MISTRAL
ENGLISH
Guide for the installer
Page
TECHNICAL SPECIFICATIONS
Model
324
324
LS
424
424
LS
Power supply (Vdc)
24
Power (W)
70
Current (A)
3
Thrust (daN)
280
Rated thrust (daN)
190
Travel (mm)
300
400
Rod extension speed (cm/sec)
1.6
Leaf max. (m)
3
a
4
b
Type and use frequency at 20° C
100%
Approximate cycle/hour at 20° C
~ 75
Protection class
IP54
Noise (dB(A))
< 70
Operating ambient temperature (°C)
-20 +55
Operator weight (Kg)
7.8
8
Operator dimensions (mm)
See fig. 2
a
With leaves exceeding 2.5 m the fitting of an electric lock is
required to ensure the leaf locking. The model
R
must always be
coupled to an electric lock.
b
With leaves exceeding 3 m the fitting of an electric lock is required
to ensure the leaf locking. The model
R
must always be coupled
to an electric lock.
TECHNICAL SPECIFICATIONS
Model
300 115V
300
LS
115V
400 115V
400
LS
115V
Power supply (Vac)
115
Power (W)
300
Current (A)
2.5
Thermal protection (°C)
140
Capacitor (µF)
25
Thrust (daN)
300
Rated thrust (daN)
200
Travel (mm)
300
400
Rod extension speed (cm/sec)
1.85
Leaf max. (m)
3
a
4
b
Type and use frequency at 20° C
S3
30%
S3
35%
S3
30%
S3
35%
Approximate cycle/hour at 20° C
~ 30
~ 25
Protection class
IP54
Noise (dB(A))
< 70
Operating ambient temperature (°C)
-20 +55
Operator weight (Kg)
7.8
8
Operator dimensions (mm)
See fig. 2
a
With leaves exceeding 2.5 m the fitting of an electric lock is
required to ensure the leaf locking. The model
R
must always be
coupled to an electric lock.
b
With leaves exceeding 3 m the fitting of an electric lock is required
to ensure the leaf locking. The model
R
must always be coupled
to an electric lock.
2.1. VERSIONS
Model
Version
Mistral 300
230 Vac non-reversing gearmotor
Mistral 300 R
230 Vac reversing gearmotor
Mistral 300 LS
230 Vac non-reversing gearmotor with opening
and closing limit switches
Mistral 300 R LS
230 Vac reversing gearmotor with opening and
closing limit switches
Mistral 400
230 Vac non-reversing gearmotor
Mistral 400 R
230 Vac reversing gearmotor
Mistral 400 LS
230 Vac non-reversing gearmotor with opening
and closing limit switches
Mistral 400 R LS
230 Vac reversing gearmotor with opening /
closing limit switches
Mistral 324
24 Vdc non-reversing gearmotor
Mistral 324 LS
24 Vdc non-reversing gearmotor with opening
and closing limit switches
Mistral 424
24 Vdc non-reversing gearmotor
Model
Version
Mistral 424 LS
24 Vdc non-reversing gearmotor with opening
and closing limit switches
Mistral 300 -115V-
115 Vac non-reversing gearmotor
Mistral 300 LS -
115V-
115 Vac non-reversing gearmotor with opening
and closing limit switches
Mistral 400 -115V-
115 Vac non-reversing gearmotor
Mistral 400 LS -
115V-
115 Vac non-reversing gearmotor with opening
and closing limit switches
For CSA-UL approved operators, control unit 455 MPS UL 115
must be used in order to maintain the approval.
3. INSTALLATION
3.1. ELECTRICAL SET-UP (standard system)
With reference to Figure 3.
Pos.
Description
Cables
230 Vac - 115 Vac
24 Vdc
a
Operators
4x1 mm
2
2x1.5 mm
2
b
TX photocells
4x0.5 mm
2
c
RX photocells
2x0.5 mm
2
d
Key selector
2x0.5 mm
2
e
Flashing lamp
2x1.5 mm
2
f
Control unit
3x0.5 mm
2
(power supply)
g
Mechanical stops
—
Use suitable tubes and/or hoses to lay electric cables
To avoid any kind of interference always separate low-vol-
tage accessories and control cables from 230/115 V~ power
supply cables using separate sheaths.
3.2. PRELIMINARY CHECKS
To ensure a correct operation of the automated system, make sure
the following requirements are observed as for the gate structure
(existing or to be created):
the mechanical parts must conform to the provisions of Standards
EN 12604 and EN 12605.
leaf length in compliance with the operator specifications.
sturdy and stiff structure of the leaves, suitable for automation.
regular and uniform movement of the leaves, without any friction
and dragging during their entire opening.
with the reversible motors to verify that the gate does not move
alone.
stiff hinges in good conditions.
presence of both opening and closing mechanical limit stops.
presence of an efficient earthing for electrical connection of
the operator.
Perform any necessary metalwork job before installing the
automated system
.
The condition of the gate structure directly affects the reliability
and safety of the automated system
.
3.3. INSTALLATION DIMENSIONS
Determine the fitting position of the operator with reference to
Fig.4.
Check with care if the distance between the open leaf and any
obstacles (walls, fences etc.) is higher than the operator dimen-
sions.
Mistral model
a
A
B
C
a
D
b
Z
c
L
E
c
300-324-
300 115V
90°
145
145
290
85
60
1110
45
110° 120
135
295
60
60
1110
45
400-424-
400 115V
90°
195
195
390
125
70
1290
45
110° 170
170
390
110
60
1290
45
a
operator useful travel
b
max. dimension
c
min. dimension
3.3.1. g
eneRal
Rules
to
deteRmine
the
installation
dimensions
to obtain
90°
leaf openings
: A+B=C
to obtain leaf openings
exceeding 90° : A+B<C
Smaller A and B dimensions determine higher peripheral speed
of the leaf.
Limit the difference between A and B dimension within 4 cm
:
•
•
•
•
•
•
•
•
•
•
•
•