Installer manual NETZERO
GEOSMART ENERGY
14
EN
1.12.
COOLING Menu
Cooling
This is used to enable the COOLING mode and adjust the active and passive cooling cut-off
temperatures. The COOLING mode cannot be activated for outside temperatures under the
cooling cut-off temperature. Only PASSIVE COOLING can be activated for outside
temperatures between passive and active cut-off temperatures. ACTIVE COOLING
activation is only allowed for outside temperatures over the active cooling cut-off
temperature.
The
icon indicates that there is a time schedule activated in the COOLING mode.
Cooling buffer
This shows the setpoint temperature of the cooling buffer storage tank and allows
adjustments to be made to the start-up temperature differential.
Cooling units
This can be used to adjust the cooling target outlet temperatures programmed by the
technical service. Each ramp increases or decreases the outlet temperature by 2°C.
Interior terminals
Used to show and adjust the inside environment temperature setpoint (Tcons) and the
comfort temperature differential (DTc) of the terminals of each outlet unit.
If the heat pump is in the COMBINED program, it can also be used to show and adjust the
temperature switch differential (DTsw) between HEATING and COOLING modes.
Auxiliary X cooling
Used to enable the auxiliary heating system in both EMERGENCY and SUPPORT mode.
In EMERGENCY mode, the auxiliary system is activated automatically if there are any active
alarms that prevent compressor start-up.
In SUPPORT mode, the auxiliary system is activated automatically for normal COOL AIR
production, as programmed by the technical service.
1.13.
DHW/LEGIONELLA PROT. Menu
DHW
This is used to enable the DHW mode and adjust the setpoint temperature and start-up
temperature differential for the DHW storage tank. It is also used to adjust the setpoint
temperature for DHW heating with the HTR system.
The
icon indicates that there is a time schedule activated in the DHW mode.
User menu
4/8
Heating
Cooling
DHW/Legionella prot.
Cooling
Enable:
StopT:
Active:
28.0ºC
Passive:
20.0ºC
Cooling buffer
SetT:
8.0ºC
DTstart:
3.0ºC
Cooling groups
- 0 +
- 0 +
DG1:
SG2:
SG3:
SG4:
Room terminals
SetT
DTc
ºC
ºC
DG1:
20.0
2.0
SG2:
21.0
2.0
SG3:
22.0
2.0
SG4:
21.0
2.0
Auxiliary cooling X
Emergency:
Support:
User menu
5/8
Refrigeración
DHW/Legionella prot.
Pool
DHW
Enable:
Remote control: ON
SetT
48.0ºC
DTstart:
5.0ºC
SetT HTR:
70.0ºC