NOTE ON NEUTRAL BONDED GENERATORS:  

Some portable generators are intended for use on jobsites, and therefore are subject to OSHA regulations for GFCI protection on all receptacles. These 

"contractor grade" generators have their neutral wire bonded to the ground wire to pass OSHA inspection on job sites, and when connected to a transfer switch, this may cause nuisance tripping of the 
generator GFCI breaker.  If you’re using a neutral bonded generator to power a house or building through a transfer switch, then determine if the neutral bond wire on the generator can be disabled without 
voiding the warranty, preferably by a dealer or a qualified electrician.  NOTE: After this action, the generator will no longer pass OSHA inspection on job sites. Consult the manufacturer of your generator to 

determine if the neutral bond can be removed.  If it can be disabled, then no modifications to your transfer switch installation are needed.  If the neutral bond cannot be disabled or voids the generator 
warranty, you must install a Switched Neutral Kit (SNK) accessory with your transfer switch

 

TABLE 1 - SPECIFICATIONS 

Model: 

6295 or 6378 

6296 or 6380 

# Circuits Provided on Transfer Switch 

10 12 

Max # Circuits 

16 16 

REQUIRED BREAKER FOR MAIN LOAD CENTER (not incl) 

60 amp 2-pole 

100 amp 2-pole 

Utility Main Breaker 

60 amp 2-pole 

100 amp 2-pole 

Generator Main Breaker  

30 amp 2-pole 

60 amp 2-pole 

Breakers Provided with Unit 

3– 15 amp 1-pole 
3– 20 amp 1-pole 
1– 20 amp 2-pole 
1 --30 amp 2-pole 

3– 15 amp 1-pole 
3– 20 amp 1-pole 
1– 20 amp 2-pole 

1 --30 amp 2-pole 

1 – 50 amp 2-pole 

Max GEN Watts 

7500 continuous / 9000 surge 

12500 continuous / 18000 surge 

Max GEN Amps 

30 Amps 

60 amps 

Voltage 

125/250 Volts 

125/250 Volts 

NEMA Type Enclosure  

1 – Indoor Only 

1 – Indoor Only 

NEMA Configuration of Male Inlet in Power Inlet Box 

NEMA L14-30 

CS-6365 

Phase 

1 1 

Minimum Gauge Cord Size 

10/4 AWG 

6/4 AWG 

*Note: 

 If Ground Fault Circuit Interrupters (GFCI), Arc Fault Circuit Interrupters (AFCI), or Surge Protector Circuit Breakers were used as the branch circuit protector in the main load center, they 

MUST be used in the transfer switch.  GFCI and AFCI breakers require an isolated neutral connected from the load to the GFCI or AFCI.  The load neutral needs to be connected with a wire nut to a 
3-6 foot piece of white wire, run through the harness conduit to the transfer switch and connected to the "load neutral" lug or pigtail on the GFCI or ACFI breaker.  

Because GFCI and AFCI circuit 

breakers can take up more than one space, the overall maximum number of circuits may be reduced from the number shown.  

 

STEP 1:  PLANNING YOUR INSTALLATION: 

1.    Determine the appliances, circuits or equipment you want to operate with generator power during a power outage, such as: 

 

Refrigerator/Freezer,  

 

Furnace Blower (gas/oil only) 

 

TV / Radio 

 

Lighting 

 

Water Heater 

 

Garage Door Opener 

 

Microwave, Coffee Maker 

 

Well Pump 

 

Security System 

 

Sump Pump 

 

Computer, Fax and Printer, Phone 

 

Aquarium 

 

FIGURE 1:  TYPICAL INSTALLATION 

2.

 

Determine the amps required for each appliance by reading the label on the 
appliance.  IMPORTANT:  No appliance should have an amperage rating that 

exceeds the GEN MAIN breaker rating in the transfer switch (See Table 1).  The 
total amperage of all circuits can exceed the generator rating, but not all circuits 
will be able to be used concurrently.  

3.

 

Assign the circuit # in the load center to a circuit (A2, B2, etc.) in the transfer 
switch matching the size of the circuit breaker in the load center to the circuit 

breaker in the transfer switch.  Once you’ve determined which circuits you want 
to connect and the appropriate amperage, you will be ready to begin installing 
your transfer switch. 

 

4.

 

The location of your load center/electrical panel in your home or business 
will determine where the transfer switch will be installed.  Refer to Figure 1.  In addition to the transfer switch, this kit includes a generator cord and power inlet 
box.  You will use the generator cord to connect your generator to the power inlet box outdoors.  Whether your load center is in a basement, interior room or 
garage, we recommend installing power inlet box on the exterior of your house or building to avoid running generator cord through a door or window.  

5.

 

Determine where you will install the power inlet box on an exterior wall at least 5 feet from any openings (doors, windows, vents, etc.).  See Figure 1. 

Summary of Contents for GenTran 6295

Page 1: ...rmination positions for all branch circuits Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits Dual wattmeters help you monitor and balance the loads on your ge...

Page 2: ...be used in the transfer switch GFCI and AFCI breakers require an isolated neutral connected from the load to the GFCI or AFCI The load neutral needs to be connected with a wire nut to a 3 6 foot piece...

Page 3: ...ound bar on the left and install the white neutral wire into neutral bar on the right Using provided wiring connectors connect black wire from PIB to black wiring going to Meter A Repeat for red wire...

Page 4: ...Mount the power inlet box on the outside of the building in a convenient location minimum 24 above grade using the four holes provided in the back of the enclosure Use sealant around the anchoring scr...

Page 5: ...2 pole 100 amp Utility Main and a 2 pole 60 amp Generator Main Protected by US Patent No US 6 861 596 B2 Generac Power Systems Inc Toll Free 1 888 GENERAC www generac com 0197000SBY 2012 Generac Powe...

Page 6: ...du circuit de service ou de la g n ratrice qui peut tre dangereuse et viter ainsi tout d g t mat riel et de graves blessures des lectriciens Le bo tier peut tre encastr ou mont en surface l int rieur...

Page 7: ...loc neutre commut SNK avec le commutateur de transfert TABLEAU 1 CARACT RISTIQUES Mod le 6295 et 6378 6296 et 6380 Nombre de circuits disponibles sur le commutateur de transfert 10 12 Nombre maximum d...

Page 8: ...ter de faire passer le cordon de la g n ratrice travers une porte ou une fen tre 5 D cidez l endroit o vous installerez la bo te d entr e d alimentation sur un mur ext rieur au moins 5 pieds de toute...

Page 9: ...u commutateur de transfert et gardez les vis D fon ez les fentes de montage sur les c t s du bo tier et fixez le la charpente avec des clous ou des vis v rifiez que le bord avant du bo tier vient suff...

Page 10: ...limentation dans la bo te d entr e d alimentation ARR TEZ tous les disjoncteurs du commutateur de transfert 3 D marrez la g n ratrice l ext rieur en suivant les proc dures d crites dans le manuel du p...

Page 11: ...6296 et 6380 a un disjoncteur bipolaire de 100 amp res pour l installation de service principaleet un disjoncteur bipolaire de 60 amp res pour la g n ratrice Prot g par le brevet am ricain no US 6 86...

Page 12: ...s electricistas La caja puede instalarse a ras o sobre una superficie en interiores Mazo de cables prearmado con todos los cables marcados claramente para una f cil conexi n al centro de carga El inte...

Page 13: ...ida la garant a del generador se debe instalar un accesorio de kit neutral con interruptor SNK con su interruptor de transferencia TABLA 1 ESPECIFICACIONES Modelo 6295 y 6378 6296 y 6380 Cantidad de c...

Page 14: ...caja de entrada de cables el ctricos Usar el cable del generador para conectar su generador a la caja de entrada de cables el ctricos en el exterior Ya sea que su centro de carga se encuentre en un s...

Page 15: ...el centro de carga ENCIENDA todos los disyuntores de circuitos derivados en ambos paneles ENCIENDA el conducto PRINCIPAL DEL SERVICIO EL CTRICO en el interruptor de transferencia Verifique que la ele...

Page 16: ...uctos de ventilaci n o cualquier otra abertura El Mon xido de carbono CO de un generador es mortal y puede matarlo en minutos Lea y siga todas las instrucciones del generador antes de usarlo A Pasar d...

Page 17: ...y 6380 incluyen un conducto principal de servicio el ctrico de 2 polos y 100 amp y un conducto principal del generador de 2 polos y 60 amp Protegido por la Patente de los Estados Unidos N US 6 861 596...

Reviews: