L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
WI994C 3/04
!
Page 41
Time and Date (Keypad) in Dealer Program Mode
The Keypad Time and Date on the GEM-RP1CAe2/GEM-K1CA keypad may be set in Dealer Program Mode.
Time and Date (Keypad) in User Program Mode
When using an GEM-RP1CAe2/GEM-K1CA with firmware version 6, the Time and Date may be set in the User Program Mode.
Time and Date Message Option
In the event of a complete power failure (AC and DC) and the loss of the system clock, when the system is re-powered, a message
‘SET TIME / DATE” will be displayed on the GEM-RP1CAe2 keypad. The message will remain until the Time and Date have been re-
programmed.
Touch-tone Dialing Only; TouchTone Dialing with Rotary Backup
Select “TouchTone Dialing Only” (Address 0394) if the subscriber has TouchTone service. TouchTone dialing is faster than rotary
dialing, but not always as reliable.
For the communicator to use TouchTone on all dial attempts, program TouchTone Dialing Only. To use TouchTone on the first attempt
with subsequent Rotary dial, program TouchTone Dialing with Rotary Backup. TouchTone Dialing Only will override TouchTone Dialing
with Rotary Backup if both are selected. Note that if Backup Reporting is also selected, the communicator will alternate between
TouchTone and rotary dial to reach Telephone 1, then Telephone 2. See Backup Report on Telco 2.
Trouble; Fire Trouble
An abnormal zone condition (a break in a normally-closed loop; a short on a normally-open loop; or either on an end-of-line-resistor
supervised loop) when disarmed.
Trouble on a Burglary Zone is automatically displayed at the keypad unless Disable Zone Fault Scrolling is programmed. If a Burglary
Zone is in trouble, it will go into alarm about 10 seconds after arming. However, if Auto Bypass is programmed, the keypad will beep
upon arming (does not apply to selective- or group-bypassed zones).
Trouble (open and/or short circuit) on a Day Zone is indicated by a pulsing sounder; display the Day Zone(s) in trouble on the LCD.
Keypad indications are reset by the
C
button unless Reset Day Zone With Arm/Disarm is selected.
Trouble on a Fire Zone will be indicated by the “
FIRE/TRBL
” reminder and the sounder. An open circuit (trouble) will cause a flashing
“
SYSTEM TROUBLE/E41-00 SERVICE
” display and a pulsing sounder after a 15-second delay. (A short circuit will cause an alarm condition:
steady-on “
FIRE ALARM
” display and pulsing sounder). The
C
button will silence the sounder. Clear the trouble, then press the the
C
button once again. The keypad will reset after a brief delay.
Trouble on Open; Trouble on Short
(Not for UL installations)
Trouble on Open will identify an open circuit on a loop as a trouble. Trouble on Short will identify a short circuit as a trouble. While
there will be no indication at the keypad, any of these trouble conditions can be reported if Report Trouble is programmed as well.
Note:
For use on Burg type Zones only. Not for use with 24-Hour Protection feature.
Trouble/Trouble Restore Telco 1/Telco 3
See Report Telco 1/Telco 3
Trouble/Trouble Restore Telco 2
See Backup Report on Telco 2
Two-Digit Format
See Data Format
Two-Wire Smoke Detectors
See Smoke Detectors
Glossar
y
TIME(1)
UNITS
MAX. PROG. TIME
ADDRESS
PGM2 OUTPUT TIMEOUT
MIN.
UNTIMED(2)
0710
PGM2 OUTPUT ACCESS CONTROL TIME
SEC.
4 MIN, 15 SEC (255 SEC)
0711
ALARM OUTPUT
MIN.
UNTIMED(1)(2)
0712
PULSE-BURG OUTPUT
MIN.
UNTIMED(1)(2)
0713
PGM1 OUTPUT
MIN.
UNTIMED(2)
0714
ABORT DELAY
SEC.
4 MIN, 15 SEC (255 SEC)(3)
0715
CHIME TIME
SEC.
63.25 SEC (255 QTR-SEC)(3)
0716
AC-FAIL REPORT DELAY
10 MIN.
42 HR, 30 MIN (2550 MIN)
0717
EXIT DELAY
SEC.
4 MIN, 15 SEC (255 SEC)(4)
0000
ENTRY DELAY 1
SEC.
4 MIN, 15 SEC (255 SEC)(4)
0001
ENTRY DELAY 2
SEC.
4 MIN, 15 SEC (255 SEC)(4)
0002
SENSOR WATCH
HRS
254 HRS
1059
CANCEL WINDOW
VERSION 10 - MIN
VERSION 9A - SEC
VERSION 10 - 254 MIN
VERSION 9A - 254 SEC
1179