Problem 2:
Inform Pyramid DSP Series Communication with UPS Slotcard inside does not
start the UPS communication or if the external RS232 communication does not work.
Solution 2:
It is required to put the DIP switches onto the UPS mainboard into the position
“ON”, if you are using a CS121 SNMP slot card! Put the DIP switches into the position “OFF”, if
you are using an external CS121 via RS232 interface!
Figure 132:
Mainboard Inform Pyramid DSP
Problem 3:
CS121 reboots again and again after a few time into company´s network
environment.
Solution 3:
The n
etwork monitoring software “WhatsUp Gold” is started. We do not support
this software, stop the service, problem solved.
Problem 4:
Sending of RCCMD signals, the following error is logged into the CS121
AlarmLog: