Model FL3112
4
2.0 Specifications
2.1 System
Specifications
Certification:
EExed – IIC T5 -40ºC TO +75ºC
EExed – IIC T6 -40ºC TO +65ºC
IP66/67
IR Detector center wavelength: (figure 1-B)
4.35 microns
Typical Response Time*:
< 3 sec. @ 50 ft.
Minimum Response Time:
< 500 ms.
Field of Vision*: (figure 3-A)
120
°
maximum
Sensitivity:
50 feet (15.2m); Maximum distance for a 1 square foot (
.092m
2
) gasoline fire to be
reliably
detected.
Maximum Cable Parameters:
4-20mA Output Signal
9000 feet (2750 m), maximum 50 Ohms loop, with maximum 250 Ohms input
impedance of readout unit.
Remote power supply
3000 feet (930 m), maximum 20 Ohms loop and 24 VDC minimum. (
See Section 3-4
Terminal Connections
)
Approvals:
ATEX & CE Mark
Warranty:
Two Years
* NOTE:
1.
Response Times and Field of View data have been derived by testing the Model
FL3112 Flame Detector with a 1 square foot gasoline fire. One cup of unleaded
gasoline on top of a one inch layer of water was ignited for each test. These are
typical values and different results may occur depending on the variation of each
fire.
2.
To meet the directional dependence requirements of EN 54-10 the horizontal
viewing angle must not exceed ±30°.