Displayed Message:
Cause:
Definition/Solution
:
5. "MENU?"
Security code
Choose menu: CAL or BATCH
properly entered
(when active) OR
MOD key pressed
6. "NEW KF"
Auto CAL procedure
K-factor successively calculated
successful
using auto cal mode (sec. 3.6)
7. "OVERRUN"
Flow measured on
Relay 2 is energized due to leaky or
input while batch
slow valve closure. Press STOP to
stopped or in delay
cancel (de-energize) alarm relay #2.
between batches
Persistent leaks will re-activate
overrun alarm condition.
8. "RAM ERR"
Power glitch or EMI
Re-cycle unit power for start-up
ram disturbance
9. "RUN" or
Batch in progress
Displays number of batch cycles ran
"RUN 12345" (number
in quantity
in quantity batching mode
of run shown)
batching mode
10. "SEC CODE"
MOD key pressed
Unit prompts the operator to enter
with security code
the entire 4-digit code for full CAL/
active
BATCH menu access, or 2 least
significant digits for BATCH (only)
menu access (sec. 3.4)
11. "...SSR CARD BAD
Enter key pressed
Remote start, stop, resume (SSR)
MISSING OR
while unit stopped
card properly installed (sec. 4.5)
WRONG TYPE..."
12. "STOPPED"
STOP pressed
Batch cycle stopped by pressing
during batching
STOP key. Resume batch cycle by
cycle
pressing RESUME
13. "00 00 10"
Delay between
Shows remaining time delay
(factory default shown)
consecutive batches
between batch cycles (sec. 3.7)
(continuous or
quantity mode)
14. "__ __ __ __"
Flow display or
Change flow display decimal for less
batch volume
resolution (sec. 3.5)
overrange
31