Model FL3112
24
7.3.2 Modbus
Read
Response Message
Byte
Modbus
Range
Referenced to FL3112
1
st
Slave Address
1-247* (Decimal) FL3112 ID (Address)
2
nd
Function Code
03
Read Holding Registers
3
rd
Byte Count
02
No. of Data Bytes
4
th
Data Hi 00-FF (Hex)
FL3112 Hi Byte Status Data
5
th
Data Lo
00-FF (Hex)
FL3112 Lo Byte Status Data
6
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
7
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time
7.4 Modbus Write Command Protocol (Query/Response)
7.4.1 Modbus
Write Query Message
Byte
Modbus
Range
Referenced to FL3112
1
st
Slave Address
1-247* (Decimal) FL3112 ID (Address)
2
nd
Function Code
06
Preset Single Register
3
rd
Register Address Hi**
00
Not used by FL3112
4
th
Register Address Lo**
00-FF (Hex)
FL3112 Command Registers
5
th
Preset Data Hi
00-FF (Hex)
FL3112 Hi Byte Command Data
6
th
Preset Data Lo
00-FF (Hex)
FL3112 Lo Byte Command Data
7
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
8
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time.
** Note: Register Address can be a maximum of 9999 Address Locations (0000-270E)
7.4.2 Modbus
Write Response Message
Byte
Modbus
Range
Referenced to FL3112
1
st
Slave Address
1-247* (Decimal) FL3112 ID (Address)
2
nd
Function Code
06
Preset Single Register
3
rd
Register Address Hi**
00
Not used by FL3112
4
th
Register Address Lo**
00-FF (Hex)
FL3112 Command Register
5
th
Preset Data Hi
00-FF (Hex)
FL3112 Hi Byte Command Data
6
th
Preset Data Lo
00-FF (Hex)
FL3112 Lo Byte Command Data
7
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
8
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time.