To turn your Windows computer into a timeserver, double-click on the clock in the lower right 
taskbar and open the following example. After some seconds the 

tab “Internet Time” appears. 

Click on “Internet Time” and check if the timeserver you have chosen here works correctly. 

After  having  configured  and  started  your  Microsoft  Windows  Timeserver  you  have  to  reboot 
your  computer  and  check  the  Event  Logfile  of  Windows  to  ensure,  the  service  was  started 
correctly. In this case, you can configure your CS121 Timeserver using the IP-address of this 
Windows computer. 

 

Note: 

Please  check  if  your  computer  is  reachable  through  the  network.  You 
may  have  to  change  the  Windows  Firewall  settings  to  allow 
inbound/Outbound UDP port 123. 

 
At Windows Server 2003 and 2008 it is required to enable the NTP server into the registry 
manually. Open the following folder: 
 
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\W32Time\TimeProviders\Ntp
Server 
Click with the right mouse button onto “Enabled” and change the “Value Data” from 0 to 1. 
After this change stop/start the W32 Time service. 
 

Summary of Contents for CS121BL

Page 1: ...Version 2016 07 05 UPS WEB SNMP MANAGER CS121 Series Additional Components CS121 Extensions User Manual English ...

Page 2: ......

Page 3: ...ing of the Generex products Generex allows its channel partners to transfer information contained in this document to third persons either staff within their own Company or their own customers either electronically or mechanically or by photocopies or similar means Generex states that the content must not be altered or adapted in any way without written permission from Generex It is agreed that al...

Page 4: ...ses Handbuch ist auch in Deutsch verfügbar Eine aktuelle Kopie erhalten Sie unter Download bei www generex de This manual is also available in German To obtain an actual copy please see the download page of www generex de ...

Page 5: ... 3 Using HTTP Webbrowser 17 3 3 4 Configuration using Telnet MS HyperTerminal 18 3 3 4 1 Main Menu IP Settings 19 3 3 4 2 UPS Settings 20 3 3 4 3 Saving Configuration 21 3 4 CS121 Restart and Boot Procedure 21 4 Configuration of the CS121 22 4 1 CS121 Menu System Network Status 22 4 2 CS121 Menu Configuration 23 4 2 1 Saving Data 23 4 2 2 UPS Model System 24 4 2 3 Network Security 25 4 2 4 The CS1...

Page 6: ...uter via FTP 66 6 Additional Software 69 6 1 RCCMD 69 6 1 1 RCCMD with SSL for Windows 69 6 1 2 RCCMD with own SSL certificates 71 6 1 3 RCCMD client as relay station 71 6 1 4 License regulations 72 6 2 jChart 72 6 3 gChart 74 6 4 UPS monitor UPSMON 76 7 CS121 Enhancements Field of applications 77 7 1 SiteSwitch4 SS4 and SiteSwitch4AUX SS4AUX 77 7 1 1 SS4 Feature overview 78 7 1 2 SS4 Contents 78 ...

Page 7: ...ameter 113 E 6 UPSMAN Status Bytes Standard Device Status Bits 136 E 7 Bus termination 137 E 8 Configuration 138 E 9 TCP IP UDP Ports 138 E 10 MODBUS Cables 139 F Available Variables of the CS121 139 G Pin layout of Input sockets of the SENSORMANAGER unit 140 H Events Alarms of the CS121 Description of the alarms 141 I Description of the alarms for single phase UPS 145 J Configuration of Microsoft...

Page 8: ...hots and described details have to be interpreted correspondingly 1 2 CS121 Device Type Overview The following CS121 device types are available as external adapter slot card adapter Devices Function Description CS121L SNMP Adapter external adapter with AC DC converter power supply CS121SC SNMP Adapter Slot card adapter for chinese UPS CS121F SNMP Adapter Slot card adapter for FUJI UPS Japan CS121R...

Page 9: ...e battery tests battery calibration and UPS shutdown restore have a wide range of network management features for alarming users and managing other SNMP devices and general overall Computer and Power resource management via RCCMD 4MB include MODBUS over IP and an optional MODEM interface offer a COM2 for connecting environmental sensors or for connecting other products and software to manage the U...

Page 10: ...dget Slot Chinese 3 x 1 For USA CA UL Supplied by NEC Class 2 Power supply only 2 For the configuration via serial interface with terminal software and for the connection to additional devices e g sensors 3 Configuration with network cable only 1 4 Functional Overview of the CS121 The CS121 is working with an integrated Simple Network Management Protocol SNMP software agent This agent exchanges da...

Page 11: ...9 Functional Overview of the CS121 Professional Functional Overview of the CS121 Budget Functional Overview of the CS121 MINI ...

Page 12: ...NMP management station The event settings configuration menu also allows for SNMP trap testing Remote Control With this function it is possible to switch the UPS to Bypass depending on the model or start battery tests This remote command is executed either via the Network Management Station or the UPS Management Software or any web browser Telnet Every Adapter can be reconfigured via the network u...

Page 13: ...our network or from Internet timeservers This log file can be accessed by web browser UPSMON JAVAMON or via FTP The size of the log file is 250 lines older entries will be overwritten automatically Network Settings The CS121 models are adjustable to the network environment An auto sensing function 10Mbit or 100Mbit can be selected Email Client The CS121 adapters incorporate a built in SMTP email c...

Page 14: ...B from our website http www generex de e download cs12x download_p html Copy the MIB file to the appropriate MIB directory of your SNMP station and compile this file In most cases your SNMP already has implemented this MIB and a compilation is only necessary if you want to read extra information than just UPS e g for SENSORMANAGER etc UPSTCP The most common way to communicate with the CS121 is ove...

Page 15: ...e at your CS121 HW131 during the reboot huge broadcast traffic into your network is present recieve buffer overflow The green LED is signalizing at the reboot that the traffic buffer is full Advice You should filter broadcasts via your switch because it comes to performance losing of the CS121 HW131 unnecessary red AND green during reboot Normal condition green flashing displays the poll interval ...

Page 16: ...that the polarity is set correctly The adapter might be damaged if the wrong polarity is used The power supply voltage should be at least 9V 12 V is recommended For the CS121SC models C and the slot card there are no power supply units These units will receive power directly from the UPS device The SNMP adapter C and slot card both incorporate a variable 9 36V input 2 Quickstart This quickstart de...

Page 17: ... After the CS121 is connected to the UPS and to the workstation via serial port or via LAN please verify the connectivity before you start to configure the CS121 The setup system can be checked before and after a configuration using the following 3 steps UPS Status Displays LEDs During the boot procedure the red LED is on whereas the green LED is off please take a look into chapter 1 6 for the com...

Page 18: ...o be able to find the IP address on your DHCP server You can also use the GENEREX Netfinder tool http www generex de generex download software install NetFinder zip This tool searches all CS121 BACS devices into your network environment We recommend to use static IP addresses because the CS121 is used for multi server shutdowns via RCCMD too and it might be that the DHCP server got a breakdown For...

Page 19: ...t destroy the configuration file upsman cfg Please note that the reboot process could last up to 3 minutes For the configuration using the webbrowser please observe the following We recommend the use of Microsoft Internet Explorer 6 x or higher or Mozilla 1 3x Please note that Java scripting has to be activated Using Internet Explorer the corresponding settings have to be made under Internet optio...

Page 20: ... Security Settings Apply your settings with the button at the right side Change to menu Save Configuration and click Save Configuration 3 3 4 Configuration using Telnet MS HyperTerminal Use of Telnet enter the command telnet IP Address whereas IP Address is in the configuration mode set to 10 10 10 10 Please note that since CS121 firmware version 4 x the basic settings IP address network settings ...

Page 21: ...nter the number of the option type space and enter the name Press enter Your new value displays next to the field heading on the top of the screen If you want to return to the main menu press 0 zero and enter For example To assign the IP address of the SNMP adapter the gateway and the subnet mask type at the prompt 1 space the IP address of the SNMP adapter enter Enter Command 1 192 10 200 0 Enter...

Page 22: ...PS models with the cable types O C 1 10 Those contact cables are UPS or alarm system specific and should be provided by the corresponding manufacturer Our Cable documentation shows examples of those cables if they are individually made cables Please choose the corresponding serial UPS model or cable model communication parameters Parameters like baud rate etc are present for the corresponding UPS ...

Page 23: ...configuration via web browser offers a much more convenient way to configure the CS121 If you have any possibility we recommend you to use this way 3 4 CS121 Restart and Boot Procedure After you have finished the basic IP and network settings you should set DIP switch 1 in position ON and restart the adapter with your configurations You can perform a CS121 restart by unplugging the power supply of...

Page 24: ...e will be no effect on the UPS output 4 1 CS121 Menu System Network Status The Menu System Network Status shows basic information about general configuration settings Figure 12 HTTP System Network Status The menu UPS Status gives information about the actual UPS data above all the state of charge and battery load Figure 13 HTTP UPS Status The menu UPS functions allows you to perform USV test and c...

Page 25: ...g provided while the gray unlit light bulb indicates the status of being switched off in which case the connected device is not being provided with power The buttons Switch Off and Switch On are password protected This is the same password that has been set in the CS121 configuration The ports 3 4 are configured as input sensors here the OFF symbol shows an open contact and alarm would show a clos...

Page 26: ...on system contact you can describe the UPS and CS121 Note Do not change the default UPS Parameters for Baud Rate and Hold time unless you have special instructions from the UPS maker Please note the field System Shutdown Time This value determines how many minutes before a complete battery unload the event System shutdown from the event menu will be executed Attention This EVENT is the final task ...

Page 27: ...fines the amount of bytes which will be send as reference data into a TCP segment The default is 1460 If you got problems with a VPN connection change the TCP MSS value to 1100 The TCP MSS value is valid for HTTP only Enable RCCMD Listener Among others here you can allow the CS121 to act as an RCCMD listener client This makes it possible for another UPSMAN Manager CS121 SITEMANAGER or other RCCMD ...

Page 28: ...pecific users With this password which is valid for the TCP IP connection to the UPSMON too the user may switch on off the UPS start battery tests switch SITESWITCH 4 outputs but can not change any other setting on the CS121 configuration Exception If the administrator password default identic was not changed The UPSMON is a Windows client which is able to connect via network to the CS121 The UPSM...

Page 29: ... the IP address of a gateway and 2 more addresses which are reachable steady If you enter only 1 or 2 addresses the amount of the checkable addresses is reduced and the possibility to initiate a reboot will increase unnecessarily because less addresses are at hand for the check of the network quality If the CS121 will reboot itself often at enabled ICMP check an analysis of the network is required...

Page 30: ... IP address has to be entered Please also note that the sender account name e g ups mailserver de should not be a random name since some mail servers do not allow this We recommend to use an existing account e g ups mailserver de Most servers require matching account names and mail server names E g someone somewhere com would be correct whereas just someone would not be sufficient If the server na...

Page 31: ...1 adapter supports only this function needs to be supported e g freemail de This changes the protocol from SMTP to ESMTP and a password is required The length of the password should be a minimum 3 and a maximum of 63 characters Send a test mail to validate your settings after you have applied the mail settings A short message on the menu indicates whether the test mail could be sent or not The usa...

Page 32: ... II screen with timestamp of the latest measuring values update 4 2 10 Email Trap Configuration The feature will be enabled through an entry into the Email Trap configuration If you delete the entries the feature will be disabled You can use the Import Settings feature to import your email settings from the previous page easily Advice The Email Trap configuration is in accordance with the common e...

Page 33: ...an define an intervall for the Heartbeat in case of an alarm Figure 25 UNMS Email Trap Settings You can trigger an Email Trap via Test button The CS121 AlarmLog will log the sending and the UNMS II with TeleService should display new measuring values within 2 to 3 minutes The default selection of the Email Trap events shows which events are critical and should be sent If you want to send further e...

Page 34: ...e CS121 firmware version 4 28 x provides the option to set the system time manually Please note that after the next reboot the synchronization will be lost Attention The NEWAVE UPS got a special feature Time synchronization via MODBUS command 99 With this signal the internal clock of the CS121 will be reset to 01 00 every night because of the optimization of a correct time To avoid that the CS121 ...

Page 35: ...ng the following languages English German Chinese French Spanish Polish Portugese Figure 27 Language Configuration To be able to use this feature it might be required to configure the following into your web browser example Internet Explorer 8 Open the Tools Internetoptions menu into the IE8 Click the Language button Add the languages you use to read websites listing in order of preference ...

Page 36: ...ll events do perform a log file event to send an email or to perform an RCCMD Command e g shutdown signals to several RCCMD clients For a short introduction into the handling of events and actions see also the section Quickstart In this menu the relationships between system events such as alarms and the actions to be taken those events are defined To configure your events and actions open the menu...

Page 37: ...ger the shutdown signal at the client side You should perform a shutdown test not until you have switched off the shutdown procedure at the client RCCMD Configuration Button Configure shutdown All jobs are not saved until you executed the Save Exit and Reboot function not until the device is restarted and running in normal mode DIP Switch 1 is ON The number of jobs per event ist limited CS121 Seri...

Page 38: ...s for external sensors are configurable through the variable SM_analogue 1 8 The proper threshold events for temperature low of 10 C and temperature high of 40 C were defined into the menu COM2 AUX for the SM_T_COM Figure 33 HTTP COM2 Threshold events SM_T_COM 4 2 13 2 Logfile Entries For a numerous of events logfile entries are already pre configured as default To configure a new logfile entry ty...

Page 39: ...ariables are only getting filled if the event actually occurs not by testing the action so a simulation is not possible you have to create a real alarm to see the full message For example please see the figure above There the variables MODEL and AUTONOMTIME will be substituted with their current values when the action will be released Please notice the syntax that each variable name must be starte...

Page 40: ...one website of your country for the accordant server name Please note that you enable receiving emails on your cell phone This is done by sending a SMS with the message OPEN to the number 3400 Only the subject or the text field of the email will be transferred as a SMS 160 characters from the subject and text field Important If you want to stop receiving emails please send a SMS to the number 3400...

Page 41: ...44 x provides SNMP V3 SNMP V3 requires the definition of at least a SNMP V3 user on both sides CS121 SNMP Management tool The following SNMP V3 security level are at present o No auth no priv No authentication no privacy but an SNMP V3 user o Auth no priv Authentication SNMP V3 user SNMP V3 password no privacy o Auth priv Authentication SNMP V3 user SNMP V3 password SNMP privacy password Figure 38...

Page 42: ...rk in configuration mode If you use SNMP Test trap you will receive SNMP Traps of a Powerfail and Power restored scenario the simulation of a power outage of some seconds Note If you use SNMP polling to retrieve data from the CS121 you should disable the MODBUS port to avoid interrupts and performance slow down The CS121 can be monitored via web browser UPSView MODBUS PROFIBUS LONBUS Email and SNM...

Page 43: ...ress The MAC address of every CS121 adapter starts with 00 03 05 02 XX XX whereas this address can be found in the Telnet menu menu IP address gateway address MIB system group Your SNMP adapter is now installed and fully functional Please read the following for configuration and functionality descriptions of the adapter The MIB is to be loaded onto each SNMP Management Station that is monitoring a...

Page 44: ...oftware can be polled via a MIB browser and data can be read Please choose the corresponding MIB variable or string of MIB variable and set the destination address TCP IP of the adapter The adapter will answer with the UPS data Alternatively the Windows UPSMON JAVAMON or the UPS SNMP WATCH of the DataWatch Pro Software can be used The UPS data will then be displayed graphically and internal UPS in...

Page 45: ...er necessary 2 serial interfaces on your UPS which are working parallel are utilized now Reminder If you have enabled this function you can no longer configure the adapter via the serial cable you must change the settings via HTTP As communication cable between CS121 and your application you have to use the original CS121 configuration cable not included Note Please note that it is required to def...

Page 46: ... simply plugged into the CS121 for setup and the only mandatory change on the adapter to enable this functioning is to set the COM2 Settings to either TEMPMAN or SENSORMAN The configuration is easily achieved via the HTML page of the CS121 web server Please note the drop down menu and entry fields on the page see screenshot above For in depth SENSORMANAGER settings see following up chapter Figure ...

Page 47: ...r the AUX ports are switched to output or input The AUX port can only read signals if the port is switched to input If switched to output the AUX port can send signals to an optocoupler for example Refer to the circuit diagrams in the appendix After a reboot the state of the switches remains in the status previous to the reboot The following describes the configuration of the AUX ports using the H...

Page 48: ...lecting unit which allows the individual measurement and monitoring of 8 analog measurement devices 0 10V and 4 digital alarm inputs or 4 outputs open collectors SENSORMANAGER has its own chapter in the manual wherein the features and field of applications etc pp are described as well as in depth the various specific configurations In generally the SENSORMANAGER unit is connected with its COM 1 po...

Page 49: ...hort discharging Custom test A custom test checks if the batteries are able to hold the downtime at least Full test A full test is used to calibrate the UPS and will discharge the batteries till the battery low limit This test should be done once a year at most because to avoid a damage of the batteries Online inverter mode This is a function to switch into Normal Mode power supply of the battery ...

Page 50: ...ceiver e g another CS121 RCCMD client or SITEMANAGER SITESWITCH4 to execute a command or program e g to start a program at a remote work station Native UPS Command for very experienced users only This is a function to execute UPS own commands Assumption The user knows the Command IDs and the proper parameter These commands require additional parameter If you want to use these kind of commands just...

Page 51: ...tatus signal LOW Since the AUX Status can only be set to High or Low and given that the CS121 in itself cannot distinguish the device an alarm email will be sent by the CS121 to the designated ADMIN at startup per default with the startup status of each connected alarm In this case it is up to the administrator to determine if the emails indicate an actual alarm or not 01 17 2007 16 34 48 MAIL sub...

Page 52: ...1 Event 70 successfully sent This Email shows that no SENSORMANAGER is connected although the CS121 is configured as having a connection to a Sensormanager This informs the ADMIN that the CS121 is incorrectly configured In this case the user should correct the settings The UPS data will be logged with timestamp into the CS121 DataLog Figure 47 HTTP CS121 DataLog The data of the connected devices e...

Page 53: ...2 the logging of a SM_T_H_COM is displayed sensor 1 for the temperature sensor 2 for the humidity At unify UPS their events will be imported out of the UPS directly and are displayed into the CS121 menu LogFiles UPS Events Figure 49 HTTP CS121 UPS Events ...

Page 54: ...Alarms Powerfail This event occurs if the UPS will lose the power supply This event might be the optimal fitting for the definition of RCCMD shutdowns System Shutdown This event will be triggered if the defined system shutdown time was reached This event should be used for operations only which will force a shutdown immediately Note This event is the last event that the CS121 can execute prior of ...

Page 55: ...er battery low events CNT_SD Counter shutdowns CNT_SA Counter shutdowns active CNT_TF Counter test failures INPHASES Amount input phases OUTPHASES Amount output phases Example of the configuration of a RCCMD Trap job for the event Power restored Figure 50 HTTP Job Editor RCCMD Trap Event Power restored You can add any kind of text measurement units It is required to add a blank ahead and behind th...

Page 56: ...trol box in the menu Network Security Settings The CS121 adapter uses the parameter based RCCMD Version 2 which can execute different actions on the same TCP channel RCCMD Version 1 clients can only execute one action shutdown file execution as default so any RCCMD signal which is transmitted to an RCCMD client V1 will cause a shutdown of this server RCCMD Version 3 is capable to handle also redun...

Page 57: ...t time settings so it is required to configure a timeserver Click the Timeserver configuration button and enter the address of at least one timeserver Figure 53 Timeserver Settings Click the Save Configuration button and the Save Exit Reboot button to confirm your settings ...

Page 58: ...CMD Client service start without trouble Therefore we use the nodes option and the newreq command CA pl newreq nodes Sign with your CA CA pl sign Now create an empty file named rccmd pem and copy the cert information of newcert pem rccmd certificate newkey pem private key and cacert pem CA into it Please note that the exact copying is required to use it without trouble Use your own RCCMD certifica...

Page 59: ...ed in will be ALWAYS executed The time specifications inside the timer box Every After seconds After seconds repeat After seconds on battery At seconds remaining time will be only executed if the alarm event is still present Note For security reasons we recommend to make the same RCCMD shutdown entries for the Event Battery low but in this Event without any delays to avoid that the server crashes ...

Page 60: ...y of x seconds Unregarded if the EVENT is still true or not after the delay the action will be started The timer settings in the blue framed scheduler box will be executed only if the EVENT is still true after the delays countdowns have run out E g if any action has been configured at do after 10 seconds than this action will NOT be started if after 9 seconds the EVENT is no longer true Only if 10...

Page 61: ...nds At seconds remaining time Action Job will be executed in case that the UPS runs on battery Powerfail and the remaining time read by the UPS or calculated by the internal CS121 routine has reached a certain remaining time Only useful if the Autonomytime of your UPS can be regarded as reliable REMAINING TIME is defined as Autonomytime in seconds of this UPS at the actual discharging level minus ...

Page 62: ...MD cancel shutdown The client which received the shutdown will be encouraged to reset it This command can be set individually into your CS121 UPSMAN or BACS WEBMANAGER Events Alarms configuration but makes sense only if the event which will send the command is true if the UPS is back in normal condition For this the events POWER RESTORED BATTERY LOW OFF UPSMAN STARTED and GENERAL ALARM OFF are sui...

Page 63: ... the RCCMD client and click the Cancel RCCMD Shutdown button Figure 65 HTTP Job Editor RCCMD WAKEUP 4 4 6 RCCMD Message With this job the user can combine and configure a text message with RCCMD event Text messages can be sent to RCCMD receivers This makes it possible to send text messages via RCCMD version 2 or higher to a Windows 2000 server or a UNIX computer using the NET SEND or the respectiv...

Page 64: ... RCCMD client see also section SNMP Target AUX port must be set to use as Output menu AUX see according section The send RCCMD Command must match the settings of the CS121 RCCMD listener client See the UPSMAN User Manual for setting up this job on a computer running UPS Management Software Example of use 2 CS121 adapter switches an output CS121 receives an external RCCMD signal to switch an output...

Page 65: ... 168 202 165 p 6002 ATTENTION The blank after the Execute is important Common syntax for the switching of AUX ports AUX 1 0 Port1 set to low AUX 1 1 Port1 set to high AUX 2 0 Port2 set to low AUX 2 1 Port2 set to high AUX 3 0 Port3 set to low AUX 3 1 Port3 set to high AUX 4 0 Port4 set to low AUX 4 1 Port4 set to high Confirm a digital alarm You can also use this syntax to e g confirm alarms for d...

Page 66: ... fire alarm or if a complete power down is wanted Attention This command will cut off the power supply only for UPS which support this function Figure 69 HTTP Job Editor Shutdown UPS Job The example above configures that 60 seconds after the event powerfail has occurred the UPS is initiating a shutdown and the UPS waits another 120 seconds after the event powerfail is gone power restored before th...

Page 67: ...cheduled Actions After you clicked the Add new action button you can define new actions for the CS121 You can select the following options for the execution of an action Once Daily Weekly Monthly Note Please check the time and timeserver settings A correct internal adapter clock is necessary for scheduled actions 4 4 11 CS121 for Transfer Switches The CS121 is used from time to time for automatic ...

Page 68: ...66 Figure 72 HTTP Status Page Socomec Transfer Switch Figure 73 HTTP Status Page Eaton Transfer Switch ...

Page 69: ... at www generex de download page Note Any interruption of a firmware upload may damage your adapter If this is the case you have to reformat the adapter with special software See section Firmware Recovery or contact your UPS software support for more information The boot procedure of the CS121 adapter performs several steps First the firmware is going to be uncompressed Starting firmware Control p...

Page 70: ...your computer and the CS121 if available use Hub recommended or a direct line Ethernet cross cable Instructions for recovery procedure In case the CS121 is not running has any defect or other problem please put dip switch 1 to OFF Dip 2 should be always OFF and follow the procedure below 1 Before starting the update unplug the adapter from the power supply slot cards have to be removed from the sl...

Page 71: ...69 Figure 76 CS121 FTP Access Figure 77 CS121 FTP Context Menu Figure 78 CS121 FTP Folders ...

Page 72: ...check if the parameter of the new data are present into the stored data If not you need to copy the missing parameter of the new data into the stored upsman cfg Now you can overwrite the upsman cfg into the flash folder via ftp Figure 80 CS121 FTP File Replacement Just reboot do not select Save Exit Reboot the CS121 via web browser ...

Page 73: ...naged UPS facility The main purpose is to transmit shutdown signal or messages to RCCMD clients in other networks or on other OS Figure 82 RCCMD Overview The RCCMD Software got his own user manual Please follow this link to get it http www generex de generex download manuals manual_RCCMD_Win_Unix_Mac_en pdf 6 1 1 RCCMD with SSL for Windows The Secure Sockets Layer SSL protocol is a cryptographic p...

Page 74: ... feature Figure 83 RCCMD SSL Settings The SSL network feature requires correct time settings so it is required to configure a timeserver Click the Timeserver configuration button and enter the address of at least one timeserver Figure 84 Timeserver Settings Click the Save Configuration button and the Save Exit Reboot button to confirm your settings ...

Page 75: ...tion and the newreq command CA pl newreq nodes Sign with your CA CA pl sign Now create an empty file named rccmd pem and copy the cert information of newcert pem rccmd certificate newkey pem private key and cacert pem CA into it Please note that the exact copying is required to use it without trouble Use your own RCCMD certificate Do the following steps at the RCCMD Client and every sender e g UPS...

Page 76: ...license for RCCMD to shutdown 1 computer For more computers to shutdown you have to order separate RCCMD client licenses If you want to shut down more than 50 clients in one company or organisation please contact your UPS dealer and order an enterprise license Then you will get one RCCMD license for all clients only 6 2 jChart jChart is a GENEREX Web 2 0 Control Chart for all web browsers which si...

Page 77: ...es into the chart only click the Unselect All Lines button and check the accordant variables Figure 88 jChart Display of the Loads To increase a desired area click the left mouse button into the area and drag an accordant rectangle from the upper left side to the lower right side ...

Page 78: ... web site Quickly and easily visualise all of the CS121 adapter logfiles using Generex s ActiveX graphical log controller GChart when using the Internet Explorer Discover UPS problems more easily and optimise system tuning more rapidly Navigate through the data with the mouse using functions like zoom and pan with continuous motion in real time and query interpolated data values by clicking in the...

Page 79: ...to follow the GChart logfile links In order to activate this function the following adjustments in the Internet Explorer Options are required Click via the menu Tools into the Internet Options Select the tab Security Click the Trusted Sites icon than the Sites button and add the desired IP address Figure 92 Internet Options of the internet explorer ...

Page 80: ...UPSMON UPS Monitor UPSMON is the graphical monitoring and command inferface application for UPSMAN and is available in standard and custom interfaces In order to display the UPSMAN provided data via the network customer friendly the modules UPSMON and JAVAMON are delivered for free The UPSMON is a client for all Microsoft platforms whereas the JAVAMON can be started on all operating systems that s...

Page 81: ...via UPSMAN and respective SNMP adapter gCHART dynamic visual log file graphic tool Remote controlling of all UPS systems via the network Graphic display of the UPS input data voltage power Read out and display of the UPSMAN event log files Programming of the UPSMAN scheduler Graphic screens containing all UPS information also under UNIX MAC JAVAMON 7 CS121 Enhancements Field of applications 7 1 Si...

Page 82: ... then use the configuration cable not included to connect the SS4 with your UPS Figure 96 Exchange COM Ports 1 2 for SS4 7 1 1 SS4 Feature overview 4 configurable powers sockets with a breaking capacity of 230V 8A Power socket status indicator via HTML UPSMON UNMS or SNMP Control via the internal CS121 or via remote CS121 or RCCMD compatible devices Remote control of the powers sockets via HTML Br...

Page 83: ...up and the 4 Power Socket Status LED one for each of the sockets should be unlit This means that none of the sockets are being provided with power thus cutting the connected devices from the power supply The CS121 establishes a user interface for the SS4 for which the user has the option of using either UPSMON Webbrowser UNMS or an SNMP Program All communications take place either through a modem ...

Page 84: ...e COM2 In the Webinterface COM2 AUX you have to change to the COM2 mode to SM_T_COM press apply and save exit and reboot to start the CS121 with your new settings The Configuration of thresholds and Events is made via the Event configuration windows and the SM_T_COM configuration page 7 2 1 SM_T_COM configuration Figure 99 CS121 SM_T_COM Settings Enter the desired values for the Threshold low and ...

Page 85: ...lick the Configure Threshold Events button into the CS121 Events Alarms menu Figure 101 CS121 Configuration Threshold Events of analogue Inputs In this example a below threshold of 13 was defined for SM_analogue 1 in this case for the temperature in C which will appear into the Event Configuration after you executed the Save Exit Reboot function ...

Page 86: ...g of 8 analog measurement devices 0 10V and 4 digital alarm inputs or 4 outputs open collectors Figure 103 Sensor Manager SensorMan The SENSORMANAGER is a system extension for the CS121 Professional BACS WEBMANAGER CS121 Mini und CS121_R_II Universal Remote Sensor Control Box for the monitoring of temperature humidity and many other types of sensors as well as for the the management of digital inp...

Page 87: ...ystem of the CS121 informs the administrator of problems and may automatically switch off computers and other devices Optional extensions SITESWITCH 4 or SITEMANGER The SENSORMANAGER is an extension to the CS121 Webmanager If you want to connect any other computing device please download the RS 232 protocol for the SENSOR MANAGER from our website and adjust your software to this communication type...

Page 88: ...SORMANAGER make sure your configuration matches your sensor type e g see example Figure 105 SENSORMANAGER II Settings Using the splitting plugs order number SPSMRJ it is possible to connect up to 8 sensors and 4 contacts to the SENSOR MANAGER A MOUNTING KIT sold separately is available for affixing the SENSORMANAGER to walls and railings The power supply for the SENSORMANAGER may also supply an ex...

Page 89: ...erex de wwwfiles dokus 1 cs121 german pdf cs121 pdf When the SENSOR MANAGER is running you will see the values in the AUX section of the CS121 Web browser Detection of the analog temperature values via variables TEMP1 TEMP2 TEMP3 TEMP4 TEMP5 TEMP6 TEMP7 TEMP8 Pin layout of INPUT Socket the SENSORMANAGER Box INPUT 1 Pin 1 Voltage 9 24Volt Pin 2 Analog Channel 1 0 10V Pin 3 Analog Channel 5 0 10V Pi...

Page 90: ...t the OUPUT to HIGH or LOW Sensor connection The sensor has to work within 0 10Volts this may be connected directly to Channels 1 8 and the CS121 will now show the values in its Web browser Alarm thresholds and actions may be configured via the EVENT manager of the CS121 7 3 3 Special features of theSENSORMANANAGER II Unlike the CS121 and the older SENSORMANAGER type the new SENSORMANAGER II confi...

Page 91: ...ined values for these types select Custom to make divergent or individual settings You can calibrate every sensor with the Sensor Range that means if you want to rise a measured value for 5 C just modify the default range from 0 100 to 5 100 Therefore you are able to adjust the measurement values like a gauged thermometer With the field Hysteresis you define the scope within the defined value can ...

Page 92: ...ich gets true only if 2 or more other events are true Figure 110 Alarm matrix Marker configuration In the figure above is shown the alarm matrix with its 8 markers to be set or unset Each marker thereby is a new state on which specific alarm scenarios can be released For example In the figure above is configured that the Marker1 will be set when at the analogue input 1 or 3 an alarm occurs Enablin...

Page 93: ...larm Matrix Switching of relay outputs Figure 112 Alarm Matrix Switching of relay outputs Detection of the analog temperature values via variables SM2_ANALOG0 SM2_ANALOG1 SM2_ANALOG2 SM2_ANALOG3 SM2_ANALOG4 SM2_ANALOG5 SM2_ANALOG6 SM2_ANALOG7 7 4 RASMANAGER The RAS Manager relays alarm signals coming from monitoring devices such as UPS SiteManagers contact alarms and the like to monitoring station...

Page 94: ...e not included and an adapter connector PINs 2 3 5 GENEREX order number GSM_A for the connection of the GSM modem and the CS121 Select into the menu COM2 AUX the GSM Modem for the COM2 mode Note It is required to disable the PIN code request of the SIM card Figure 114 PIN Adjustment Adapter Connector GSM_A Alternative you can make a Mini8 DSUB9 cable for the Siemens GSM TMA T35i Modem by yourself ...

Page 95: ...e 116 COM2 Mode GSM Modem Add an accordant function via the Events Alarms menu Select the function Send SMS with GSM modem for the notification via SMS and set the telephone number of the receiver and the message Figure 117 Configuration of the Function ...

Page 96: ... not present Slowly red flashing SIM card active Fast red flashing Figure 118 Siemens GSM TMA T35i Modem Into the menu System Network Status you can see the signal level of the modem to adjust your antenna optimal Green means a good signal is present Figure 119 GSM Signal Quality Display 7 6 LED Matrix Display The LED Matrix display is a remote display unit for relaying RCCMD messages that can be ...

Page 97: ... standard communications protocol in industry and is now the most commonly available means of connecting industrial electronic devices Modbus allows for communication between many devices connected to the same network for example a system that measures temperature and humidity and communicates the results to a computer Modbus is often used to connect a supervisory computer with a remote terminal u...

Page 98: ...er takes place in similar way Figure 122 CS121 PROFIBUS Installation 7 8 UNMS UPS Network Management System UNMS II is a UPS network monitor designed to inform you of emergency power supply systems problems before your clients end users or managers do The UNMS as a limited version is part of every UPSMAN license UPSMAN suite contains UPSMAN RS232 USB UPS Manager UPSMON Windows client and UNMS 2 li...

Page 99: ...s timeserver Microsoft Windows SNTP Timeserver As timeserver you can use any e g Windows PC in your network which has access to a timeserver in the internet or a local PC clock To use the Microsoft Windows timeserver you have to configure and start the Windows Time Server service see screenshot in the service list Figure 124 MS Timeservices ...

Page 100: ...rvice was started correctly In this case you can configure your CS121 Timeserver using the IP address of this Windows computer Note Please check if your computer is reachable through the network You may have to change the Windows Firewall settings to allow inbound Outbound UDP port 123 At Windows Server 2003 and 2008 it is required to enable the NTP server into the registry manually Open the follo...

Page 101: ...nd the maintenance of the time functions via distributed network systems Basic Configuration The following command executes the synchronization of the local system to another server to get the most accurate time prior of the start of the NTP server configuration bash ntpd b If this command does not work please use the following bash ntp b ...

Page 102: ...odify notrap noquery nopeer The NTP Pool servers have been listed as a time source already ver 4 2 onwards and they too need restrictions applied so the local server can synchronise from them Ensure the access control parameters are strict enough that the remote servers can only be used for queries restrict 0 pool ntp org mask 255 255 255 255 nomodify notrap noquery restrict 1 pool ntp org mask 25...

Page 103: ...h ntpd b If this command does not work use the following bash ntp b Figure 127 Bash ntp b You should now set the runlevels which are required for the NTPD service chkconfig level 2345 ntpd on etc init d ntpd restart or chkconfig level 2345 ntp on etc init d ntp restart Figure 128 Runlevel You can check with the following command which runlevels are active bash chkconfig list ntpd or bash chkconfig...

Page 104: ...Figure 129 Check Configuration Execute the following command to check if the service is started successful bash grep ntpd var log messages Figure 130 Check Configuration Use the NTP Query Tool bash ntpq pn ...

Page 105: ... you are using a CS121 SNMP slot card Put the DIP switches into the position OFF if you are using an external CS121 via RS232 interface Figure 132 Mainboard Inform Pyramid DSP Problem 3 CS121 reboots again and again after a few time into company s network environment Solution 3 The network monitoring software WhatsUp Gold is started We do not support this software stop the service problem solved P...

Page 106: ...e 05 20 2014 08 59 59 MAIL bad answer from mail server 504 5 7 4 Unrecognized authentication type Solution 7 The setting for mail encryption has to match the configuration on your mail server Problem 8 Not all modules are transferred to the slave into Pipe Through modus Solution 8 Since firmware version 5 x it is required that you wait at least 20 minutes until the master got all required informat...

Page 107: ...105 Figure 135 Internet Explorer LAN Proxy Einstellungen ...

Page 108: ...ule Appendix A CS121 Technical data Product Power Size Weight Operating temperature CS121L Extern 12VDC 300 mA 12 5 x 7 x 2 8 cm 210 gr 40 C CS121SC Slot chinese 13 5 x 6 x 1 5 cm 66 gr 40 C CS121F Slot FUJI 7 5 x 8 x 1 5 cm 64 gr 40 C CS121R Slot RIELLO 14 5 x 7 5 x 1 5 cm 80 gr 40 C CS121MOD MODBUS Extern 12 5 x 7 x 2 8 cm 210 gr 40 C CS121BL Budget Extern 12VDC 300mA 12 5 x 7 x 2 8 cm 202 gr 40...

Page 109: ...condensation B CE and UL Certification Both models CS121L and CS121SC are certificated by Underwriters Laboratories Inc for the US and Canada with the power supply 12 V DC 300 mA As well for both hardware specifications 121 and 131 of CS121 Adapter a certification of Conformity has been drawn up Please see the download page at www generex de to get a copy of the certifications and documents C Cabl...

Page 110: ...ure 139 External D SUB 9 polig male Pin1 DCD Pin6 DSR Pin2 RxD Pin7 RTS Pin3 TxD Pin8 CTS Pin4 DTR Pin9 RI Pin5 GND Figure 140 Slot version Circuit board connection Pin1 GND Pin2 VDD Pin3 TxD Pin4 RxD Pin9 GND Pin8 connected with Pin 10 Figure 141 Pin COM2 Mini DIN 8 pol female ...

Page 111: ... Input Output 3 Pin5 Input Output 4 Pin6 GND The maximum input voltage is 3 3V The input signals may be fed from external power sources or feed directly from Pin 1 If the external power supply delivers more than 3 3V a pre resistor has to be fitted The input resistance of the input is 1 5 k When using a opto coupler switch a Pull up resistor of 1 5kOhm has to be used Output voltage If configured a...

Page 112: ...10 Figure 144 Opto coupler logic Figure 145 Example Outputs Figure 146 Examples AUX Input on hardware model CS131 only left side pull down right side pull up configuration Figure 147 AUX Port Assignment ...

Page 113: ...nager function Additionally this device checks the input power supply and blocks the startup of the processor until the power supply is stabilized and has reached at least a level of 8 Volt This avoids startup problems at non stabilized power supplies or other power supply problems in UPS slots This product is designed to work as add on for all CS121 based products with an internal connector such ...

Page 114: ... or specific measurement values e g battery low Communication Parameters ASCII Mode works at CS131 CS121 platforms with communcation parameters 7 E 2 or 7 E 1 or with 7 N 2 from baudrate 1200 to 38400 We recommend for ASCII the use of 7 N 2 and the highest baudrate supported by your device RTU Mode works at CS131 CS121 platforms with communcation parameters 8 E 1 or 8 N 2 or 8 N 1 or 8 E 2 or 8 O ...

Page 115: ...sters 04H Read Input Registers 05H Write Single Coil Which functions are supported depends on the connected UPS For standard UPS only functions 03H and 04H are available In this case the CS121 M makes no difference between function 03H and 04H The baud rate is adjustable up to 38400 Baud Note Please note that the MODBUS adapter client allows a timeout of 40ms at 9600 baud for one value E 3 Excepti...

Page 116: ...s of first word to read word count Checksum LRC or CRC 1 byte 1 byte High byte Low byte High byte Low byte 1 or 2 byte s Answer slave no function code Byte count high byte of first word low byte of first word bytes with contents of n words Checksum LRC or CRC 1 byte 1 byte 1 byte 1 byte 1 byte n 2 bytes 1 or 2 byte s Example Read Words Function 04h ASCII Mode Read one word at address 63h 99 decima...

Page 117: ...ss Description Please note that this is just an example for a typical UPS not every UPS has all these values some UPS may have more some less Please contact your UPS manufacturer to check which variables are available and which requests are not supported Note Type U S this defines whether the answer has an algebraic sign math or not U means unsigned S means signed this answer may be positive or ne...

Page 118: ...arm Output Bad 1 active 0 not active 1 122 U 3 4 Alarm Output Overload 1 active 0 not active 1 123 U 3 4 Alarm On Bypass 1 active 0 not active 1 124 U 3 4 Alarm Bypass Bad 1 active 0 not active 1 125 U 3 4 Alarm Output Off as requested 1 active 0 not active 1 126 U 3 4 Alarm UPS Off as requested 1 active 0 not active 1 127 U 3 4 Alarm Charger Failed 1 active 0 not active 1 128 U 3 4 Alarm UPS Outp...

Page 119: ...e 10 1 146 U 3 4 xid3017 Bits 0 15 Statusbit of UPS 1 true 0 false 1 147 U 3 4 xid3017 Bits 16 31 Statusbit for details please contact NEWAVE 1 148 U 3 4 xid645 Bits 0 15 Alarmbit for details please contact NEWAVE 1 149 U 3 4 xid645 Bits 16 31 Alarmbit for details please contact NEWAVE 1 150 U 3 4 xid645 Bits 32 47 Alarmbit for details please contact NEWAVE 1 151 U 3 4 xid645 Bits 48 63 Alarmbit f...

Page 120: ...al Input Status DI 0 bit 2 Bypass working Status 0 Normal Status 1 Alert 1 1 bit 2 Bypass Interruption Status 0 Normal Status 1 Alert 1 2 bit 2 Rectifier Failure Status 0 Normal Status 1 Alert 1 3 bit 2 Inverter Failure Status 0 Normal Status 1 Alert 1 4 bit 2 Over Temperature Status 0 Normal Status 1 Alert 1 5 bit 2 Over Load Status 0 Normal Status 1 Alert 1 6 bit 2 0 Status 0 Normal Status 1 Ale...

Page 121: ...urrent 0 1A 2 12 word 4 I out T phase output current 0 1A 2 13 word 4 P out output power 0 1kVA 2 14 word 4 P out output power 0 1kW 2 15 word 4 PF output power factor 0 01Cos 2 16 word 4 U Bypass R phase voltage 0 1 Volt 2 17 word 4 U Bypass S phase voltage 0 1 Volt 2 18 word 4 U Bypass T phase voltage 0 1 Volt 19 word 4 F out output frequency 0 1Hz 20 word 4 U Bat battery voltage 0 1 Volt 21 wor...

Page 122: ...Time in Minutes 1 109 U 3 4 STATUS UPS Status ASCII HEX Please note UPSMAN status bytes table below 1 110 U 3 4 BATTVOLT Battery Voltage 1 111 U 3 4 INFREQ0 Input Frequency Phase 1 in Hz 1 112 U 3 4 INFREQ1 Input Frequency Phase 2 in Hz 1 113 U 3 4 INFREQ2 Input Frequency Phase 3 in Hz 1 114 U 3 4 CNT_PF Powerfail Counter 1 115 U 3 4 SNMP Alarm Alarmbit for details please contact NEWAVE 1 116 U 3 ...

Page 123: ...larm Alarmbit for details please contact NEWAVE 1 137 U 3 4 SNMP Alarm Alarmbit for details please contact NEWAVE 1 138 U 3 4 SNMP Alarm Alarmbit for details please contact NEWAVE 1 139 U 3 4 Status Bit Statusbit for details please contact NEWAVE 1 140 U 3 4 OUTPUT_VOLT0 Output Voltage Phase 1 1 141 U 3 4 OUTPUT_VOLT1 Output Voltage Phase 2 1 142 U 3 4 OUTPUT_VOLT2 Output Voltage Phase 1 1 143 U 3...

Page 124: ...1 103 U 3 4 OUTPUTCURR Output Current 1 104 U 3 4 LOADPERC Load 1 105 U 3 4 OUTPUTPOW Output Power in W 1 106 U 3 4 KVA KVA 1 107 U 3 4 FREQUENCY Frequency 1 108 U 3 4 CS121UPSSTAT CS121 UPS Status 1 109 U 3 4 Alarm Battery Bad 1 active 0 not active 1 110 U 3 4 Alarm On Battery 1 active 0 not active 1 111 U 3 4 Alarm Battery Low 1 active 0 not active 1 112 U 3 4 Alarm Battery Depleted 1 active 0 n...

Page 125: ...0 not active 1 131 U 3 4 Alarm Shutdown Imminent 1 active 0 not active 1 132 U 3 4 Alarm Test In Progress 1 active 0 not active 1 133 U 3 4 AUX Port 1 1 active high 0 not active low 1 134 U 3 4 AUX Port 2 1 active high 0 not active low 1 135 U 3 4 AUX Port 3 1 active high 0 not active low 1 136 U 3 4 AUX Port 4 1 active high 0 not active low 1 137 U 3 4 SensorManager SMTH_COM Sensor 1 Analog Value...

Page 126: ...UTCURR0 Input Current Phase 1 in A 1 116 U 3 4 INPUTCURR1 Input Current Phase 2 in A 1 117 U 3 4 INPUTCURR2 Input Current Phase 3 in A 1 118 U 3 4 INPUTPOW0 Input Power Phase 1 in W 1 119 U 3 4 INPUTPOW1 Input Power Phase 2 in W 1 120 U 3 4 INPUTPOW1 Input Power Phase 3 in W 1 121 U 3 4 BATTVOLT Battery Voltage in V 1 122 U 3 4 BATTTEMPDEG Battery Temperature in Degree Celsius 1 123 U 3 4 BATTSEC ...

Page 127: ... 4 INVOLT Input Voltage l1 n 1 101 U 3 4 INVOLT Input Voltage l2 n 1 102 U 3 4 INVOLT Input Voltage l1 l2 1 103 U 3 4 OUTPUTVOLT Output Voltage l1 n 1 104 U 3 4 OUTPUTVOLT Output Voltage l2 n 1 105 U 3 4 OUTPUTVOLT Output Voltage l1 l2 1 106 U 3 4 OUTPUTCURR Output Current l1 n 1 107 U 3 4 OUTPUTCURR Output Current l2 n 1 108 U 3 4 OUTPUTWAT Output Watts l1 n 1 109 U 3 4 OUTPUTWAT Output Watts l2 ...

Page 128: ...d 1 active 0 not active 1 134 U 3 4 Alarm UPS Off As Requested 1 active 0 not active 1 135 U 3 4 Alarm Charger Failed 1 active 0 not active 1 136 U 3 4 Alarm UPS Output Off 1 active 0 not active 1 137 U 3 4 Alarm UPS System Off 1 active 0 not active 1 138 U 3 4 Alarm Fan Failure 1 active 0 not active 1 139 U 3 4 Alarm Fuse Failure 1 active 0 not active 1 140 U 3 4 Alarm General Fault 1 active 0 no...

Page 129: ...Value 1 156 U 3 4 SensorManager Sensor 6 Analog Value 1 157 U 3 4 SensorManager Sensor 7 Analog Value 1 158 U 3 4 SensorManager Sensor 8 Analog Value 1 Secti on OEM POWERTRONIX MIZAR Adres se Name ALCOR QUASAR SUPERNOVAE 100 Outpower Phase 1 x x x 101 Outpower Phase 2 x x x 102 Outpower Phase 3 x x x 103 Battery Capacity x x x 104 Input Voltage Phase 1 V x x x 105 Input Voltage Phase 2 V x x x 106...

Page 130: ... x x x 126 Alarm UPS Off As Requested x x x 127 Alarm Charger Failed x x 128 Alarm UPS Output Off x x x 129 Alarm UPS Sytem Off not supported x not supported 130 Alarm Fan Failure x not supported x 131 Alarm Fuse Failure not supported not supported not supported 132 Alarm General Fault x x x 133 Alarm Diagnose Test Failed not supported not supported not supported 134 Alarm Communication Lost x x x...

Page 131: ...4 OUTPOWER1 Outpower Phase 2 1 109 U 3 4 OUTPOWER2 Outpower Phase 3 1 110 U 3 4 SOLSETEMPBAD Temperature bad 1 111 U 3 4 SOLSEINPUTBAD Input bad 1 112 U 3 4 SOLSEOVERLOAD Overload 1 113 U 3 4 SOLSEBYPASSFAULT Bypass fault 1 114 U 3 4 SOLSECHARGERFAULT Charger fault 1 115 U 3 4 SOLSEGENERALFAULT General fault 1 116 U 3 4 SOLSESDPENDING Shutdown pending 1 117 U 3 4 SOLSETESTRESULT Test result 1 118 ...

Page 132: ... 2 1 102 U 3 4 OUTPOWER2 Outpower Phase 3 1 103 U 3 4 BATTCAP Battery Capacity 1 104 S 3 4 INVOLT0 Input Voltage Phase 1 V 1 105 S 3 4 INVOLT1 Input Voltage Phase 2 V 1 106 S 3 4 INVOLT2 Input Voltage Phase 3 V 1 107 S 3 4 TEMPDEG Temperature C 1 108 S 3 4 AUTONOMTIME Autonomy Time minutes 1 109 U 3 4 STATUS e g UPS normal 4 Powerfail 12 Battery test running 68 Bypass 5 UPS Status ASCII HEX please...

Page 133: ... 3 Alarm UPS Output Off 1 129 U 3 4 SNMPALARMS 0x4000 1 4 Alarm UPS System Off 1 130 U 3 4 SNMPALARMS 0x8000 1 5 Alarm Fan Failure 1 131 U 3 4 SNMPALARMS 0x10000 1 Alarm fuse failure 1 132 U 3 4 SNMPALARMS 0x20000 1 Alarm general fault 1 133 U 3 4 SNMPALARMS 0x40000 1 Alarm diagnose test failed 1 134 U 3 4 SNMPALARMS 0x80000 1 Alarm communication lost 1 135 U 3 4 SNMPALARMS 0x100000 Alarm awaiting...

Page 134: ...for details please contact Effekta directly 1 156 U 3 4 AEESerModulePresent 6 Status data for details please contact Effekta directly 1 157 U 3 4 AEESerModuleError 1 1 Status data for details please contact Effekta directly 1 158 U 3 4 AEESerModuleError 1 2 Status data for details please contact Effekta directly 1 159 U 3 4 AEESerModuleError 1 3 Status data for details please contact Effekta direc...

Page 135: ...Status data for details please contact Effekta directly 1 173 U 3 4 AEESerModuleError 5 1 Status data for details please contact Effekta directly 1 174 U 3 4 AEESerModuleError 5 2 Status data for details please contact Effekta directly 1 175 U 3 4 AEESerModuleError 5 3 Status data for details please contact Effekta directly 1 176 U 3 4 AEESerModuleError 5 4 Status data for details please contact E...

Page 136: ...eState 3 Status data for details please contact Effekta directly 1 190 U 3 4 AEESerModuleState 4 Status data for details please contact Effekta directly 1 191 U 3 4 AEESerModuleState 5 Status data for details please contact Effekta directly 1 192 U 3 4 AEESerModuleState 6 Status data for details please contact Effekta directly 1 193 U 3 4 AEESerModuleVolt 1 Status data for details please contact E...

Page 137: ...RRENT0 Output Current Phase 1 in Ampere 10 1 155 U 3 4 OUTPUT_CURRENT1 Output Current Phase 2 in Ampere 10 1 156 U 3 4 OUTPUT_CURRENT2 Output Current Phase 3 in Ampere 10 1 Section Transfer Switches All transfer switch vendors except PILLER 1 U 3 4Sources Asynchronous Warning input current difference switching might not be possible 1 2 U 3 4Static Switch A Failure Alarm switching failure 1 3 U 3 4...

Page 138: ...4 BATTCAP Battery capacity in percent 1 104 U 3 4 INVOLT0 Input Voltage Phase 1 in V 1 105 U 3 4 INVOLT1 Input Voltage Phase 2 in V 1 106 U 3 4 INVOLT2 Input Voltage Phase 3 in V 1 107 U 3 4 TEMPDEG Temperature C 1 108 U 3 4 AUTONOMTIME Autonomy Time minutes 1 109 U 3 4 STATUS GENEREX UPS status 1 110 U 3 4 BATTVOLT Battery Voltage V 1 111 U 3 4 INFREQ0 Input Frequency Hz Phase 1 1 112 U 3 4 INFRE...

Page 139: ...4 TRIMOD_OUTCURR1 10 0 Output Current 2 1 145 U 3 4 TRIMOD_OUTCURR2 10 0 Output Current 3 1 152 U 3 4 TEMP1 Sensormanager SMTCOM sensor 1 1 153 U 3 4 TEMP2 Sensormanager SMTHCOM sensor 2 1 154 U 3 4 TEMP3 Sensormanager sensor 3 1 155 U 3 4 TEMP4 Sensormanager sensor 4 1 156 U 3 4 TEMP5 Sensormanager sensor 5 1 157 U 3 4 TEMP6 Sensormanager sensor 6 1 158 U 3 4 TEMP7 Sensormanager sensor 7 1 159 U ...

Page 140: ...RR Nominal Current 1 109 U 3 4STATUS GENEREX UPS Status see below 1 110 U 3 4 EX_EXTSTATUS 0xffff0000 16 Bytes 98 99 Device Status 1 111 U 3 4EX_EXTSTATUS 0xffff Bytes 100 101 Device Status 1 112 U 3 4 STATUS 0x02 2 Output active 1 on 0 off 1 113 U 3 4 STATUS 0x20 5 Overtemperature 1 on 0 off 1 114 U 3 4 STATUS 0x40 6 Test active 1 on 0 off 1 115 U 3 4 STATUS 0x100 8 Overload 1 on 0 off 1 116 U 3 ...

Page 141: ...16384 for snmp UPS_SB_DVG_ALARM 0x8000 32768 SiteManager SiteMonitor Example decimal STATUS 5 means UPS_SB_OUTPUT_ACT 4 UPS_SB_BYPASS_MODE 1 are active UPS on Bypass STATUS 12 means UPS_SB_OUTPUT_ACT 4 UPS_SB_BACKUP_MODE 8 are active UPS Powerfail STATUS 22 means UPS_SB_OUTPUT_ACT 4 UPS_SB_BACKUP_MODE 8 UPS_SB_BATTERY_LOW 10 are active UPS Powerfail and Battery low STATUS 4 means UPS_SB_OUTPUT_ACT...

Page 142: ... position Figure 151 MODBUS CS121 COM2 Settings E 9 TCP IP UDP Ports The following are ports of the CS121 SNMP Adapter These are the ports that have to be made available in the Firewall in order to use all of the CS121 functions Echo 7 tcp echo 7 udp WOL 9 udp ftp data 20 tcp ftp 21 tcp telnet 23 tcp smtp 25 tcp http 80 tcp snmp 161 udp snmptrap 162 udp time rfc868 37 tcp time sntp 123 tcp rccmd 6...

Page 143: ... all variables are supported from all UPS models Please try the use of the variable to see whether your UPS supports the variable or not Variable Meaning OUTPUT_VOLT Output voltage only supported from specified USV manufactures OUTPUT_CURRENT Output currency SECSONBATT Seconds since the event power outage has been released STATUS Actual UPS state INVOLT0 Input voltage phase 1 INVOLT1 Input voltage...

Page 144: ...IN Resttime AUTONOMTIME POWERREMAIN LOCALTIME Local timestamp OUTPHASES Output phase INPHASES Input phase LOCATION UPS Adapter location DATE Date TIME Time ATTACHED_DEVICESAttached devices BATTINSTDATE Battery installation date AGENTSOFTREV Firmware version MANUFACTURER Manufacturer TEMP1 TEMP8 Actual measurement for sensors 1 8 used for SensorMan settings only TEMP1LOCATION TEMP8LOCATION Configur...

Page 145: ...s The Events Alarms are different from UPS to UPS depending on the UPS manufacturer We are describing in the following example the Events Alarms of a NEWAVE UPS which are similar to most of the UPS Anyway all alarms which are not POWERFAIL BATTERY LOW SYSTEM SHUTDOWN UPSMAN STARTED and AUX you should advice your UPS manufacturer because an UPS hardware failure might be present The mentioned alarms...

Page 146: ...ve Load will be supplied through the grid directly Maintenance Breaker Open Maintenance breaker open inactive Load will be supplied via the UPS Regular UPS protected operation Inverter Breaker Open Inverter breaker open Load is not UPS protected Inverter Breaker Closed Inverter breaker closed Load will be supplied via the inverter Normal condition Battery Breaker Open Battery breaker open No batte...

Page 147: ...tdown Imminent UPS shutdown switching off is imminent Unit Powerfail Powerfail at an UPS module Unit Power Restored Power restored at an UPS module Redundancy Lost UPS redundancy lost load to high or UPS modules are not at hand Inverter Failure Inverter failure Emergency Power Off Emergency power off UPS was switched off Synchronization Error Synchronization error between the parallel modules or f...

Page 148: ...Generator on Generator Off Generator off Output Normal Output normal normal condition Redundancy Ok Redundancy is at hand AUX Port 1 High AUX port 1 opened AUX Port 2 High AUX port 2 opened AUX Port 3 High AUX port 3 opened AUX Port 4 High AUX port 4 opened AUX Port 1 Low AUX port 1 closed AUX Port 2 Low AUX port 2 closed AUX Port 3 Low AUX port 3 closed AUX Port 4 Low AUX port 4 closed Schematic ...

Page 149: ...d UPS RS232 communication restored UPS Battery Old UPS batteries too old call UPS service Overload UPS overload reduce load otherwise the UPS shutdown is pending Load Normal No more overload Overtemperature Overtemperature of the UPS Temperature Normal Temperature of the UPS is back in normal range Bypass on Bypass on Bypass off Bypass off Battery low The autonomy of the battery has reached the de...

Page 150: ...ork devices and configure an alert generating SNMP trap based monitor to raise alerts when specific traps are received from cs121 devices Installation of the SNMP service on Windows Server 2003 In the Control Panel select Add Remove Programs Click on Add Remove Windows Components Scroll down and select Management and Monitoring Tools click Details Click on the checkboxes for Simple Network Managem...

Page 151: ...of the managed devices that will forward SNMP traps to the OpsMgr server Alternatively you could select the Accept SNMP packets from any host option Restart the SNMP Service IMPORTANT SNMP community strings are case sensitive Activate the SNMP Trap Service on Windows Server 2003 In the Services Panel select the SNMP Trap Service In the SNMP Trap Service properties dialog select Startup type Automa...

Page 152: ...s of this configuration step Configuration of one or more alert generating SNMP trap based Monitors In the Administration space create a unsealed management pack to store your SNMP based monitoring rules Figure 155 General Properties In the Operations console Authoring space start the Create a Monitor Wizard On the Select a Monitor Type page do the following Expand SNMP Trap Based Detection Simple...

Page 153: ... Monitor Optionally type a Description for the monitor Click Select select View all targets click a target such as SNMP Network Device and then click OK Leave Monitor is enabled selected to have the monitor take affect at the completion of the wizard or clear the check box to enable the monitor at a later time and then click Next ...

Page 154: ... page for the First SNMP TrapProvider leave Use discovery community string selected Click to place the cursor in the Object Identifier Properties section and type the first object identifier OID that you want to monitor 1 3 6 1 2 1 33 2 3 upsTrapAlarmEntryAdded Then click Next ...

Page 155: ...nd 2 Value Why did we use SnmpVarBind 2 in our expression Because the traps second contains the OID of the traps UPS alarm Object upsAlarmDescr of the trap Click to place the cursor in the Operator section and select Equals Click to place the cursor in the Value section and type the value to match here 1 3 6 1 2 1 33 1 6 3 2 The 1 3 6 1 2 1 33 1 6 3 2 is the well known alarm OID for upsAlarmOnBatt...

Page 156: ... On the Build Event Expression page click to place the cursor in the Parameter Name section and type the trap parameter variable that you want to use here DataItem SnmpVarBinds SnmpVarBind 2 Value Why did we use SnmpVarBind 2 in our expression Because the traps second contains the OID of the traps UPS alarm Object upsAlarmDescr of the trap Click to place the cursor in the Operator section and sele...

Page 157: ... Health On the Configure Alerts page set the properties of the alert for example Type the Name for the alert such as UPS OnBattery Alert Optionally type the Alert description You can also click the button and select Target and Data variables to include in the description such as Device Name Select a Priority from the list such as High Select a Severity from the list such as Critical Click Create ...

Page 158: ... What would you like to manage page select Network Devices Then click Next 192 168 On the Discovery Method page enter the Start and End of the IP address range that you want to scan Type the SNMP community of the objects that you want to manage Select the Management Server that should receive the cs121 traps Click Discover to display the Discovery Progress page ...

Page 159: ...inish The objects will display in the Network Devices node of the Operations Console Administration space At this point SNMP enabled device availability monitoring will start automatically Any traps of kind upsAlarmOnBattery received from the cs121 target devices will be raised as alerts in the Operations console K DHCP Configuration via Telnet Establish a connection to the CS121 via telnet Select...

Page 160: ...er the reboot L RARITAN Dominion PDU Configuration In the following we will describe how a RARITAN PDU Type Dominion can be controlled through any RCCMD client or any CS121 or any other RCCMD compatible device 1 Install a RCCMD client on a Windows OS and copy create a file like the following into the RCCMD directory default C Program Files RCCMD and use a SNMPwalk tool from an open source with the...

Page 161: ...f the Raritan Community This is the community string for write access configured at the Raritan or SNMP set commands default is public Outlet This is the number of the Raritan Outlet 1 to 12 which you want to switch On Off This is the signal you want to transmit where 0 is off and 1 is on Example pxout bat 192 168 200 11 public 0 This example will switch the Raritan with the IP address 192 168 200...

Page 162: ...the background on this Windows computer so you will better see whats going on Stop the RCCMD service than open a command line into the RCCMD folder and start rccmd exe debug Now the software will run in the foreground and you can watch the communication 4 The Raritan with firmware 1 4 1 is unfortunetaley buggy Here the workaround The default community strings for the Raritan are identically set fo...

Page 163: ...in normal mode 13 Figure 4 Connection PC Switch Hub and CS121 2 Connection PC Cross Cable Network Cable and CS121 16 Figure 5 HTTP Administrator login 17 Figure 6 HTTP UPS Model System Settings 18 Figure 7 HTTP Network Security Settings 18 Figure 8 Telnet Main Menu 19 Figure 9 Telnet IP Settings 19 Figure 10 Telnet UPS Settings 20 Figure 11 HTTP Adapter reboot dialog 21 Figure 12 HTTP System Netwo...

Page 164: ...ettings 46 Figure 44 HTTP RAS Manager Settings 47 Figure 45 HTTP Scheduled Actions 47 Figure 46 HTTP CS121 DataLog 50 Figure 47 HTTP CS121 ExternalDeviceLog 51 Figure 48 HTTP CS121 UPS Events 51 Figure 49 HTTP Job Editor RCCMD Trap Event Power restored 53 Figure 50 HTTP Job Editor RCCMD TRAP 54 Figure 51 HTTP Job Editor RCCMD Shutdown 55 Figure 52 HTTP Event Configuration 56 Figure 53 HTTP Event E...

Page 165: ...II Settings 84 Figure 102 SENSORMANAGER II LEDs 85 Figure 103 SENSORMANAGER II Status Site 87 Figure 104 SENSORMANAGER II Configuration Analog Inputs 87 Figure 105 SENSORMANAGER II Configuration Outlets 88 Figure 106 Alarm matrix Marker configuration 88 Figure 107 Alarm Matrix Switching of relay outputs 89 Figure 108 Alarm Matrix Switching of relay outputs 89 Figure 109 RASMANAGER network integrat...

Page 166: ...re 145 CS121 WDP piggyboard installed on a CS121 SC BSC view from left and behind 109 Figure 146 CS121 WDP connecting PINs on a CS121 SC BSC board top view 110 Figure 147 MODBUS Jumper 138 Figure 148 MODBUS CS121 COM2 Settings 138 Figure 149 MODBUS Cable 112 139 Figure 150 SNMP Service Properties 147 Figure 151 SNMP Trap Service 147 Figure 152 General Properties 148 Figure 153 Select a Monitor Typ...

Reviews: