Model FL3112
33
7.7.13
Sun COPM Fault Total
A read indicates the Total Number of Sun Channel Window or Sensor COPM Faults that
occurred in the slave device. This fault is usually caused by a dirty Window or a faulty Fire
Channel Sensor or Circuitry. The maximum count is 255 and then the counter will roll over
to zero and begin counting again.
7.7.14 Remote
Reset
Writing a 1 to the bit activates the Remote Reset function that resets the Alarm and Warn
Conditions. The function is active momentarily and will reset automatically after being
used.
Function Bit
(LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
7.7.15
Remote Alarm Test
Writing a 1 to the bit activates the Remote Alarm Test function that activates the Warn and
Alarm relay turn-on along with the analogue current status. Once the Alarm Test is
complete the function should be disabled by writing a zero to Remote Alarm Test and then
resetting the Alarm and Warn relays by writing a one to the Remote Reset (referenced
above).
Function Bit
(LSB) Access
Enable 1 Read/Write
Disable 0 Read/Write
7.7.16 Clear
COPM
Faults
A write to enable the bit activates the Clear COPM Faults function that resets all of the Fire
Window COPM faults, the Fire Sensor COPM Faults, and the Sun COPM Faults. The bit
and enable function is active momentarily and will reset to disable and zero after being
used.
Function
Bit (LSB)
Access
Enable
1
Read/Write
Disable
0
Read/Write