Model FL3112
27
7.6 FL3112
Command Register Locations
7.6.1 Operational
Mode
Commands
R – indicates Read Only Access
R/W – indicates Read/Write Access
LFF – Low Frequency Fire
HFF – High Frequency Fire
LFS – Low Frequency Sun
Master
Reg
I/O
Refer
to
Parameter Function Type Scale Access Addr Addr Section
Analogue
4-20mA Current Output
Value 16-Bit
R
0000 40001
7-7-1
Mode
Indicates Fire Status Mode
Value (0-11)
R
0001 40002
7-7-2
Status/Error Indicates
error
Bit 8-Bit R
0002
40003 7-7-3
Fire Type
LFF, HFF or both
Value (1,2,3)
R
0003 40004
7-7-4
Model Type
Identifies the Model FL3112
Value (3112)
R
0004 40005
7-7-5
Software Rev Indicates the SW Revision
ASCII 2-Char R
0005 40006
7-7-6
COPM Fault
IR COPM Fault
Bit
8-Bit
R
0006 40007
7-7-7
Not Used
0007
40008
Options
Indicates Unit Options
Bit
8-Bit
R/W
0008 40009
7-7-8
Address
Unit Address
Value (1-247) R/W
0009 40010
7-7-9
Not Used
000A
40011
Baud Rate
Indicates present Baud Rate
Value (0-3)
R/W
000B 40012
7-7-10
(2400,
4800,
9600,
19200)
Data Format
Indicates Data Format
Value (0-3)
R/W
000C 40013
7-7-11
(8-N-1, 8-E-1, 8-O-1, 8-N-2)
Not Used
000D
40014
Not Used
000E
40015
Fire COPM
Indicates Total No. of Fire
Value 8-Bit
R
000F 40016
7-7-12
Fault Total
Channel Window/Detector
COPM
Faults
Sun COPM
Indicates Total No. of Sun
Value 8-Bit
R
0010 40017
7-7-13
Fault Total
Channel Window/Detector
COPM
Faults
Remote Reset Remotely Resets the Alarm
Bit
1-Bit
R/W
0011 40018
7-7-14
& Warn Condition