11

2.11  LOW OIL LEVEL SHUTDOWN SYSTEM

The engine is equipped with a low oil level sensor that shuts down 
the engine automatically when the oil level drops below a specified 
level. If the engine shuts down by itself and the fuel tank has enough 
gasoline, check engine oil level.

2.11.1  SENSING LOW OIL LEVEL

If the system senses a low oil level during operation, the engine shuts 
down.  The  engine  will  not  run  until  the  oil  has  been  refilled  to  the 
proper level.

2.12   CHARGING THE BATTERY (ELECTRIC 

START UNITS ONLY)



 

Storage batteries give off explosive hydrogen gas while 
recharging. An explosive mixture will remain around the 
battery for a long time after it has been charged. The 
slightest spark can ignite the hydrogen and cause an 
explosion. Such an explosion can shatter the battery and 
cause blindness or other serious injury.

‹ 

 Do not permit smoking, open flame, sparks or any other 
source of heat around a battery. Wear protective goggles, 
rubber apron and rubber gloves when working around a 
battery. Battery electrolyte fluid is an extremely corrosive 
sulfuric acid solution that can cause severe burns. If spill 
occurs flush area with clear water immediately.

NOTE:

The battery shipped with the generator has been fully charged. 
A  battery  may  lose  some  of  its  charge  when  not  in  use  for 
prolonged periods of time. If the battery is unable to crank the 
engine, plug in the 12V charger included in the accessory box. 
RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY.

Use battery charger plug to keep the battery charged and ready for 
use. Battery charging should be done in a dry location.

1.  Plug  charger  into  “Battery  Charger  Input”  jack,  located  on  the 

control panel (Figure 12). Plug wall receptacle end of the battery 
charger into a 120 Volt AC wall outlet.

2.  Unplug  battery  charger  from  wall  outlet  and  control  panel  jack 

when generator is going to be in use.

NOTE:

Charge the battery at least once every three (3) months. Do not 
use  the  battery  charger  for  more  than  48  hours  at  one  charge. 
Charger input is protected by a 1.5 Amp replaceable in-line fuse.

Figure 12 - Battery Charger Jack

BATTERY

CHARGER

INPUT

3.1 

 PERFORMING SCHEDULED MAINTENANCE

It  is  important  to  perform  service  as  specified  in  the  Maintenance 
Schedule  for  proper  generator  operation,  and  to  ensure  that  the 
generator  complies  with  the  applicable  emission  standards  for  the 
duration of its useful life. Service and repairs may be performed by 
any  capable  person  or  repair  shop.  Additionally,  emissions  critical 
maintenance  must  be  performed  as  scheduled  in  order  for  the 
Emissions  Warranty  to  be  valid.  Emissions  critical  maintenance 
consists of servicing the air filter and spark plugs in accordance with 
the Maintenance Schedule. 

3.2 

MAINTENANCE SCHEDULE

Follow the calendar intervals. More frequent service is required when 
operating in adverse conditions noted below.

Check Oil Level 

At Each Use

Change Oil ‡ 

*Every 100 hours or Every Season

Check Valve Clearance 

***Every Season

Service Air Filter 

** Every 200 hours or Every Season

Replace Spark Plug 

Every Season

‡  Change oil after first 30 hours of operation then every season.
*  Change oil and oil filter every month when operating under heavy load or in high 

temperatures.

**  Clean more often under dirty or dusty operating conditions.  Replace air filter parts 

if they cannot be adequately cleaned.

***   Check valve clearance and adjust if necessary after first 50 hours of operation and 

every 100 hours thereafter.

3.3 

PRODUCT SPECIFICATIONS

3.3.1  GENERATOR SPECIFICATIONS

Rated Power ..................................................................................... 8.0 kW**
Surge Power ......................................................................................... 10 kW
Rated AC Voltage .............................................................................. 120/240
Rated AC Load
  Current @ 240V ....................................................................... 33.3 Amps**
  Current @ 120V ....................................................................... 66.6 Amps**
Rated Frequency ............................................................ 60 Hz @ 3600 RPM
Phase ........................................................................................ Single Phase
Unit Weight .............................................................................. 86.9kg (191.5)
Unit Dimensions ............................L = 692mm (27.25") x W = 687mm (27") x 

H = 638mm (25")

**  Operating Temperature Range : -18 deg. C (0 deg. F) to 40 Deg. C (104 Deg. F). 

When operated above 25 deg. C (77 deg. F) there may be a decrease in power.

**  Maximum wattage and current are subject to, and limited by, such factors as fuel 

Btu content, ambient temperature, altitude, engine condition, etc.. Maximum power 
decreases about 3.5% for each 1,000 feet above sea level; and will also decrease 
about 1% for each 6° C (10° F) above 16° C (60° F) ambient temperature.

Maintenance

Summary of Contents for 0065141C

Page 1: ...r www generac com or 1 888 436 3722 DEADLY EXHAUST FUMES ONLY use OUTSIDE far away from windows doors and vents NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS SAVE this Manual Provide this...

Page 2: ...nits Only 11 Maintenance 11 3 1 Performing Scheduled Maintenance 11 3 2 Maintenance Schedule 11 3 3 Product Specifications 11 3 4 General Recommendations 12 3 5 Service Air Filter 13 3 6 Valve Clearan...

Page 3: ...g technique that the manufacturer does not specifically recommend ensure that it is safe for others Also make sure the procedure work method or operating technique utilized does not render the generat...

Page 4: ...tical to correct generator operation Do not alter the installation or permit even partial blockage of ventilation provisions as this can seriously affect safe operation of the generator The generator...

Page 5: ...ntilation of the generator Do not insert objects through unit s cooling slots Never operate the generator if connected electrical devices overheat if electrical output is lost if engine or generator s...

Page 6: ...Refer to Figure 1 and install the Frame Foot and Rubber Bumpers as shown Slide the Rubber Bumper studs through the Frame Foot then install the Locking Flange Nuts Slide the Hex Head Bolts through the...

Page 7: ...Amp single phase 60 Hz electrical lighting appliance tool and motor loads 3 Circuit Breakers AC Each receptacle is provided with a push to reset circuit breaker to protect the generator against elect...

Page 8: ...off when the engine is running This signifies that the meter is tracking hours of operation 2 3 CONNECTION PLUGS 2 3 1 120 VAC 20 AMP GFCI DUPLEX RECEPTACLE This is a 120 Volt outlet protected agains...

Page 9: ...n of the generator The generator MUST be operated outdoors This exhaust system must be properly maintained Do nothing that might render the exhaust system unsafe or in noncompliance with any local cod...

Page 10: ...rt the largest motor 2 Add to that figure the running watts of all other connected loads The Wattage Reference Guide is provided to assist in determining how many items the generator can operate at on...

Page 11: ...g open flames sparks or heat in the vicinity while handling gasoline 1 Use regular UNLEADED gasoline with the generator engine Do not use any gasoline with more than 10 added ethanol Do not use E85 ga...

Page 12: ...in to the Run position If engine falters move choke knob back out to 1 2 Choke position until the engine runs smoothly and then to Run position 2 9 1 MANUAL START This generator is also equipped with...

Page 13: ...er input is protected by a 1 5 Amp replaceable in line fuse Figure 12 Battery Charger Jack BATTERY CHARGER INPUT 3 1 PERFORMING SCHEDULED MAINTENANCE It is important to perform service as specified in...

Page 14: ...on the generator internal windings will eventually decrease the insulation resistance of these windings 3 4 2 TO CLEAN THE GENERATOR Use a damp cloth to wipe exterior surfaces clean A soft bristle br...

Page 15: ...before re installing it NOTE To order a new air filter please contact the nearest authorized service center at 1 888 436 3722 Figure 15 Air Filter KNOB TO OPEN AIR BOX 3 6 VALVE CLEARANCE Intake 0 15...

Page 16: ...e the unit in a clean dry place 3 9 OTHER STORAGE TIPS Do not store gasoline from one season to another Replace the gasoline can if it starts to rust Rust and or dirt in the gasoline will cause proble...

Page 17: ...Low oil level 10 Excessive rich fuel mixture 11 Intake valve stuck open or closed 12 Engine has lost compression 1 Turn Fuel Shut off ON 2 Clean or replace air filter 3 Fill fuel tank 4 Drain fuel tan...

Page 18: ...MENT SERVICE PARTS Description Part No Oil Quart 0G0752 Spark Plug 0G84420101 Air Filter 0G84420151 Fuel Filter 0H1326 Battery 0G9449 Battery Fuse 0K3029 Spark Arrestor 0K3857 Maintenance Kit 005577 0...

Page 19: ...17 Notes...

Page 20: ...10 07 14 Printed in U S A 2014 Generac Power Systems Inc All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from...

Page 21: ...m o 1 888 436 3722 PELIGRO EMANACIONES DE ESCAPE MORTALES Use NICAMENTE EN EXTERIORES lejos de ventanas puertas y ventilaciones NO EST N DESTINADOS AL USO EN APLICACIONES CR TICAS DE SOPORTE A LA VIDA...

Page 22: ...uci n del mantenimiento programado 11 3 2 Programa de mantenimiento 11 3 3 Especificaciones del producto 11 3 4 Recomendaciones generales 12 3 5 Servicio del filtro de aire 13 3 6 Luz de v lvulas 13 3...

Page 23: ...cnica de funcionamiento que el fabricante no recomienda espec ficamente aseg rese de que sea seguro para otras personas Aseg rese tambi n de que el procedimiento m todo de trabajo o t cnica de funcio...

Page 24: ...ciones suficientes puede causar inconsciencia o incluso la muerte El flujo adecuado y sin obstrucciones de aire de enfriamiento y ventilaci n resulta cr tico para el funcionamiento adecuado del genera...

Page 25: ...use el generador si los dispositivos el ctricos conectados se recalientan si se pierde la salida el ctrica si el motor o el generador producen chispas o si se observan llamas o humo mientras la unida...

Page 26: ...lte la Figura 1 e instale el pie del bastidor y los parachoques de caucho como se muestra Deslice los esp rragos de los parachoques de caucho a trav s del pie del bastidor e instale las contratuercas...

Page 27: ...30 A monof sicos de 60 Hz 3 Disyuntores CA Cada tomacorriente cuenta con un disyuntor de pulsar para reconectar para proteger al generador contra sobrecargas el ctricas 4 Vaciado de aceite Se usa para...

Page 28: ...llevando un registro de las horas de funcionamiento 2 3 ENCHUFES DE CONEXI N 2 3 1 TOMACORRIENTE DOBLE DE 120 VCA 20 A GFCI Es un tomacorriente de 120 V protegido contra sobrecargas por un disyuntor...

Page 29: ...er inseguro al sistema de escape o que infrinja cualquier c digo y o norma local Siempre use en interiores una alarma de mon xido de carbono alimentada por bater a instalada conforme a las instruccion...

Page 30: ...ios de consumo funcionando de todas las otras cargas conectadas La gu a de referencia de potencia en vatios se provee para asistir en la determinaci n de cu ntos elementos puede accionar el generador...

Page 31: ...que se fume o que haya llamas abiertas chispas o calor en la zona mientras maneje gasolina 1 Use gasolina com n SIN PLOMO en el motor del generador No use ninguna gasolina con m s de 10 de etanol a a...

Page 32: ...y luego a la posici n de funcionamiento Si el motor falla intermitentemente tire de la perilla del cebador nuevamente a la posici n de medio cebado hasta que el motor funcione suavemente y luego a la...

Page 33: ...1 5 A sustituible Figura 12 Conector del cargador de bater a BATER A ENTRADA DEL CARGADOR 3 1 EJECUCI N DEL MANTENIMIENTO PROGRAMADO Es importante ejecutar el mantenimiento como se indica en el Progra...

Page 34: ...el aislamiento de estos devanados 3 4 2 LIMPIEZA DEL GENERADOR Use un pa o h medo para limpiar las superficies exteriores Se puede usar un cepillo de cerdas suave para aflojar tierra compactada aceite...

Page 35: ...es de volver a instalarla NOTA Para pedir un filtro de aire nuevo comun quese con el centro de servicio autorizado m s cercano llamando al 1 888 436 3722 Figura 15 Filtro de aire PERILLA PARAABRIR LA...

Page 36: ...cuentren abiertas y sin obstrucciones 8 Almacene la unidad en un lugar limpio y seco 3 9 OTROS CONSEJOS SOBRE EL ALMACENAMIENTO No almacene gasolina de una estaci n a otra Sustituya el contenedor de g...

Page 37: ...de admisi n se encuentra atorada abierta o cerrada 12 El motor ha perdido compresi n 1 Gire la v lvula de cierre de combustible a la posici n ON 2 Limpie o sustituya el filtro de aire 3 Llene el tanq...

Page 38: ...cripci n N m de pieza Aceite cuarto de gal 0G0752 Buj a 0G84420101 Filtro de aire 0G84420151 Filtro de combustible 0H1326 Bater a 0G9449 Fusible de bater a 0K3029 Supresor de chispas 0K3857 Kit de man...

Page 39: ...17 Notas Notas...

Page 40: ...Impreso en EE UU 2014 Generac Power Systems Inc Todos los derechos reservados Las especificaciones est n sujetas a cambios sin aviso No se permite la reproducci n bajo ninguna forma sin previo consen...

Reviews: