120
0
bit
1 / 5
UPS Turn On
1
bit
1 / 5
UPS Shut down
2
bit
1 / 5
Alarm Reset
3
bit
1 / 5
Battery Instant Charging
4
bit
1 / 5
Battery Floating Charging
5~10
bit
For future expansion
After
Vender self definition
Section OEM Rittal PMC Extension
New
from
CS121
firmware
version
4.50.14
100
U
3 / 4
OUTPOWER0
True Output Power Current
Phase 1 in Kilowatt
1
101
U
3 / 4
OUTPOWER1
True Output Power Current
Phase 2 in Kilowatt
1
102
U
3 / 4
OUTPOWER2
True Output Power Current
Phase 3 in Kilowatt
1
103
U
3 / 4
BATTCAP
Battery Capacity
1
104
U
3 / 4
INVOLT0
Input Voltage Phase 1
1
105
U
3 / 4
INVOLT1
Input Voltage Phase 2
1
106
U
3 / 4
INVOLT2
Input Voltage Phase 3
1
107
U
3 / 4
TEMPDEG
Temperature in Degree C°
1
108
U
3 / 4
AUTONOMTIME
Autonomy Time in Minutes
1
109
U
3 / 4
STATUS
UPS Status (ASCII HEX)
Please note UPSMAN status
bytes table below
1
110
U
3 / 4
BATTVOLT
Battery Voltage
1
111
U
3 / 4
INFREQ0
Input Frequency Phase 1 in
Hz
1
112
U
3 / 4
INFREQ1
Input Frequency Phase 2 in
Hz
1
113
U
3 / 4
INFREQ2
Input Frequency Phase 3 in
Hz
1
114
U
3 / 4
CNT_PF
Powerfail Counter
1
115
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
116
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
117
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
118
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
119
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
120
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
121
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
122
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1
123
U
3 / 4
SNMP Alarm
Alarmbit, for details please
contact NEWAVE
1