SY-SIX-CTRL-DIN-1D | Synergis IX DIN Rail Single Door Controller | Installation Manual
Last Updated August 2018
27
Resistor Value Options
When using the EOL resistor configuration, the EOL resistor option must be configured based on the site
requirements. Note these resistor options are supported on the Controller but not all resistor options are
supported on all Synergis field modules.
Value 1
Value 2
Monitored Status
1k
1k
Open, Closed, Tamper, Short
1k
No Resistor
Open, Closed
<5K7
No Resistor
Open, Closed
No Resistor
No Resistor
Open, Closed
2k2
6k8
Open, Closed, Tamper, Short
10k
10k
Open, Closed, Tamper, Short
2k2
2k2
Open, Closed, Tamper, Short
4k7
2k2
Open, Closed, Tamper, Short
4k7
4k7
Open, Closed, Tamper, Short
5k6
5k6
Open, Closed, Tamper, Short