GLX-RSS-2-300 WL User Manual
13
GLX-RSS-2-300 WL Non-Contact Flow Meter
5
Surface Velocity Radar Settings
Communication Interfaces Parameters
Baud rate
1
0
0
1
0
0
1
0
1
1
0
1
N bits per second
Band Rate
1 bit
Baud rate -
Configures the baud rate (bits per second) for serial communication on both RS-232
and RS-485 data lines. This setting controls how many bits are sent on the communication line in
one second. The available values are standardized. Using higher baud rates over longer lines may
introduce errors in transferred data. The default instrument baud rate is 9600 bps.
RS-232 and RS-485 protocol
1
0 0
1
0
$ABCD...
Protocol RS232 and RS485
RS-232 protocol
- Selects the communication protocol to be used for data communication on RS-
232 interface. The NMEA protocol is a GPS-like human readable messaging protocol where each
data packet contains a checksum for data integrity verification.
RS-485 protocol
- Selects the communication protocol to be used on RS-485 half-duplex interface.
HS protocol is a simple request-response protocol for the simplest applications. Modbus RTU
protocol is a standardized protocol which is commonly used in automation and instrumentation as
it provides all measurements with detailed diagnostics of device operation and the possibility to
change the instrument’s operating parameters.
Summary of Contents for GLX-RSS-2-300 WL
Page 71: ...2022 ...