background image

COMPAS 24 - COMPAS 24C

ENGLISH

Guide for the installer

Page

on the graph on the measured value, this line to cross the whole 

graph.

you will obtain the maximum permissible angular opening accor-

ding to dimension “

A

” of the graph.

select the opening range you require 

select dimension “

B

” so that it intersects the horizontal line (di-

mension “

A

”) inside the required opening range.

  If dimension “A” permits opening values greater than the ope-

ning value selected, the value of dimension “B” can change 

up to the maximum permissible opening value. 

  Make sure that the minimum dimension of 450mm in Fig. 5 is 

observed.

  When the operator has been installed, check if dimension “X” 

in Fig. 5 is minimum 500 mm. If dimension “X” is less than 

500 mm, run an impact test on the point indicated in Fig. 5, 

as described in UNI EN12445 standard, and make sure that 

the measured values conform to the specifications of UNI 

EN 12453 standard.

  If the thrust values are not within the values specified in UNI 

EN12453 standard, the zone indicated in figure 5 MUST be 

protected with a protective device conforming to the UNI 

EN12978 standard.

  The operator was studied and made to be secured vertically 

(Fig. 6). The operator cannot be installed in other positions.

4.3. INSTALLING THE OPERATOR

When you have established dimensions “

A

” and “

B

”, you can install 

the operator as follows:

Loosen by about 1/2 turn the four securing screws of the upper 

housing (Fig. 7 ref. 

a

) and withdraw the housing. Set the operator 

for manual operation, see paragraph 6.

Establish the height of the operator, bearing in mind that:

the  securing  bracket  of  the  curved  arm  must  be  in  a  zone 

where it can be secured to the gate leaf (Fig. 8)

the minimum off ground height of the operator must permit 

securing the curved arm and positioning the lower housing (at 

least 85 mm, see fig. 8).

the lower edge of the rear bracket must be aligned with res-

pect to the upper edge of the front bracket (Fig. 9).

Secure the rear bracket in the position you had established, using 

four M8 screws. As you secure the bracket, respect the lay-out in 

Fig. 10 and check, using a level,  if the bracket is horizontal.

 

To improve water tightness, the external housing covers the 

securing  bracket  -  this  prevents  the  bracket  from  being 

directly welded on the pilaster.

 

The rear bracket must be secured on an as smooth as possible 

surface. For masonry pilasters, a counter-plate for walling is 

available as an accessory. 

Position the operator on the bracket you have just secured, using 

two M8x100 screws and the relevant nuts - supplied (Fig. 11).

Set the operator for manual operation, see paragraph 6.

Install the straight arm (Fig. 12) with the supplied screw.

Assemble the rest of the arm as illustrated in Fig. 13.

  For correct operation, tighten the two securing screws (Fig. 

13 ref. 

a

) and then loosen them by about 1/2 turn to enable 

rotation without any friction on the arms.

Align the arms you have just assembled, pushing in the central 

zone until they stop, see Fig. 14 ref. 

a

.

  There are two stops on the curved arm to facilitate the ali-

gning operation.

Rest the front bracket on the leaf, Fig. 14 ref. 

b

.

Move back the front bracket by about 20 mm and mark the 

securing holes, Fig. 14 ref. 

c

.

Secure  the  bracket  in  the  established  position  using  two  M8 

screws.

  We advise you to secure the bracket with the screws, and 

not weld it to the leaf, in order not to rule out future adjust-

ments.

Move the bracket by hand and - with the leaf in closing position 

- make sure that the two arms do not impact each other, as 

shown in Fig. 14 ref. 

b

Take the operator back to the work position - see paragraph 

6.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

4.4. WIRING THE OPERATOR

When  you  have  finished  securing  the  operator,  you  can  wire  it. 

There are three holes in the lower part of the operator. They should 

be used for positioning the cable grippers, for routing the power 

cables, for connecting accessories and, if necessary, for connecting 

the second motor.

Install  all  the  three  supplied  cable  grippers  with  the  securing 

nuts (Fig. 15). 

  Always use the largest cable gripper (Fig. 15 ref. 

a

)

  If the other two cable grippers are not used, they must be 

closed, using the supplied plugs (Fig. 15 ref. 

b

). Fit the plastic 

plug in the cable routing hole and close the cable gripper 

until it is tight.

Connect the power cable, as shown in Fig. 16. The earthing wire 

must also be connected. Make sure that the power cable wires 

are correctly fitted in the ‘comb’ which restrains them Fig. 16.

  If the protective fuse has to be replaced, use a fuse with the 

following characteristics: 5x20 2A 450V.

Wire all the accessories and safety devices, observing the re-

levant instructions.

4.5. POSITIONING THE MECHANICAL STOPS

The COMPAS operator is supplied standard with opening and clo-

sing mechanical stops. This is to facilitate the installation operations 

because there is no need to construct the mechanical stop ele-

ments. The mechanical stops should be fitted in the lower part of 

the operator, coupled to a toothed sector. Installation procedure 

for the stops:

o

pening

 

mechAnicAl

 

stop

Set the operator for manual operation, see paragraph 6.

Manually move the leaf to its opening position.

Take the mechanical stop as close as possible to the straight 

arm and fasten the two securing screws.

  Make sure that the toothed sector is coupled correctly.

c

losing

 

mechAnicAl

 

stop

  Use  the  closing  mechanical  stop  only  in  the  absence  of  a 

mechanical stop on the closing leaf.

  The closing mechanical stop does not guarantee locking the 

leaf in case of burglary.

Set the operator for manual operation, see paragraph 6.

Manually move the leaf to its closed position.

Take the mechanical stop as close as possible to the straight 

arm and fasten the two securing screws.

  Make sure that the toothed sector is coupled correctly.

5. AUTOMATED SYSTEM TEST

When you have made all the necessary electrical connections, 

power up the system and program the control unit according to 

your requirements.

Run the test for the automation and for all the connected acces-

sories, taking great care when checking the safety devices.

Re-locate the upper covering housing, tighten the securing screws 

and position the four covering plugs fig. 18 ref. 

a

.

Position the lower housing as shown in fig. 18 ref. 

b

.

Hand the “User’s Guide” booklet to the customer and describe 

its correct operation and use.

  Point  out,  to  the  end  user,  any  residual  risks  present  in  the 

installation.

6. MANUAL MODE OPERATION

If the operator has to be manually activated due to a power cut 

or to an operator fault, proceed as follows:

Cut power to the system with the differential switch.

Lift the protective plug from the lock, fig. 19 ref. 

a

.

Fit the key and turn it anti-clockwise until it stops, fig. 19 ref. 

b

.

Turn the release knob clockwise until it stops, fig.19 ref. 

c

.

Move the leaf by hand.

p

rocedure

 

for

 

restoring

 

normAl

 

operAtion

:

Make sure that the system is not powered.

Position the leaf to its closing position.

Turn the release knob anti-clockwise until it stops, then turn the 

key clockwise until it stops and remove  it.

Check if the release device has been correctly engaged, by 

trying to move the leaf by hand. The leaf must be locked and 

it must not be possible to move it by hand.

1.

2.

3.

1.

2.

3.

1.

2.

3.

1.

2.

3.

4.

5.

1.

2.

3.

4.

Summary of Contents for COMPAS 24

Page 1: ...COMPAS 24 COMPAS 24 C GUIda per l installatore Guide for the installer Guide pour l installateur Gu a para el instalador Leitfaden f r den Installateur Gids voor de installateur...

Page 2: ...4 5 6 7 8 9 10 11 12 13 14 15 in the Standards indicated at point 10 The safety devices EN 12978 standard protect any danger areas against mechanical movement Risks such as crushing dragging and shear...

Page 3: ...ede Anlage wird der Einsatz von mindestens einem Leuchtsignal empfohlen sowie eines Hinweisschildes das ber eine entsprechende Befestigung mit dem Aufbau des Tors verbunden wird Dar ber hinaus sind di...

Page 4: ...nts of the following EEC directives 2006 95 EC Low Voltage directive 2004 108 EC Electromagnetic Compatibility directive and also declares that it is prohibited to put into service the machinery until...

Page 5: ...ed power 120 W 40 W Max torque 250 N m Nominal torque 165 N m Max angular speed 13 sec Max leaf a b 2 5 m Max leaf weight b See graph fig 2 Use frequency at 20 C 80 cycles day Consecutive cycles at 20...

Page 6: ...hown in Fig 14 ref b Take the operator back to the work position see paragraph 6 1 2 3 4 5 6 7 8 9 10 11 12 13 4 4 WIRING THE OPERATOR When you have finished securing the operator you can wire it Ther...

Page 7: ...ATIONS Applications other than those in this manual are EXPRESSLY PROHI BITED 8 MAINTENANCE To ensure correct long term operation and a constant level of sa fety we advise you to generally control the...

Page 8: ...COMPAS 24 COMPAS 24C Immagini Images Images Im genes Bilder Afbeeldingen Pag Fig 01 Fig 02 Fig 03 Fig 04 Fig 06 Fig 07 Fig 05...

Page 9: ...COMPAS 24 COMPAS 24C Immagini Images Images Im genes Bilder Afbeeldingen Pag Fig 08 Fig 09 Fig 10 Fig 11 Fig 12 Fig 13 Fig 14 Fig 15...

Page 10: ...COMPAS 24 COMPAS 24C Immagini Images Images Im genes Bilder Afbeeldingen Pag Fig 16 Fig 17 Fig 18 Fig 19...

Page 11: ...hat pre vent the gate from closing when there is an obstacle in the area they protect The system ensures mechanical locking when the motor is not ope rating and therefore for gates of less than 2m in...

Page 12: ...ng 1 Velligheldsvoorziening 1 Dispositivo di sicurezza 2 Safety device 2 dispositif de s curit 2 Dispositivo de seguridad 2 Scherhelt svorrichtung 1 Velligheldsvoorziening 2 Coppia di fotocellule 1 Pa...

Page 13: ...chnicien T cnico Techniker Technicus Cliente Customer Client Cliente Kunde Klant 4 Tecnico Technicia Technicien T cnico Techniker Technicus Cliente Customer Client Cliente Kunde Klant 5 Tecnico Techni...

Page 14: ...el derecho dejando inmutadas las caracter sticas esenciales de los aparatos de aportar en cualquier momento y sin comprometerse a poner al d a la presente publicaci n todas las modificaciones que cons...

Reviews: