UPSMAN Started
UPS service is started into the CS121. This event is always true, if the
CS121 is running and therefore ideal for permanent recurrent jobs
suitable like the forwarding of emails always after restart of the UPS or
to produce log file entries steady.
UPS Connection Lost
UPS RS232 communication lost, CS121 tries to restore the connection.
UPS Connection Restored
UPS RS232 communication restored
Battery Low
The autonomy of the battery has reached the defined threshold
"Battery Low". The UPS shutdown is pending.
ADVICE: The RCCMD
shutdowns will be set into this event too, but without delay!
(Emergency shutdown, if batteries are to weak)
Output Breaker Open
Output breaker open. UPS is isolated from load. No supply of the
consumers.
Output Breaker Closed
Output breaker closed. Load will be supplied.
Maintenance Breaker Closed
Maintenance breaker closed (active). Load will be supplied through the
grid directly.
Maintenance Breaker Open
Maintenance breaker open (inactive). Load will be supplied via the UPS.
Regular UPS protected operation.
Inverter Breaker Open
Inverter breaker open. Load is
not
UPS protected!
Inverter Breaker Closed
Inverter breaker closed. Load will be supplied via the inverter. Normal
condition.
Battery Breaker Open
Battery breaker open. No battery buffering active!
Battery Breaker Closed
Battery breaker closed. OK, normal condition.
UPS Off
UPS off
UPS On
UPS on
New Alarm
New alarm, buzzer was activated.
Buzzer Off
Buzzer off
General Alarm
An alarm has occured. Alarm LED at the UPS is flashing.
General Alarm Off
No more alarm is active. Alarm LED at the UPS is off.
Overtemperature
Overtemperature of the UPS
Temperature Ok
Temperature of the UPS is back in normal range.
Output Bad
UPS output failure (e. g. voltage, frequency)
Output Okay
UPS output OK
Overload
UPS overload, reduce load otherwise the UPS shutdown is pending
No More Overload
No more overload
Bypass Bad
Bypass failure at input (e. g. voltage, frequency)