Installer manual NETZERO
GEOSMART ENERGY
46
EN
DIGITAL OUTPUTS
CONNECTIONS
DESCRIPTION
Connection terminal
Controller terminal
Type
Signal
Block III / DO1
/ J16 / NO1-NC1
Activation 24Vac / 1A max
Passive cooling production
Block III / DO2
/ J27 / NO9-NC9
Activation 24Vac / 2A max
Pool production
Block III / DO3
/ J27 / NO10-
NC10
Activation 24Vac / 2A max
DHW production
Block III / DO4
/ J28 / NO11
Activation 230Vac / 2A max
DHW Recirculation
Block III / DO5
/ J28 / NO12
Activation 230Vac / 2A max
DG1 group production
Block III / DO6
/ J28 / NO13
Activation 230Vac / 2A max
SG2 group production
Block III / DO7
/ J22 / NO6
Activation 230Vac / 2A max
HTR system production
Block III / DO8
/ J23 / NO7
Activation 230Vac / 2A max
Comp circulator activation
Block III / DO9
/ J24 / NO8
Activation 230Vac / 2A max
Alarm signal
Block IV / DO10
/ J17 / Out2
Activation 230Vac / 1A max
Buffer storage tank resistor /
Internal resistor
Block IV / DO11
/ J18 / Out3
Activation 230Vac / 2A max
DHW inter-accumulator resistor
Block IV / DO12
/ J19 / Out4
Activation 230Vac / 2A max
Heating / cooling consumption
Block IV / DO13
/ J20 / Out5
Activation 230Vac / 2A max
Active cooling production
Block IV / DO14
pCOe / J5 / NO1
Activation 230Vac / 2A max
SG3 group production
Block IV / DO15
pCOe / J6 / NO2
Activation 230Vac / 2A max
SG4 group production
Block IV / DO16
pCOe / J7 / NO3NC3
Activation 230Vac / 2A max
Air source
Block IV / DO17
pCOe / J8 / NC3
Activation 230Vac / 2A max
Geothermal source
PROTECTIONS
CONNECTIONS
DESCRIPTION
Connection terminal
Controller terminal
Type
Signal
Block III / PS
Inverter / 3
Safety switch
High pressure switch
Block III / ESS
Inverter / 4
Safety switch
External safety switch
COMMUNICATIONS
CONNECTIONS
DESCRIPTION
Serial port
Controller terminal
Type
Signal
pLAN
/ J15 Phone connector
RJ11
Controller screen
/ J14 Plug-in connector
RS485 Modbus RTU
Controller network connector
FBus
/ J9
RS485 ModBus RTU
Compressor inverter
FBus2
/ J29
RS485 ModBus RTU
Outdoor bus terminals
Expansion module pCOe
Outside temperature probe
BMS Card
/ J13
RS485 ModBus RTU
Connector for remote access
communication cards
BMS2
/ J11
RS485 ModBus RTU
Remote access through bus
Remote outside temperature probe
Expansion
valve
/ J12
Stepper motor
Unipolar valve control