2.7 AUXILIARY
CONTACTS
If desired, there are Auxiliary Contacts on the transfer switch to
operate customer accessories, remote advisory lights, or remote
annunciator devices. A suitable power source must be connected to
the COMMON (C) terminal. See Figure 2.4.
Contact operation is shown in the following chart:
Switch Position
Utility
Standby
Common to Normally Open
Open
Closed
Common to Normally Closed
Closed
Open
NOTE:
Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC. DO
NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE
CONTACTS.
Figure 2.4 – 400A Switch Auxiliary Contacts