Generac Power Systems RTSG300A3 Owner'S Manual Download Page 12

 10 

3.4  GENERATOR TESTS UNDER LOAD

1.  Set the generator's main circuit breaker to its OFF or OPEN posi-

tion.

2.  Manually actuate the transfer switch main contacts to their emer-

gency (Standby) position. Refer to “Manual Operation”.

3.  To start the generator, select the MANUAL mode or operation. 

When engine starts, let it stabilize for a few minutes.

4.  Turn the generator's main circuit breaker to the ON or CLOSED 

position. The generator now powers all LOAD circuits. Check 

generator operation under load as follows:

•    Turn ON electrical loads to the full rated wattage/amperage 

capacity of the generator. DO NOT OVERLOAD.

•    With maximum rated load applied, check voltage and frequency 

across transfer switch terminals E1 and E2. Voltage should be 

greater than 230 volts (240VAC system); frequency should be 

greater than 59 Hz.

•    Let the generator run under rated load for at least 30 minutes. 

With unit running, listen for unusual noises, vibration, overheat-

ing, etc., that might indicate a problem.

5.   When checkout under load is complete, set main circuit breaker 

of the generator to the OFF or OPEN position.

6.   Let the generator run at no-load for several minutes. Then, shut 

down by selecting the OFF mode.

7.   Move the switch's main contacts back to the UTILITY position. 

For example, load connected to utility power supply. Refer to 

“Manual Operation”. Handle and operating lever of transfer 

switch should be in down position.

8.   Turn on the utility power supply to transfer switch, using what-

ever means provided (such as a utility main line circuit breaker). 

The utility power source now powers the loads.

9.   Select the generator's OFF mode to shut down the generator. 

The system is now set for fully automatic operation.

3.5 CHECKING 

AUTOMATIC 

OPERATION

To check the system for proper automatic operation, proceed as fol-

lows:
1.  Ensure that the generator is in it’s OFF mode.
2.  Install front cover of the transfer switch.
3.  Turn ON the utility power supply to the transfer switch, using the 

means provided (such as a utility main line circuit breaker).

NOTE:

Transfer Switch will transfer back to utility position.
4.  Set the generator’s main circuit breaker to its ON (or CLOSED) 

position.

5.  On the generator panel, select the AUTO mode. The system is 

now ready for automatic operation.

6.  Turn OFF the utility power supply to the transfer switch.
With the generator ready for automatic operation, the engine should 

crank and start when the utility source power is turned OFF after a 

10 second delay (factory default setting). After starting, the transfer 

switch should connect load circuits to the standby side after a five 

(5) second delay. Let the system operate through its entire automatic 

sequence of operation.

3.6   TESTING OVERLOAD PREVENTION 

CONTROL BOARD (OPCB)

A Test push-button is provided on the bottom of the OPCB to test the 

operation of the load shed functions. The Test button will work when 

the ATS is in the Utility or the Generator position. 
1.  Turn the Utility supply on to the ATS.
2.  Press the TEST push-button on the OPCB.
3.  Verify that all of the connected loads to be “shed” become dis-

abled. The method of verification will depend on the type of load.

4.  After five (5) minutes verify AC 1 and Load 1 are energized 

Status LED AC 1 and Load 1 is ON.

5.  After another 15 seconds, verify AC 2 and Load 2 are energized 

Status LED AC 2 and Load 2 are ON.

6.  After another 15 seconds, verify Load 3 is energized Status Load 

3 is ON.

7.  After another 15 seconds, verify Load 4 is energized Status Load 

4 is ON.

3.7 INSTALLATION 

SUMMARY

1.  Ensure that the installation has been properly performed as 

outlined by the manufacturer and that it meets all applicable laws 

and codes.

2.  Test and confirm proper operation of the system as outlined in 

the appropriate installation and owner’s manuals.

3.  Educate the end-user on the proper operation, maintenance and 

service call procedures.

3.8   SHUTTING THE GENERATOR DOWN 

WHILE UNDER LOAD

Important! To turn the generator off during utility outages to 

perform maintenance, or conserve fuel, follow these important 

steps:
To turn the generator OFF (while running in AUTO and online):
1.  Turn OFF (or OPEN) the main Utility disconnect.
2.  Turn OFF (or OPEN) the Main Line Circuit Breaker (MLCB) on 

the generator.

3.  Turn the generator OFF.
To turn the generator back ON:
1.  Put the generator back into AUTO and allow to start and warm-

up for a few minutes.

2.  Turn ON (or CLOSE) the MLCB on the generator.
The system will now be operating in its automatic mode. The main 

utility disconnect can be turned ON (or CLOSED), but to shut the unit 

off, this complete process must be repeated.

Operation

Summary of Contents for RTSG300A3

Page 1: ...This manual should remain with the unit Owner s Manual Automatic Transfer Switch SE 300 400 Amp Single Phase REFERENCE ALL APPROPRIATE DOCUMENTATION...

Page 2: ...tility distribution system when the generator is operating Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems as applicable Failure to isolate electric system by thes...

Page 3: ...LL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF Competent qualified personnel should install operate and service this equipment Adhere strictly to local state and national elec...

Page 4: ...ctrical feedback between two different power sources such as the UTILITY and GENERATOR sources and for that reason codes require it in all standby electric system installations The transfer switch con...

Page 5: ...1 1AMAX 1AMAX 1AMAX 1AMAX A C 2 LOAD 2 LOAD 3 LOAD 4 Air ConditionerConnections Up to two A Cs can be controlled here via their low voltage thermostatwires Status LEDs Shows which loads are currently...

Page 6: ...ize conductors The installation must comply fully with all applicable codes standards and regulations All power cables must enter the enclosure through the knockouts provided If not using the knockout...

Page 7: ...ould be used Use quick connect terminals to make the contactor coil connections on the PMM See Figure 2 1 A grommet is provided to route Class 2 wiring through The grommet can be used in any knockout...

Page 8: ...Loads of lesser importance are wired to the remaining contactors Load 3 Load 4 If the OPCB is fully functional and managing six connected loads and an event occurs which causes a load to increase bey...

Page 9: ...Closed Common to Normally Closed Closed Open NOTE Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE CONTACTS Figure 2 4 400A Switch Auxili...

Page 10: ...eration 3 2 MANUAL OPERATION Do NOT manually transfer under load Disconnect transfer switch from all power sources by approved means such as a main circuit breaker s A manual HANDLE is shipped with th...

Page 11: ...NEUTRAL and N2 to NEUTRAL FAILURE TO TURN OFF THE UTILITY SUP PLY BEFORE WORKING ON THE UTILITY CONNECTIONS OF THE ATS WILL RESULT IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK 3 When ce...

Page 12: ...the AUTO mode The system is now ready for automatic operation 6 Turn OFF the utility power supply to the transfer switch With the generator ready for automatic operation the engine should crank and s...

Page 13: ...N2 NEU E2 GROUND CUSTOMER SUPPLIED NEUTRAL WIRE NEUTRAL BLOCK CONNECTION PANEL LIQUID COOLED ENGINE GENERATOR NOTES 1 INSTALLATION MUST MEET ALL NATIONAL STATE AND LOCAL ELECTRICAL CODES RESIDENTIAL...

Page 14: ...0mm 42 91 1219 3mm 48 00 554 3mm 21 82 255 5mm 10 06 PADLOCK CUSTOMER SUPPLIED LOCATION 571 5mm 22 50 NOTE FOR 3R RATINGS CONDUITS MUST ENTER BELOW ENERGIZED COMPONENTS FOR FURTHER DETAILS SEE INTERC...

Page 15: ...13 Notes...

Page 16: ...nc All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S4...

Page 17: ...15 Este manual debe permanecer con la unidad Manual del propietario Interruptor autom tico de transferencia ATS SE monof sico de 300 400 A CONSULTE TODA LA DOCUMENTACI N APROPIADA...

Page 18: ...t funcionando Art culo 701 Sistemas de reserva requeridos legalmente o art culo 702 Sistemas de reserva opcionales seg n corresponda No aislar el sistema el ctrico mediante estos medios puede ocasiona...

Page 19: ...AN SIDO EFECTIVAMENTE COLOCADOS EN OFF La instalaci n operaci n y servicio de este equipo deben ser realizados por personal competente y calificado Observe estrictamente los c digos el ctrico y de con...

Page 20: ...es de SERVICIO P BLICO y de GENERADOR y por ese motivo los c digos lo requieren en todas las instalaciones de los sistemas el ctricos de reserva El interruptor de transferencia consta de un mecanismo...

Page 21: ...sta dos A A a trav s de sus cables de termostato de bajo voltaje LED de estado Muestra a qu cargas se les permite funcionar actualmente Conexiones de carga Se pueden controlar hasta cuatro cargas de c...

Page 22: ...instalaci n debe cumplir estrictamente todos los c digos normas y regla mentos aplicables Todos los cables de alimentaci n deben ingresar en el gabinete a trav s de los tapones desprendibles provisto...

Page 23: ...trola Este es un circuito de 24 VCA y se deben usar los m todos de cableado para la Clase 2 Use terminales de conexi n r pida de 1 4 in para hacer las conexiones de la bobina del contactor en el m dul...

Page 24: ...nectadas y ocurre un evento que motiva que una carga aumente m s all de la capacidad del generador la tarjeta OPCB identifica una condici n de sobrecarga e instant neamente restringe todas las cargas...

Page 25: ...Abierto Cerrado Com n a normalmente cerrado Cerrado Abierto NOTA Los contactos auxiliares tienen capacidades nominales de 10 A con 125 o 250 VCA NO EXCEDA EL VOLTAJE Y CORRIENTE NOMINALES DE LOS CONT...

Page 26: ...ferencia sea accionado el ctricamente Para comprobar la operaci n manual proceda como sigue 1 Aseg rese de que el generador est en modo OFF 2 Coloque en OFF u OPEN Abierto ambas fuentes de alimentaci...

Page 27: ...F LA ALIMENTACI N DE SERVICIO P BLICO ANTES DE REALIZAR TRABA JOS EN LAS CONEXIONES DE SERVICIO P BLICO DEL ATS PUEDE RESULTAR EN CHOQUE EL C TRICO EXTREMADAMENTE PELIGROSO Y POSIBLE MENTE MORTAL 3 Cu...

Page 28: ...El sistema esta ahora listo para funcionamiento autom tico 6 Coloque en OFF el suministro de alimentaci n del servicio p blico al interruptor de transferencia Con el generador listo para funcionar au...

Page 29: ...27 Notas...

Page 30: ...echos reservados Las especificaciones est n sujetas a cambios sin aviso No se permite la reproducci n bajo ninguna forma sin previo consentimiento escrito de Generac Power Systems Inc Generac Power Sy...

Page 31: ...Ce manuel doit rester avec l appareil Manuel du propri taire Interrupteur de transfert automatique SE 300 400 A Monophas CONSULTEZ TOUTE LA DOCUMENTATION APPROPRI E 29...

Page 32: ...fait de ne pas isoler un syst me lectrique l aide de tels moyens pourrait provoquer des dommages au g n rateur et galement entra ner des blessures ou la mort de travailleurs du r seau public en raiso...

Page 33: ...installation l utilisation et l entretien de cet quipement doivent tre effectu s par du personnel comp tent et qualifi Conformez vous strictement aux codes lectriques et de construction locaux provin...

Page 34: ...une alimentation en provenance d un r seau PUBLIC et d un G N RATEUR C est pour cette raison que le Code exige un tel commuta teur pour toutes les installations d alimentation de secours Le commutate...

Page 35: ...ci par l entremise de leurs fils de thermostat faible tension DEL d tat Affichent les charges qui peuvent actuellement tre mises en marche Connexions de charge Jusqu quatre charges de tout type peuven...

Page 36: ...ls L installation doit tre conforme tous les codes toutes les normes et toutes les r glementations Les c bles sous tension doivent tre achemin s dans le bo tier au moyen des entr es d fon ables cet ef...

Page 37: ...s charges Il s agit d un circuit 24 V a c Les m thodes utilis es pour le c blage doivent tre celles de la Classe 2 Utilisez des bornes connexion rapide de 0 25 po pour connecter la languette de connex...

Page 38: ...s de moindre importance sont c bl es aux contacteurs restants Load 3 et Load 4 L OPCB tableau de commande de pr vention de surcharge s il est pleinement fonctionnel et g re les six charges connect es...

Page 39: ...teur R seau public Veille Commun normalement ouvert Ouvert Ferm Commun normalement ferm Ferm Ouvert REMARQUE Les contacts auxiliaires supportent une tension de 10 A 125 ou 250 V c a NE PAS D PASSER LA...

Page 40: ...de transfert L utilisation manuelle doit tre v rifi e AVANT que le commutateur de transfert soit aliment Pour v rifier le fonctionnement manuel proc dez de la mani re suivante 1 Assurez vous que le g...

Page 41: ...rez travers les cosses N1 et N2 du CTA v rifiez galement N1 NEUTRE et N2 NEUTRE DANGER L OUBLI D TEINDRE L ALIMENTATION DU R SEAU PUBLIC AVANT DE COMMENCER TRAVAILLER SUR DES CONNEXIONS DU R SEAU PUBL...

Page 42: ...on service public 4 Mettez le disjoncteur du circuit principal du g n rateur sur MARCHE ou FERM 5 Sur le panneau du g n rateur s lectionnez le mode AUTO Le syst me est maintenant pr t au fonctionnemen...

Page 43: ...41 Remarques...

Page 44: ...s Les caract ristiques techniques sont modifiables sans pr avis Aucune reproduction n est autoris e sous quelque forme que ce soit sans le consentement crit pr alable de Generac Power Systems Inc Gen...

Reviews: