Sec-3.11
Monitored Edges, Hardwired
Actuating the operator by using constant contact on the CLOSE button will override non-functioning
external reversing devices, including sensing edges.
WARNING
!
AVERTISSEMENT
!
L’activation de l’operateur en util isant un contact constant sur le bouton FERMER annulera les dispositifs
d’inversions externes, y compris les systèmes de détection des bords.
1/2 Door Height
+ 12in.
COIL
CORD
Monitored
Safety Edge
Red
MillerEdge®
Interface Module
Install
Black
White
Red
OPERATOR TERMINAL STRIP
Control Wire
Terminals
ODC
STB
ODC
STB
Junction
Box
1. Mount junction box to wall one half the door height plus 12 inches from floor.
2. Install hard-wiring from operator and coil cord to junction box and secure with conduit clamps.
3. Connect hard-wiring from operator to coil cord with wire nuts and install junction box cover plate.
These are not polarity sensitive.
4. Install wires to ODC STB terminals in operator.
5. Attach coil cord to Monitored Edge Interface Module in junction box as shown and secure with conduit
clamps.
6. Install wires from monitored edge to Interface Module as shown below.
7. Install cover plate.
Right-hand installation shown, Left-hand installation mirrored
MillerEdge® “DC” Series & ASO Monitored Sensing Edge
Installation with Interface Module.
NOTE:
DO NOT use take up reels with Monitored Edge systems
Section 3: Wiring
NOTE:
Installer must enable ODC STB in CALIBRATION MODE (see programming section)