Temporarily Defaulting the IP Address
The Controller can have its IP address temporarily set to
192.168.111.222
by using the following procedure.
This resets the IP address for as long as power is applied but will
not
save the change permanently. Once the
link is removed and power is cycled to the unit, the previously configured IP address is used again. This
means that if the currently configured IP address is unknown, you are able to connect to the web interface to
view and/or change it.
1. Remove power from the Controller by disconnecting the 12V DC
input.
2. Connect a wire link between
NA
of the module network and
SA
of
the reader network, and between
NB
of the module network and
SB
of the reader network.
3. Connect
Input 2
to ground.
4. Power up the Controller.
5. When the Controller starts up it will use the following settings:
IP address : 192.168.111.222
Gateway : 192.168.111.254
Net Mask : 255.255.255.0
DHCP : disabled
6. Connect to the web interface by typing 192.168.111.222 into the
address bar of your web browser, and view or change the IP
address as required.