SY-SIX-CTRL-DIN-1D | Synergis IX DIN Rail Single Door Controller | Installation Manual
Last Updated August 2018
14
In addition to the dynamic battery test procedure, the Power Supply performs a battery presence test every 60
seconds, which determines whether the presence of a backup battery is detected. Similarly, a battery
condition alarm will be generated and the battery trouble zone associated with the address assigned to the
Controller will also be activated.
In order to comply with
EN 50131-1
only one battery can be connected and monitored per system. If
more capacity is required a single, larger battery
must
be used.
Ethernet 10/100 Network Interface
The communication between the Synergis System and the Controller uses a 10/100 Ethernet network
operating the TCP/IP protocol suite. The IP address of the Controller can be configured using an LCD Keypad
terminal or via the built in web interface. The default IP address is set to a static IP address of 192.168.1.2
with a subnet mask of 255.255.255.0. These IP address settings are commonly used for internal networks.
Installing the Controller on an active network requires knowledge of the configuration and structure for the
network. Always consult the network or system administrator and ask them to provide you with a fixed IP
address that can be assigned to the Controller
When installing an Ethernet connection the Controller should be interfaced using a standard segment (<100m
in length) and should be connected to a suitable Ethernet hub or switch.
Ethernet 10/100 Switch hub Connection:
N+ N- NA NB
RS485 NETWORK
12VDC IN/OUT
ETHERNET
RS485 NETWORK
SB SA S- S+ Z2 V- Z1 NC C NO
12VDC OUT
ZONE 2
ZONE 1
RELAY 1
Controller
N+ N- NA NB
RS485 NETWORK
12VDC IN/OUT
ETHERNET
RS485 NETWORK
SB SA S- S+ Z2 V- Z1 NC C NO
12VDC OUT
ZONE 2
ZONE 1
RELAY 1
Controller
Temporary direct connections can be used for onsite programming by connecting directly to the computer
Ethernet port.
Ethernet 10/100 Direct Connection:
N+ N- NA NB
RS485 NETWORK
12VDC IN/OUT
ETHERNET
RS485 NETWORK
SB SA S- S+ Z2 V- Z1 NC C NO
12VDC OUT
ZONE 2
ZONE 1
RELAY 1
Controller