47
4.2.17
This is the standard setting for the RASManager, the CS121 with the built-in modem. Most of
the CS121 products can also have the RASManager feature enabled by purchasing PPP
License Key and by connecting a supported modem. The RASManager, RASControl Software,
the UNMS II Software with the TeleService Module come with an extra user manual for
describing this feature.
Figure 45:
HTTP - RAS Manager Settings
4.2.18
Scheduled Actions
Figure 46:
HTTP
– Scheduled Actions
In the “Scheduled Actions” menu you can schedule the following actions:
Self test:
A self test is a short hardware test, which switches the device to a short discharging.
Battery test:
A battery test is a short battery test, which switches the battery to a short
discharging.
Custom test:
A custom test checks, if the batteries are able to hold the downtime at least.
Full test:
A full test is used to calibrate the UPS and will discharge the batteries till the „battery
low“ limit. This test should be done once a year at most, because to avoid a damage of the
batteries.
Online (inverter mode):
This is a func
tion to switch into “Normal Mode” (power supply of the
battery). This status is the normal UPS mode and it is actual not necessary to schedule any
kind of commands.
Offline (bypass mode):
This is a function to switch into “Bypass Mode”. Thereby the inverter
of the UPS is not in usage and the current would not be buffered, if a failure would occur. This
mode displays a failure of the UPS
, please call the UPS service to solve the problem.
Shutdown UPS:
This action causes the switch off of the UPS. This could be arranged, if a low
charging of the battery occurs, in case of a fire alarm or a power failure happens.