Model FL3112
16
WARN and ALARM Relay Options
WARN
(1)
Relay
ALARM (2) Relay
DIP LA NL
EN
DE
LA NL
EN DE
1
ON
OFF
2
ON
OFF
3
ON
OFF
4
ON
OFF
5
OFF OFF OFF OFF
OFF OFF OFF OFF
6
OFF OFF OFF OFF
OFF OFF OFF OFF
7
OFF OFF OFF OFF
OFF OFF OFF OFF
8
ON ON ON ON ON ON ON ON
LA
= Latching
NL
= Non Latching
EN
= Energized
DE
= De-Energized
The above options have been represented pictorially on the label attached to the
Program Card
Return to FACTORY DEFAULT settings
DIP Default
5
ON
6
ON
7
OFF
8
ON
DIP switch positions 1 to 4 are not relevant here
WARNING: During the following steps proper anti-static procedures must
be observed. Failure to do so may permanently damage the FL3112
electronic circuits and void the warranty.
To (re)program, remove the detector from the Base Assembly, disconnect the fly-lead
and disconnect the retainer strap at the rear of the Base only.
1. Refer to figure 3-G and remove the five screws securing the front cap assembly to
the FL3112 enclosure.
2. Remove the front cap assembly.
3. Disconnect the fly-lead connector from the power supply board.
4. Insert the Program Card with the required DIP switch settings into connector J3 on
the microprocessor board.