160
Figure 167:
CS121 Configuration for such a relay command
The target of the RCCMD command is the Windows computer with RCCMD and the
„pxout.bat“ with the IP address 192.168.200.41. If the event „UPS Major Alarm Added“ will
occur, this Job will execute the command „pxout.bat 192.168.222.43 public2 1 0“ to switch off
the socket number 1 at the Raritan with the IP address 192.168.222.43 immediately.
Tip:
You should stop RCCMD running in the background on this Windows computer, so you
will better see, whats going on. Stop the RCCMD service, than open a command line into the
RCCMD folder and start „rccmd.exe –debug“. Now the software will run in the foreground and
you can watch the communication.
4. The Raritan with firmware 1.4.1 is unfortunetaley buggy. Here the workaround:
The default community strings for the Raritan are identically set for „read“ and „write“ to
„public“, but this configuration is invalid! It must be different!
Solution: Stop the SNMP Agent at the Raritan, change the community for „write“ to any other
than „public“ and restart it!
Figure 168:
Raritan Device Settings