3.2 CAL Menu Functions
1. K-factor:
Number of pulses generated by a
flow sensor per volumetric unit. K-factors are listed
in your flow sensor manual by pipe size and
material.
2. K-factor decimal:
Changes the K-factor
decimal position.
3. Flow display timebase:
Changes the time-
base used in the flow rate display. Timebase
modifications do not affect the batch display or
flow accumulator. The flow display decimal may
require adjustment for certain flow rates.
4. Flow display averaging:
Averages the sensor
input frequency to compensate for turbulence
within the process pipe. High averaging values
will smooth erratic flow rates. Low averaging
values are used for stable flow rates.
5. Flow display decimal:
Changes the flow
display decimal position. Decimal may require
adjustment to prevent display overflow when
certain K-factor/timebase values are used.
6. Totalizer display mode:
Changes the
totalizer display. Select
flow volume
to read total
volume, or
batch count
to read number of batches
processed.
7. Totalizer reset:
Resets totalizer to zero.
8. Totalizer multiplier:
Multiplies the totalizer by
an user specified value (
flow volume
mode only).
Not shown in menu when
batch count
mode is
selected.
13
K-factor range:
0.0001 to 19999
K-factor decimal:
X.XXXX - 4, XX.XXX - 3,
XXX.XX - 2, XXXX.X - 1,
XXXXX - 0
Flow display timebase:
1= seconds
2= minutes
3= hours
4= days
Flow display averaging:
selectable from 1 to 10 s
Flow display decimal:
X.XXXX - 4, XX.XXX - 3,
XXX.XX - 2, XXXX.X - 1,
XXXXX - 0
Totalizer multiplier:
X 0.001, 0.01, 0.1, 1, 10,
100, 1000