.
Used to limit the heat pump electrical consumption. And for each service, it limits the
thermal capacity.
Limit pumps
1.
Used to limit the modulation range of the source and production circulation pumps.
This option is used to adjust the flow of the source and production circuits.
Source protection
1.
Used to adjust the maximum and minimum temperature of the source circuit. If any of
the limit values are reached, the source temperature alarm is activated.
2.
Used to set the minimum pressure of the source circuit, under which the alarm is
triggered.
Danger:
The setting of the minimum source temperature is a very important parameter in
the start-up of the equipment. A bad configuration of this value can lead to serious
equipment damage due to freezing. The minimum source temperature must be at least
5ºC higher than the freezing temperature of the fluid used. If you are not sure of the
freezing temperature of the fluid used, check it with a refractometer.
CASCADE configuration
Cascade: Master
Number of Slaves:
1
Controler address: 1
Installer menu
2/7
a.Change language
b.Configuration
c.Information
Configuration
6/7
e.Remote control
f.Protections
g.Probe conf.
Compressor capacity
Min
Max
Heating:
25
100 %
Cooling:
25
100 %
DHW:
25
100 %
Pool:
25
100 %
Compressor capacity
Consumption:
1.5kW
Heating:
19.7kW
Cooling:
15.5kW
DHW:
14.3kW
Pool:
18.0kW
Pumps capacity
Min
Max
Brine:
30.0
89.1 %
Produc.:
30:0
87.4 %
Brine protection
MaximumT:
40.0ºC
MinimumT:
2.0ºC
MinimumP:
0.5bar